Read Performance and cost-benefit analysis of an integrated earth-air heat exchanger and air handling unit system by Naim Ben Ali, Joy Djuansjah, Ihab Omar, As’ad Alizadeh, Shaymaa Abed Hussein, Walid Aich, Rashid Khan, Milad Faraji (2025) in the Tower of Babel, a free online library of public-domain works preserved in clean, searchable text. No sign-up. The full text is served as a plain-text file at a predictable URL, where text is present: https://antarctic-labs.com/tower-of-babel/pmc-12819528.txt.

Description

Ben Ali and co-authors model a cooling system that pipes air underground before it enters a building, in a 2025 paper. Earth-air heat exchangers use the soil's steady temperature to trim air-conditioning loads. The team tested how pipe shape, burial depth, and wall thickness shape both cooling power and cost.

Rectangular pipes cooled best, reaching eighty-five percent efficiency and cutting air temperature by up to ten and a half degrees. Burying pipes four meters deep nearly doubled compressor savings compared with one meter. A fifteen-meter rectangular pipe buried three to four meters deep balanced savings, about thirty-eight percent, against a payback of under four years.

Catalog record

CREATORNaim Ben Ali, Joy Djuansjah, Ihab Omar, As’ad Alizadeh, Shaymaa Abed Hussein, Walid Aich, Rashid Khan, Milad Faraji
YEAR2025
COLLECTIONPAPERS
FORMATTXT
FILE SIZE118 KB
VERSION1.0
LICENSECC BY 4.0
RIGHTSCC BY
SOURCEEurope PMC

Source: https://europepmc.org/articles/PMC12819528