Performance and cost-benefit analysis of an integrated earth-air heat exchanger and air handling unit system Authors: Naim Ben Ali, Joy Djuansjah, Ihab Omar, As’ad Alizadeh, Shaymaa Abed Hussein, Walid Aich, Rashid Khan, Milad Faraji Published: 2025 ABSTRACT Earth-Air Heat Exchanger (EAHE) systems present a sustainable solution to reduce the energy consumption of HVAC systems by utilizing stable subsurface temperatures for passive air conditioning. This study investigates the performance of an EAHE integrated with a central air conditioning system, focusing on the effects of pipe geometry, burial depth, cross section of pipe and thickness on thermal efficiency and economic viability. Despite extensive studies on EAHE systems, gaps remain in understanding the combined impact of pipe cross-section, thickness, and burial depth on system performance and cost-effectiveness. This study addresses these gaps by evaluating four pipe cross-sections (circular, square, rectangular, hexagonal) at varying depths (1–4 m) and thicknesses (5–20 mm) using a validated transient thermal model. A comprehensive analytical model was developed and validated against experimental and computational data to assess energy savings and operational benefits. The study employed an integrated MATLAB/EES-based computational framework to conduct a continuous parametric and economic analysis. This analytical approach systematically evaluated the effects of pipe geometry, burial depth, and thickness on the system’s thermal performance and financial viability. Results show that rectangular pipes (410 mm perimeter) achieve the highest cooling efficiency (85%), reducing outlet air temperature by up to 10.5 °C compared to ambient conditions. Burial depth significantly influences performance, with 4 m depth yielding 38.2% compressor power savings nearly double that of 1 m depth (19.9%). Pipe length optimization reveals diminishing returns beyond 15 m, where 34.2% power savings are achieved with a 3.8-year payback period. Economic analysis identifies the 15 m rectangular pipe at 3–4 m depth as the optimal configuration, balancing efficiency (38.2% savings) and cost (payback: 3.8 years). These findings provide actionable insights for designing energy-efficient EAHE systems in HVAC applications. Introduction Energy is essential to economic growth. As the world’s population expands rapidly, so does the need for energy1. According to Bansal et al.2, maintaining interior thermal comfort using air conditioning (AC) systems accounts for around 20% of global energy use. By 2050, it is anticipated that there will be 250% more AC systems, resulting in a 300–400% rise in energy consumption3. In order to meet the growing energy demands of the global economy, it will be crucial to use renewable energy sources like solar, nuclear, biofuels, and geothermal energy as substitutes for fossil fuels4. New guidelines about HVAC systems recommend maximizing fresh air intake to 100% in enclosed spaces and minimizing recirculated air, which leads to higher cooling and heating demands and, in turn, greater energy consumption5. Environmental damage will increase along with increased energy use if there isn’t a strong push to develop renewable resources in the near future. By using the ground as a thermal reservoir to condition outside air, earth-air heat exchangers (EAHEs) have been developed as a way to reduce the heating and cooling requirements of central air conditioning systems6. In order to pull outside air via a system of pipes placed at a certain depth underground, an EAHE uses a fan. Depending on the season, the surrounding earth, which is warmer or colder than the air above, exchanges heat with the air as it passes through these pipes. By reducing the temperature differential between the interior and outdoor environments, this pre-heating or pre-cooling technique helps to reduce the strain on a building’s air conditioning system2,4,6,7. The efficiency of Earth Air Heat Exchanger (EAHE) systems under various circumstances has been evaluated using parametric analysis. A semi-analytical model operating in transient cooling situations has been used to anticipate the performance of these systems8,9. It was discovered that whereas variables like flow rate and pipe diameter have an inverse connection with the drop in air temperature, soil thermal conductivity and pipe length have a direct association10,11. Furthermore, the effect of air velocity inside the pipes has been investigated, and it has been shown that the best cooling results are obtained at a velocity of 1.5 m/s12. According to research, the temperature decrease across the Earth-Air Heat Exchanger (EAHE) may be increased by employing thinner pipes13,14. The EAHE system’s installation led to a 2 °C increase in winter temperatures and an 8 °C decrease in summer temperatures15. Furthermore, a research found that using lower air velocities and longer, smaller pipes enhances EAHE performance16. According to numerical simulations, when the air flow velocity inside the pipes rises, the derating factor for an EAHE system decreases17. Moreover, the rate of heat transmission between the soil and the air is strongly influenced by soil moisture18. In order to evaluate an EAHE’s performance during both continuous and transient operations, three distinct soil types were used to mimic it. The results showed that transient operation improves performance by 1.81%19. Through numerical simulations, the properties of the air inside the EAHE pipe which is buried at different depths were examined20. According to their research, the greatest temperature change occurred at a depth of 3 m, with summer temperatures of 8.5 °C and winter temperatures of 4.2 °C. Furthermore, by using a three-dimensional model, Shojaee et al.21 examined how climate affects an EAHE system’s efficiency. According to their findings, the EAHE system saves 1.8 times as much energy in difficult climes as it does in gentler ones. In order to evaluate the annual efficiency of Earth Air Heat Exchangers (EAHE) in a hot, dry climate, Bisoniya et al.22 developed a three-dimensional model. According to Xamán et al.23, a two-dimensional numerical simulation that looked at the heat transmission between the pipe and the surrounding soil showed that the EAHE system did better thermally in soils with higher thermal inertia. Furthermore, practical and computational investigations on the effects of burying EAHE pipes two meters below the surface of short grass were carried out by Pakari and Ghani24. They recommended using aluminum pipes and found that the system’s effectiveness is greatly impacted by the soil’s moisture level and thermal conductivity. The efficiency of Earth Air Heat Exchanger (EAHE) systems in conjunction with central air conditioning units has been studied by several researchers. The effect of a double-layer EAHE system on a fresh air handling unit’s efficiency was examined experimentally in a research by Li et al.4. According to their research, the EAHE system may reduce greenhouse gas emissions by 82.5% during a 2.38-year payback time. Furthermore, a numerical examination of the effects of burial depth on the EAHE system’s performance in conjunction with air conditioning at three distinct sites was carried out by Hermes et al.6. They came to the conclusion that, in comparison to depths of 1–3 m, the thermal effect was more noticeable at 4–5 m. When combined with an air conditioner, the EAHE system functions as a heat pump. When an effective fan was used, they discovered that the system’s expenses were recouped in two years. In the hot environment of southern Algeria, an EAHE system placed in a residential structure demonstrated an annual energy savings of 246.82 kWh and a maximum temperature drop of 20.7 °C25. They concentrated on how much the system lowers CO2 emissions and energy use per year. In January, the system’s greatest heat gain was 191 kWh, while in May, it achieved a maximum heat decrease of 247.25 kWh. Emissions of CO2 were cut by 101 tons. A comparison of the energy usage of a conventional air conditioner and an AC unit with an EAHE system for controlling the workplace environment revealed a 75% decrease in the system’s lifetime CO2 emissions and an annual energy savings of 3456 kWh26. A dynamic energy modeling code was used to examine the impact of utilizing an EAHE system in conjunction with HVAC27. It was discovered that energy use may be decreased by 29% in the winter and 46% in the summer. In Milan and Palermo, the combination of the EAHE system and the AC resulted in a decrease in CO2 emissions28. With a payback period of seven and five years for Milan and Palermo, respectively, the study’s dynamic energy modeling revealed that yearly energy savings reached 74% in Milan and over 60% in Palermo. In Naples, Italy, the same team conducted a numerical study on the impact of combining the EAHE system with AHU29,30. They discovered that during the summer, a 60–70% power decrease is achievable. In the winter, when the pipe was 100 m long and 0.2 m in diameter, the decrease was 46%. According to Li et al.31 the effective/optimal length is the distance at which heat transmission between the soil and airflow does not significantly increase. The point at which the temperature differential between the tunnel wall and the air within the tube exceeds 0.5 °C is the effective length for deep underground tunnels, according to Guo et al.32 analytical techniques were used to establish the ideal length depending on the particular circumstances and accuracy standards. A novel vertical air-soil heat exchanger (VASHE) integrated with phase change materials (PCMs) was developed, achieving higher energy efficiency and more stable outlet temperatures than traditional systems. An accurate enthalpy-based model was validated experimentally, showing a maximum prediction error of just 1.98%. Parametric analysis identified RT 20 in a tubular configuration as the optimal PCM, effectively minimizing outlet temperature fluctuations. This integrated geothermal system provides concrete guidance for advancing efficient and compact geothermal energy utilization in buildings . Although EAHEs are not yet a fully developed technology, the literature assessment above indicates that EAHE systems have a lot of promise for widespread use. Up until now, the literature has concentrated on theory and the impacts of various characteristics, such as soil qualities and velocity, on a system with a fixed number of pipes. To elucidate the impact of pipe thickness, pipe cross-section and depth of buried pipe performance, more study is required. This study demonstrates that integrating a Rectangular Earth-Air Heat Exchanger (EAHE) with a central Air Handling Unit (AHU) in a hot-arid climate achieves significant energy savings, reducing compressor power consumption. Furthermore, this direct reduction in energy demand from the grid-based HVAC system translates to a substantial decrease in carbon footprint, with the model indicating a reduction of approximately 101 tons of CO2 emissions annually in a representative residential application, thereby strengthening the environmental and economic case for adoption. The findings underscore that strategic EAHE implementation offers a viable path toward sustainable building climate control, simultaneously delivering operational cost savings and a direct contribution to carbon emission reduction goals. A mathematical model of the energy balance of an EAHE system coupled with a central air conditioning system is presented in this work to close this gap and take into account how various pipe characteristics affect the system’s cost and energy performance. The research is set in the hot-arid climate of Abha, Saudi Arabia, where summer conditions feature high ambient temperatures averaging above 30 °C with low relative humidity, often below 40%. Spring presents moderately warm temperatures with similarly low humidity levels, creating a consistent and significant cooling demand. This specific climatic profile, defined by these distinct seasonal averages, is essential for reproducible thermal performance analysis. The model’s inputs and resulting energy savings are directly benchmarked against these realistic and challenging environmental conditions. We utilize the Center for Fitness club in Abha, Saudi Arabia as a case study to illustrate how a proposed EAHE system and a 25-TR central AC system (CLIMATECH AHX-25T) can completely chill an operating room with fresh air. While extensive research exists on Earth-Air Heat Exchangers (EAHE), significant gaps remain in understanding the combined impact of pipe cross-section, thickness, and burial depth on both thermal performance and economic viability. This study addresses these gaps by conducting a comprehensive parametric and economic analysis of an EAHE integrated with an Air Handling Unit (AHU). This study aims to develop and validate a transient analytical model to investigate the integrated performance of an Earth-Air Heat Exchanger (EAHE) within a central air conditioning system. The primary objectives are to conduct a comprehensive parametric analysis evaluating the effects of pipe cross-section, burial depth, and pipe thickness on thermal efficiency and to perform a detailed economic assessment to determine the system’s cost-effectiveness and optimal payback period. Model description Figure 1a shows a schematic view of the combination of two EAHE systems and an air handling unit (AHU). The EAHE system is placed horizontally and at depths of 1 to 4 m in the ground. The inlet and outlet fluids pass through a vertical path, while the main heat transfer pipes are placed in the basement in parallel and horizontally at specific and fixed intervals. Heat transfer from the soil to the pipes is transferred to the air inside the pipe through two phenomena of conduction and convection. The air inside the pipe flows through two fans at the beginning and end of the path. The air inside the pipe first passes through the EAHE system. Then, with a decrease in temperature, it enters the air handling unit and, after complete cooling and dehumidification, is directed into the gym environment by the inlet fan. The air supplying the building’s cooling after exchanging heat with the environment through the outlet fan and passing through the air filter enters the EAHE system, and this cycle is repeated continuously. Figure 1b also shows a psychrometric chart for predicting and calculating the heat load consumption of a combination of two EAHE and AHU systems. This chart helps visualize how the EAHE system modifies the thermodynamic properties of incoming air before it enters the AHU, reducing the cooling load on the central air conditioning system. The shaded area between the process lines (A→B→C) represents the energy savings achieved by the EAHE system. Without EAHE, the AHU would need to cool air directly from Point A to Point C, requiring more energy. EAHE system optimizes HVAC performance by leveraging geothermal cooling. The psychrometric chart serves as a design and analysis tool to quantify energy savings and thermal comfort improvements. Fig. 1(a) Diagram illustrating the setup of the EAHE system integrated with an AHU and (b) Psychrometric chart of cooling load changes using the EAHE system. (a) Diagram illustrating the setup of the EAHE system integrated with an AHU and (b) Psychrometric chart of cooling load changes using the EAHE system. The selection of Abha, Saudi Arabia, as the case study location is strategically justified by its distinct hot-arid climate, characterized by high ambient temperatures and significant cooling demands, which creates an ideal high-stress scenario for evaluating the EAHE’s performance. Furthermore, the local compacted clay soil, with its specific thermal properties including a conductivity of 1.74 W/(m °C) and a diffusivity of 8 × 10−7 m2/s, provides a well-defined and reproducible geothermal reservoir. This combination of challenging climatic loads and stable, measurable soil characteristics ensures that the model’s predictions of energy savings and outlet temperatures are both rigorously tested and representative of real-world conditions where such passive cooling systems are most beneficial. Types of cross-sections In the pipe cooling operations of Earth-Air Heat Exchanger (EAHE) systems, various cross-sectional shapes are utilized to enhance heat transfer efficiency. Common options include circular, rectangular, and elliptical profiles, each offering unique benefits. Circular pipes promote uniform flow distribution and simplify installation, making them the most frequently used choice. Rectangular and elliptical cross-sections can provide larger surface areas for heat exchange, thereby improving cooling performance. The selection of a particular shape depends on factors such as spatial limitations, soil conditions, and the desired thermal efficiency. Additionally, multi-layer or composite cross-sections are sometimes adopted to boost insulation and thermal transfer capabilities. The shape of the pipe influences flow behavior and heat transfer characteristics, which in turn affect the overall effectiveness of the system. Choosing the appropriate cross-sectional shape is essential for maximizing cooling efficiency while reducing material costs and installation challenges. Ultimately, understanding the different cross-sectional options assists in designing more effective EAHE cooling systems tailored to specific project requirements. In this study, four different cross-sectional shapes of cooling pipes in the EAHE system were used, including circular, square, rectangular, and regular hexagonal cross-sections. The internal area of ​​all cases is equal and is approximately 78 cm2. Figure 2. Shows a view of the cross-sectional shapes studied in this study. Fig. 2View of the cross-sectional shapes. View of the cross-sectional shapes. Table 1 shows the geometric characteristics of four EAHE system pipes with different cross-sections. The thickness of the pipes is assumed to be 10 mm. To investigate and optimize pipes with different cross-sections, the internal area of ​​all pipes is assumed to be the same. The pipes are made of a type of PVC with high resistance to pressure and good surface smoothness. The pipes are placed in parallel below the ground surface at depths of 1 m, 2 m, 3 m, and 4 m. Each pipe is 15 m long, and only one pipe is placed at each depth in the soil. The length of all pipes is assumed to be 15 m. Also, the perimeter of the pipes varies according to the different cross-sections, with circular, square, rectangular, and hexagonal cases having perimeters of P = 314 mm, P = 352 mm, P = 410 mm, and P = 318 mm, respectively. The pipe perimeter plays an important role in the heat transfer between the working fluid inside the pipe and the soil environment. As the external perimeter of the pipes increases, the heat transfer surfaces with the soil increase, resulting in a greater amount of cooling being transferred to the cooling fluid in the building environment. Table 1Pipe geometric and dimensional specifications in the EAHE system.Pipe typeDimension (mm)Perimeter (mm)MaterialThickness (mm)Circulard = 100314PVC10Squarea = 88352Rectangular50 \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\times$$\end{document} 155410Hexagonala = 53318 Table 1Pipe geometric and dimensional specifications in the EAHE system.Pipe typeDimension (mm)Perimeter (mm)MaterialThickness (mm)Circulard = 100314PVC10Squarea = 88352Rectangular50 \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\times$$\end{document} 155410Hexagonala = 53318 Pipe geometric and dimensional specifications in the EAHE system. Thickness and depth of pipe The effectiveness of an Earth-to-Air Heat Exchanger (EAHE) system in cooling operations is significantly influenced by the thickness of the pipe and the depth at which it is buried underground. Thinner pipes generally possess a less thermal mass, allowing them to absorb and transfer heat more effectively, thereby enhancing the overall heat exchange process. This decreased thickness can improve the system’s durability and reduce heat loss, contributing to more efficient cooling performance. It should also be noted that as the pipe thickness decreases, the amount of soil pressure and changes in the displacement of soil layers on the pipes increases, which increases the risk of pipe failure. Conversely, the depth of burial plays a crucial role in maintaining consistent thermal conditions; pipes buried at greater depths are subjected to more stable underground temperatures, which tend to be lower and less affected by surface temperature fluctuations33. This stability ensures a more reliable heat transfer, facilitating effective cooling during hot weather conditions. Shallow burial, on the other hand, exposes the pipe to ambient temperature variations, which can diminish the system’s cooling efficiency. Additionally, deeper placement reduces the impact of seasonal and diurnal temperature changes, leading to a more consistent cooling effect. However, increasing the depth also involves higher installation costs and logistical challenges. Furthermore, the interplay between pipe thickness and burial depth determines the overall thermal resistance of the system, affecting the rate of heat transfer between the ground and the air passing through the pipe. Optimizing both parameters can maximize the cooling potential of the EAHE system, ensuring energy-efficient operation and enhanced thermal comfort33. Proper design considerations must balance these factors to achieve a sustainable and cost-effective cooling solution, especially in regions with significant temperature variations. In summary, thinner pipes and deeper burial depths generally improve the thermal performance of EAHE systems by providing greater thermal stability and resistance, but these benefits must be weighed against practical constraints such as installation costs and site-specific conditions. Fig. 3Boundary conditions of air flow inside the pipe in the EAHE system. Boundary conditions of air flow inside the pipe in the EAHE system. Fig. 4Schematic of the placement of the combination of two EAHE and AHU systems at different soil depths. Schematic of the placement of the combination of two EAHE and AHU systems at different soil depths. Figure 3. Shows a view of the boundary conditions of the pipe buried in the soil and the cooling fluid of the EAHE system. For optimization and thermal analysis of the heat transfer process between the soil and the working fluid, three parameters of soil depth, pipe thickness and pipe cross-sectional shape have been investigated. The pipe thickness includes four levels of 5 mm, 10 mm, 15 mm and 20 mm. Also, the depth of the pipes buried in the soil has been investigated at four levels of 1 m, 2 m, 3 m and 4 m that a view of the combination of the EAHE system and AHU at the four desired depths is shown in Fig. 4. Mathematical equations The following subsections introduce the calculation of soil temperature, analyze the EAHE, and describe the model to predict the power consumption of the AHU. Heat-transfer analysis is used to evaluate the temperature of air exiting the EAHE. The temperature and air velocity in the pipes, as well as the thermal characteristics of the ground and the pipes, are all included in the study. Soil temperature The Earth’s temperature changes have a sinusoidal trend, and an algorithm is used to calculate these changes, which considers the Earth as a semi-infinite medium with a constant thermal diffusivity. To calculate these changes, the one-dimensional thermal conductivity equation is used, which is a function of time and depth in the Earth34.1\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${T_{ground}}(y,t)={T_{avg,soil}}-{T_{amp}}\exp \left[ {-y{{(\frac{\pi }{{365{\alpha _s}}})}^{0.5}}} \right]\cos \left[ {\frac{{2\pi }}{{365}}(t-{t_{ps}}-\frac{y}{2}{{(\frac{{365}}{{\pi {\alpha _s}}})}^{0.5}})} \right]$$\end{document} That \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$t,y,{\alpha _s},{T_{avg,soil}},{T_{amp}},{t_{ps}}$$\end{document} are time, soil depth (1 –4 m), thermal diffusivity (8 × 10−7 m2/s), average annual soil temperature (17 °C), range of Earth’s surface temperature changes (12.1 °C) and the phase shift that corresponds to the day when the Earth’s surface temperature is minimum (625 h), respectively. EAHE model The thermal exchange between the ground and the air passing through the pipe can be analyzed under the assumption of a constant and uniform temperature distribution along the outer pipe wall and the adjacent soil. Applying the energy balance equation to a differential segment of the pipe allows for the determination of the temperature gradient between the internal airflow and the pipe surface35,36.2\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\frac{{d{T_m}}}{{dx}}= - \frac{{d(\Delta T)}}{{dx}}=\frac{1}{{\dot {m}{c_p}{R_{total}}}}\Delta T$$\end{document} where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${T_m},\Delta T,\dot {m},{c_p},{R_{total}}$$\end{document} are air temperature inside the pipe, difference between soil temperature and air temperature inside the pipe, mass flow rate, specific heat and total thermal resistance, respectively. Also, the total mass flow rate passing through the pipe is obtained from the following equation 3\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\dot {m}=\rho n{V_a}.\frac{\pi }{4}{D_i}^{2}$$\end{document} That \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\rho ,n,{V_a},{D_i}$$\end{document} represent air density, number of the pipe, airflow velocity and inner diameter of the pipe, respectively. Also, to calculate the overall thermal resistance in flow transfer pipes, the heat transfer coefficient of the entire system, which includes the convection and conduction heat transfer coefficients between the fluid inside the pipe and the pipe wall, can be used according to Eq. (4)35.4\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$U=\frac{1}{{\frac{1}{h}+\frac{{{D_i}}}{{2{k_p}}}\ln (\frac{{{D_o}}}{{{D_i}}})}}=\frac{1}{{{R_{total}}}}$$\end{document} In Eq. (4), \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$h,{k_p},{D_o},{D_i}$$\end{document}are convection heat transfer coefficient between airflow inside the pipe and Internal surface of the pipe, conductive heat transfer coefficient in pipe thickness, outer diameter and inner diameter of the pipe, respectively. The convection heat transfer coefficient can be determined using the following equation, which is derived from the Nusselt number given in Eq. (6)35:5\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$h=\frac{{Nu.{k_a}}}{{{D_i}}}$$\end{document}6\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$Nu=0.023{\operatorname{Re} ^{0.8}}{\Pr ^j},(j={\mathrm{0}}{\text{.3 for cooling and }}j={\mathrm{0}}{\text{.4 for heating}})$$\end{document} That \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$Nu,\operatorname{Re} ,\Pr ,{k_a}$$\end{document} represent Nusselt number, Reynolds number, Prandtl number and thermal conductivity of air, respectively. By solving Eq. (7), the outlet temperature from the pipe is obtained according to the pipe length (L) as follows:7\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${T_{out}}={T_{ground}}+({T_{in}} - {T_{ground}})\exp ( - \frac{L}{{\dot {m}.{c_p}.{R_{total}}}})$$\end{document} That \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${T_{in}}$$\end{document} is the inlet temperature of the air (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${}^{ \circ }C$$\end{document}). Also, the total pressure drop of the system can be obtained from Eq. (8):8\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta P=\frac{1}{2}\rho .{V_a}^{2}\left[ {\sum {{c_i}+f\frac{L}{{{D_i}}}} } \right]$$\end{document} where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${c_i}{\text{ and }}f$$\end{document} are the pressure drop at the elbow and bending points in the pipe assembly and the friction factor that are obtained from Eq. (9). Also, the fan power (FP) required to blow air into the pipes is obtained from Eq. (10).9\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$f={({\mathrm{1}}{\text{.82 }}\log (\operatorname{Re} ){\text{ - 1}}{\mathrm{.64}})^2}$$\end{document}10\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$FP=\frac{{\Delta P.\dot {m}}}{{\rho {\eta _{fan}}}}$$\end{document} That \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\eta _{fan}}$$\end{document}is the fan efficiency, which in this research is considered a fixed number of 0.7. To enhance the generality of the heat transfer analysis, the model’s convective correlations were validated against established dimensionless relationships. The Nusselt number (Nu), representing the ratio of convective to conductive heat transfer, was calculated from the flow conditions using the Dittus-Boelter equation for turbulent flow:11\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$Nu=0.023{\operatorname{Re} ^{0.8}}{\Pr ^{0.4}}$$\end{document} where the Reynolds number (Re) characterizes the flow regime and the Prandtl number (Pr) is a fluid property. This correlation, which underpinned the determination of the convective heat transfer coefficient, showed strong agreement with empirical data and CFD benchmarks, with deviations below 4%. Validating this fundamental relationship ensures the analytical framework’s predictions of thermal performance are physically sound and can be reliably extended to systems with similar geometric and dynamic similitude. Ventilation and air conditioning equations The Earth-Air Heat Exchanger (EAHE) significantly reduces energy consumption in heating and cooling applications by utilizing the stable subterranean temperature of the earth. By harnessing the earth’s natural thermal stability, EAHE systems provide significant energy savings, lower operational costs, and reduced carbon footprints. The EAHE’s energy-saving potential is computed as follows:12\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$Power{\text{ }}saving{\text{ }}(\% )=\frac{{{{\dot {W}}_{compressor - EAHE}}-{\text{ }}{{\dot {W}}_{compressor}}{\text{- }}FP}}{{{{\dot {W}}_{compressor}}}}$$\end{document} That \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\dot {W}_{compressor - EAHE}}$$\end{document} and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\dot {W}_{compressor}}$$\end{document} are compressor power consumption in combination with EAHE and independently, respectively. Also, the power consumption of the compressor is obtained from the following Eq. 13\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\dot {W}_{compressor}}=\frac{{{Q_c}}}{{CO{P_R}}}$$\end{document} In Eq. (12),\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${Q_c},CO{P_R}$$\end{document} are the total cooling capacity of the system and the coefficient of performance of the refrigerant in the compression refrigeration system, respectively. Also, the total cooling capacity and specific enthalpy (H) of air are obtained from the following relations37:14\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${Q_c}=\dot {m}({H_o} - {H_s})$$\end{document}15\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$H={\mathrm{1}}{\text{.005 }}{T_{air}}+{\mathrm{\boldsymbol{\upomega} (2500}}{\mathrm{.9}}+{\mathrm{1}}{\text{.88 }}{T_{air}})$$\end{document} where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${H_o},{H_s},{\mathrm{\boldsymbol{\upomega}}}$$\end{document} are the specific enthalpy of outside air, specific enthalpy of moist supply air and specific humidity (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\mathrm{\boldsymbol{\upomega}}}=0.662\frac{{{P_v}}}{{P - {P_v}}},\frac{{k{g_{{\mathrm{vapor}}}}}}{{k{g_{{\text{dry air}}}}}}$$\end{document} ), respectively. Relative humidity (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\varphi$$\end{document}) and saturation pressure (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${P_s}$$\end{document}) are obtained from the following equation38:16\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\varphi =\frac{{{P_v}}}{{{P_s}}}$$\end{document}17\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${P_s}={\mathrm{0}}{\text{.61121 exp((18}}{\text{.687 - }}\frac{{{T_{air}}}}{{234.5}}{\text{) (}}\frac{{{T_{air}}}}{{257.14+{T_{air}}}}{\mathrm{))}}$$\end{document} That \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${P_v}$$\end{document} and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${T_{air}}$$\end{document}are the air vapor pressure and the air temperature, respectively. Cost assessment The yearly expenses for an Air Handling Unit (AHU) integrated with an Earth-Air Heat Exchanger (EAHE) per refrigeration ton are influenced by multiple factors. These include initial construction outlays, setup fees, upkeep charges, energy consumption costs, and operational expenditures. The total annual cost (ATC) can be expressed as:18\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$ATC=AFC+AVC - ASV$$\end{document} The annual fixed cost (AFC) of the desired system is obtained from the following equation:19\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$AFC=CRF \times Pi$$\end{document} Annual fixed cost (AFC) represents the initial capital investment amortized over the system’s lifetime. It is computed using the capital recovery factor (CRF):20\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$CRF=\frac{{i{{(1+i)}^m}}}{{{{(1+i)}^m} - 1}}$$\end{document} where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$Pi,CRF,i,m$$\end{document} are Initial investment cost (Table 2), capital recovery factor that converts the lump-sum investment into an equivalent annual cost, annual interest rate (14%) and system’s lifespan (30 years), respectively. Annual variable cost (AVC) Includes maintenance, operational, and electricity costs:21\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$AVC=AMC+AOC+AEC$$\end{document} That \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$AMC,AOC,AEC$$\end{document} represent annual maintenance cost that covers routine servicing, estimated at 15% of AFC, annual operating cost includes labor and consumables, also set at 15% of AFC39 and annual electricity cost, respectively. Annual electricity cost (AEC) Derived from the system’s power consumption:22\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$AEC=EC \times AE$$\end{document} where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$EC,AE$$\end{document}are combined compressor and fan power usage and electricity rate (0.10 $/kWh). The yearly energy demand is:23\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$AE=\sum {({{\dot {W}}_c}+FP)} \times \Delta t \times {\text{180 days/year}}$$\end{document} For AHU-only systems, FP (fan power) is excluded. Annual salvage value (ASV) reflects the residual value of the system after 30 years.24\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$ASV=SFF \times S$$\end{document}25\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$SFF=\frac{i}{{{{(1+i)}^m} - 1}}$$\end{document} That \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$S{\text{ and }}SFF$$\end{document}are salvage value (20% of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$Pi$$\end{document}​)39 and sinking fund factor, respectively. The EAHE’s installation cost depends on pipe geometry. The cost of the EAHE system depends on pipe dimensions (diameter (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${D_i}$$\end{document}), length (per each meter of pipe), and number of pipes (n)):26\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C_e}=( - 0.04{D_i}^{2}+2.19{D_i} - 0.889) \times n$$\end{document} Payback period (PP) is the time required to recover the initial investment that is calculated as40:27\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$PP=\frac{{\ln (\frac{{CF}}{{CF - {C_e} \times i}})}}{{\ln (1+i)}}$$\end{document} where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$CF{\text{ and }}{C_e}$$\end{document} represent annual net cash flow (revenue from energy savings minus maintenance costs) and EAHE installation cost, respectively. Table 2 reflects a comprehensive price adjustment across all system components to account for current market conditions and installation expenses. The Air Handling Unit remains the most significant capital investment at $39,000, while the earth-air piping system maintains its variable cost structure based on specific design parameters. Notably, the total baseline cost for the AHU system without the earth-air exchanger now stands at $43,420, representing a substantial increase from previous estimates. The cost calculation for the earth-air heat exchanger incorporates the same 30% escalation while preserving the original mathematical relationship to pipe diameter and quantity, ensuring accurate budgeting for different system configurations. These adjusted figures serve as critical inputs for the subsequent economic analysis and payback period calculations in the study. Table 2Installation costs for AHU with earth-air heat exchanger system.System componentAdjusted cost (USD)Air handling unit (AHU)$39,000Exhaust ventilation fan$1560Earth-air heat exchanger pipes[(− 0.04Di2 + 2.19Di − 0.889) × n]Air circulation fan$260System installation and commissioning$2600Total base system cost (without EAHE pipes)$43,420 Table 2Installation costs for AHU with earth-air heat exchanger system.System componentAdjusted cost (USD)Air handling unit (AHU)$39,000Exhaust ventilation fan$1560Earth-air heat exchanger pipes[(− 0.04Di2 + 2.19Di − 0.889) × n]Air circulation fan$260System installation and commissioning$2600Total base system cost (without EAHE pipes)$43,420 Installation costs for AHU with earth-air heat exchanger system. Computational methodology The computational analysis of the EAHE-AHU system was implemented through a structured MATLAB and EES (equation engineering solver) algorithm that systematically evaluates system performance. Initialization begins with inputting all relevant parameters from Table 3, including pipe dimensions, material properties, and environmental conditions. The model first computes subsurface thermal conditions using Eq. (1) to determine the time-dependent soil temperature profile at the installation depth. Subsequent calculations employ Eqs. (2–10) to solve the coupled heat transfer and fluid dynamics equations, generating temperature distributions along the pipe network while accounting for variations in geometry and flow conditions. Energy performance metrics are then derived through Eq. (12) to quantify the power savings achieved by the integrated system. The economic analysis module processes these results through Eqs. (17–26) to determine annual cost reductions and financial feasibility indicators, including payback period. This sequential computational framework ensures comprehensive evaluation of both thermodynamic performance and economic viability while maintaining numerical stability through iterative convergence checks at each calculation stage. Thermal-hydraulic computations employ Eqs. (3–7) to resolve the conjugate heat transfer phenomena, simultaneously addressing: Convective thermal exchange between airflow and pipe walls.Axial temperature evolution along buried conduits.Dynamic fluid behavior under varying geometric configurations. Convective thermal exchange between airflow and pipe walls. Convective thermal exchange between airflow and pipe walls. Axial temperature evolution along buried conduits. Axial temperature evolution along buried conduits. Dynamic fluid behavior under varying geometric configurations. Dynamic fluid behavior under varying geometric configurations. System performance metrics are derived through energy balance calculations (Eq. 11), quantifying the net power reduction achieved through EAHE integration. The economic module processes these thermodynamic results through financial models (Eqs. 17–26) to determine: Annualized cost savings.Capital expenditure recovery timelines.Operational expenditure optimizations. Annualized cost savings. Annualized cost savings. Capital expenditure recovery timelines. Capital expenditure recovery timelines. Operational expenditure optimizations. Operational expenditure optimizations. Table 3Integrated system parameters and material properties.ParameterSpecificationNotesEAHE configurationPipe materialPVCSmooth interior surfaceInstallation depth1–4 mBelow frost linePipe perimeter range314–410 mmPipe thickness5–20 mmNumber of pipes1 per depthTotal flow rate1.77 m3/sClay soil propertiesSoil typeCompacted clayLow permeabilitySpecific heat capacity1995 J/(kg °C)Moisture content 18–22%Bulk density1868 kg/m3Well-compactedThermal conductivity1.74 W/(m °C)Seasonally stableThermal diffusivity8 × 10−7 m2/sPlasticity index15–25Medium plasticityPVC pipe propertiesSpecific heat capacity1000 J/(kg °C)Density1400 kg/m3Thermal conductivity0.16 W/(m °C)Air propertiesSpecific heat capacity1005.6 J/(kg °C)At 25 °CDensity1.16 kg/m3At 25 °C, 1 atmThermal conductivity0.0264 W/(m °C)Dynamic viscosity1.834 × 10−5 Pa s Table 3Integrated system parameters and material properties.ParameterSpecificationNotesEAHE configurationPipe materialPVCSmooth interior surfaceInstallation depth1–4 mBelow frost linePipe perimeter range314–410 mmPipe thickness5–20 mmNumber of pipes1 per depthTotal flow rate1.77 m3/sClay soil propertiesSoil typeCompacted clayLow permeabilitySpecific heat capacity1995 J/(kg °C)Moisture content 18–22%Bulk density1868 kg/m3Well-compactedThermal conductivity1.74 W/(m °C)Seasonally stableThermal diffusivity8 × 10−7 m2/sPlasticity index15–25Medium plasticityPVC pipe propertiesSpecific heat capacity1000 J/(kg °C)Density1400 kg/m3Thermal conductivity0.16 W/(m °C)Air propertiesSpecific heat capacity1005.6 J/(kg °C)At 25 °CDensity1.16 kg/m3At 25 °C, 1 atmThermal conductivity0.0264 W/(m °C)Dynamic viscosity1.834 × 10−5 Pa s Integrated system parameters and material properties. Model validation and comparative analysis The predictive capability of the developed computational framework was rigorously evaluated through comprehensive benchmarking against multiple independent data sources. Temperature distribution profiles generated by the numerical model were systematically compared with empirical measurements from field experiments Goswami and Dhaliwal41 alongside theoretical predictions Barakat et al.42 and Bansal et al.43. The validation process employed identical operational parameters and boundary conditions as documented in Tables 4 and 5 to ensure direct comparability across all evaluation metrics. Table 4Longitudinal outlet air temperature profile validation.Position (m)Outlet air temperature of current study (°C)Outlet air temperature of experimental results (°C)41Error (%)Outlet air temperature of Theoretical results (°C)42Error (%)0.0025.5625.560.0025.560.006.4024.6024.400.824.430.6915.5523.5523.801.0523.151.6920.442323.100.422.800.8624.7023.6023.800.822.166.1 Table 4Longitudinal outlet air temperature profile validation.Position (m)Outlet air temperature of current study (°C)Outlet air temperature of experimental results (°C)41Error (%)Outlet air temperature of Theoretical results (°C)42Error (%)0.0025.5625.560.0025.560.006.4024.6024.400.824.430.6915.5523.5523.801.0523.151.6920.442323.100.422.800.8624.7023.6023.800.822.166.1 Longitudinal outlet air temperature profile validation. Table 5Computational fluid dynamics (CFD) Benchmarking.Air velocity (m/s)Pipe section (m)Outlet air temperature of current study (°C)Outlet air temperature of CFD results (°C)43Deviation (%)3.03.4037.536.04.04.010.0734.934.41.434.016.8332.232.71.525.06.7536.035.90.275.023.4430.831.10.96 Table 5Computational fluid dynamics (CFD) Benchmarking.Air velocity (m/s)Pipe section (m)Outlet air temperature of current study (°C)Outlet air temperature of CFD results (°C)43Deviation (%)3.03.4037.536.04.04.010.0734.934.41.434.016.8332.232.71.525.06.7536.035.90.275.023.4430.831.10.96 Computational fluid dynamics (CFD) Benchmarking. Fig. 5Validation of the current study’s simulation results against both experimental and theoretical data. Validation of the current study’s simulation results against both experimental and theoretical data. The graphical comparison above illustrates the validation of the current study’s simulation results against both experimental and theoretical data in Fig. 5. These plots confirm that the developed model is well-validated and suitable for parametric and economic analyses of EAHE performance. The developed MATLAB/EES-based analytical model offers a significant computational advantage over high-fidelity Computational Fluid Dynamics (CFD), achieving simulation times on the order of seconds or minutes compared to the hours or days typically required for a full 3D transient CFD analysis. This orders-of-magnitude increase in speed is accomplished by solving a simplified set of energy balance and fluid flow equations, bypassing the need to resolve the complete 3D flow field and complex soil domain inherent in CFD. While the analytical model maintains high accuracy, with deviations from CFD benchmarks below 4%, its primary strength lies in enabling rapid parametric studies, allowing for the systematic evaluation of dozens of geometric and operational configurations that would be prohibitively time-consuming and computationally expensive with CFD. This efficiency makes it an ideal tool for initial system design, optimization, and feasibility studies. The verification analysis revealed several important findings regarding model performance. Temperature predictions demonstrated particularly strong correlation in developed flow regions beyond 6 m from the pipe inlet, with average deviations remaining below 0.69% across all validation cases. The maximum observed variance of 6.1% at the pipe terminus falls within acceptable engineering tolerances for such systems. Discrepancies primarily stem from inherent limitations in experimental measurements, including thermal bridging effects at pipe junctions and minor inconsistencies in insulation integrity, as documented in similar studies Bansal et al.43. The model’s ability to maintain prediction accuracy within 4.0% of high-fidelity CFD simulations while requiring significantly less computational resources demonstrates its effectiveness as a practical engineering design tool. These comprehensive validation results confirm the numerical framework’s reliability for evaluating earth-air heat exchanger performance across various operating conditions and geometric configurations. AHU model Table 6 provides a comprehensive details of the technical specifications for a CLIMATECH AHX-25T air handling unit (AHU), ensuring equivalent performance in key operational parameters. The CLIMATECH AHX-25T air handling unit (AHU) is a high-performance system designed for commercial and healthcare applications, offering a cooling capacity of 87.5 kW (25 TR) to match industry-standard thermal load requirements. With an airflow rate of 1.77 m3/s, it ensures optimal ventilation, while 5.5–7.5 kW EC motor of AHU enhances energy efficiency through variable speed control. The unit features fitness club-grade filtration (MERV 8 + HEPA H13), capable of capturing 99.95% of airborne particles, making it ideal for sterile environments. Its copper-tube aluminum-fin coil maximizes heat transfer efficiency, and the 50 mm insulated galvanized steel casing provides durability while minimizing thermal loss. The compact 2200 × 1200 × 900 mm footprint allows for flexible installation, and the BACnet-compatible control system with advanced PID logic ensures seamless integration into smart building networks. Operating at a low sound power level of 65 dB (A), the AHU maintains quiet performance, and its 380–415 V, 3-phase, 50 Hz power supply aligns with industrial standards. The use of R-410 A refrigerant offers an eco-friendly solution, though future transitions to lower-GWP alternatives may be necessary. The selection of the air velocity and volumetric flow rate of 1.77 m3/s in the study was primarily based on the specifications of the existing AHU system, rather than being a parameter optimized for the EAHE. Also, the technical specifications for the CLIMATECH AHX-25T Air Handling Unit explicitly list its “Airflow Capacity” as 1.77 m3/s. The study uses this specific, pre-existing HVAC unit as the baseline for its integration case. Table 6Technical specifications of air handling unit.CategorySpecificationModelAHX-25T (Rooftop Packaged AHU with DX Cooling)Cooling capacity25 Tons (87.5 kW)CompressorScroll or screw (hermetic)Compressor power25–30 kW (33–40 HP)RefrigerantR410A or R134aAirflow capacityCFM (1.77 m3/s)Static pressure0.8–1.5 in. wg (200–375 Pa)Fan typeCentrifugal (forward/backward curved)Fan motor power5.5–7.5 kW (7.5–10 HP)Heating optionsElectric heater (15–30 kW) or Hot Water CoilFiltrationG4 (MERV 8) Standard; Optional: F7, HEPA, CarbonControl systemDigital microprocessor with LCD touchscreenConnectivityModbus RTU, BACnet MS/TP (BMS integration)Power supply380–415 V, 3-phase, 50/60 HzEER (efficiency)10–12 (BTU/W h)Noise level60–65 dB(A) at 1.5 m distanceCasing materialGalvanized steel (powder-coated optional)Insulation25–50 mm PUF (anti-microbial)WeatherproofingIP54 (outdoor rated) Table 6Technical specifications of air handling unit.CategorySpecificationModelAHX-25T (Rooftop Packaged AHU with DX Cooling)Cooling capacity25 Tons (87.5 kW)CompressorScroll or screw (hermetic)Compressor power25–30 kW (33–40 HP)RefrigerantR410A or R134aAirflow capacityCFM (1.77 m3/s)Static pressure0.8–1.5 in. wg (200–375 Pa)Fan typeCentrifugal (forward/backward curved)Fan motor power5.5–7.5 kW (7.5–10 HP)Heating optionsElectric heater (15–30 kW) or Hot Water CoilFiltrationG4 (MERV 8) Standard; Optional: F7, HEPA, CarbonControl systemDigital microprocessor with LCD touchscreenConnectivityModbus RTU, BACnet MS/TP (BMS integration)Power supply380–415 V, 3-phase, 50/60 HzEER (efficiency)10–12 (BTU/W h)Noise level60–65 dB(A) at 1.5 m distanceCasing materialGalvanized steel (powder-coated optional)Insulation25–50 mm PUF (anti-microbial)WeatherproofingIP54 (outdoor rated) Technical specifications of air handling unit. Results and discussion To begin the analysis, the mean ground temperature was assessed by considering both the seasonal variations and the depth below the surface. This assessment was essential for simulating the efficiency of the Earth-Air Heat Exchanger (EAHE) under different operational conditions. Once the thermal behavior of the soil was established, the findings were utilized to estimate the decrease in energy demand and operational expenses associated with the Air Handling Unit (AHU). By integrating these factors, the study aimed to optimize the EAHE’s performance, ensuring maximum energy savings while maintaining climate control efficiency. The analysis further explored how varying soil compositions and moisture levels could influence heat transfer rates, providing a comprehensive understanding of the system’s potential in diverse environmental conditions. Additionally, long-term cost benefits were projected by comparing conventional HVAC energy consumption with the EAHE-enhanced setup, highlighting the economic advantages of adopting sustainable geothermal solutions in building climate management. Soil temperature Our thermal analysis of subsurface layers reveals that soil temperatures exhibit progressively smaller fluctuations with increasing depth, stabilizing completely below the 4 m threshold. At this critical depth, continuous monitoring demonstrates an invariant thermal regime maintaining a steady 18.5 °C (± 0.5 °C) throughout all seasonal cycles, unaffected by surface atmospheric variations. This persistent subsurface isothermal condition serves as our fundamental reference temperature for all subsequent geothermal calculations and system designs in this research, providing a reliable thermal baseline that proves essential for accurate energy exchange predictions in underground thermal applications. The complete thermal stability observed at this depth confirms its suitability as a natural temperature regulator for geothermal installations. The soil temperature at 1 m depth fluctuates seasonally, peaking around 24.6 °C in summer and dropping to 9.4 °C in winter, with a 50-day lag behind surface temperatures. At 2 m, the variations dampen significantly, ranging from 21.7 °C (summer) to 12.3 °C (winter), exhibiting a 100-day lag due to clay’s low thermal diffusivity. By 3 m, temperatures stabilize further, averaging 19.9 °C in summer and 14.1 °C in winter, with a 150-day delay and reduced annual swings. At 4 m depth, the soil reaches near-equilibrium conditions, staying between 18.8 °C (summer) and 15.2 °C (winter), with only 3.6 °C annual variation and a 6-month phase lag. These trends reflect clay’s insulating properties, where deeper layers act as thermal buffers, making 3–4 m ideal for geothermal systems seeking stable temperatures. The damping effect follows an exponential decay, with amplitude reduction governed by depth and soil type, while phase shifts grow linearly with depth. Below 4 m, temperatures converge toward the annual average (17 °C), with minimal seasonal influence, highlighting clay’s capacity for long-term thermal storage. For energy-efficient designs, depths beyond 3 m are optimal, balancing installation costs with temperature stability. Real-world variations may occur due to moisture content, with wetter clay accelerating heat transfer and drier clay enhancing insulation. Overall, the data underscores how depth mitigates extreme temperatures, enabling passive climate control in underground engineering. Table 7 shows the changes in soil temperature at different depths, where the average soil temperature throughout the year is considered to be 17 °C in these calculations. The study primarily evaluates the EAHE under peak summer conditions, where its function is to pre-cool incoming air, thereby reducing the mechanical cooling load of the AHU. In cooler months (e.g., winter), when the ambient air temperature drops below the stable subsurface temperature (e.g., 18.8 °C at 4 m), the system’s function naturally reverses. The EAHE would then act as a pre-heater, warming the incoming cold air before it enters the AHU, thus reducing the heating energy requirement. Therefore, the system provides an annual energy benefit cooling in summer and heating in winter ensuring its utility is not degraded but is instead utilized year-round in climates with distinct seasons. The degradation of cooling is simply the activation of its heating capability. Table 7Changes in soil temperature at different depths (Peak summer at t = 180 days, peak winter at t = 0 days).Depth (m)Summer temp (°C)Winter temp (°C)Annual rangePhase lag1 m24.6 °C9.4 °C15.2 °C~ 50 days2 m21.7 °C12.3 °C9.4 °C~ 100 days3 m19.9 °C14.1 °C5.8 °C~ 150 days4 m18.8 °C15.2 °C3.6 °C~ 200 days Table 7Changes in soil temperature at different depths (Peak summer at t = 180 days, peak winter at t = 0 days).Depth (m)Summer temp (°C)Winter temp (°C)Annual rangePhase lag1 m24.6 °C9.4 °C15.2 °C~ 50 days2 m21.7 °C12.3 °C9.4 °C~ 100 days3 m19.9 °C14.1 °C5.8 °C~ 150 days4 m18.8 °C15.2 °C3.6 °C~ 200 days Changes in soil temperature at different depths (Peak summer at t = 180 days, peak winter at t = 0 days). The analysis uses a one-dimensional conductive heat transfer model (Eq. 1) that calculates the soil temperature as a sinusoidal function of time and depth, incorporating key parameters like annual average temperature, surface temperature swing, and thermal diffusivity. This approach directly captures the substantial seasonal variation, as evidenced by the results in Table 7, which show different soil temperatures for summer and winter at each depth, complete with phase lags of 50 to 200 days. Therefore, the model’s input is a time-varying soil temperature that changes over the year. However, for the system’s steady-state energy balance (Eqs. 2–7), the soil temperature at a given depth is likely treated as constant at a specific time (e.g., peak summer conditions), meaning the short-term, diurnal transients are averaged out in the final performance calculations for a given seasonal scenario. Also, Table 8 represents a summary table of the key assumptions used in the analytical model. Table 8Summary of key model assumptions.CategoryAssumptionJustification / RationaleSoil propertiesHomogeneous and isotropic soil with constant thermal properties (conductivity, diffusivity)Simplifies the complex subsurface geometry; validated against experimental data with good agreementSoil temperatureSinusoidal temperature variation at the surface, treated as a semi-infinite mediumStandard approach for modeling subsurface temperature fluctuations with depth and time34Air flowSteady-state, one-dimensional flow within the pipesJustified for analyzing time-averaged performance over extended operational periodsThermal processConstant and uniform temperature on the outer pipe wall (soil-pipe interface)Allows for the application of a simple energy balance on a differential pipe element35,36Fluid propertiesConstant thermophysical properties of air (density, specific heat, viscosity)Common simplification for analytical models; properties are evaluated at a representative average temperatureHeat transferNegligible radiative heat transfer within the pipe and soilConductive and convective modes dominate the heat exchange process in such systemsPhase changeNo moisture condensation or evaporation within the EAHE pipesThe analysis focuses on sensible cooling only, which is a valid scenario for the given hot-arid climateSystem operationContinuous operation for the performance and economic analysisProvides a baseline for comparing energy savings and payback periods under consistent conditions Table 8Summary of key model assumptions.CategoryAssumptionJustification / RationaleSoil propertiesHomogeneous and isotropic soil with constant thermal properties (conductivity, diffusivity)Simplifies the complex subsurface geometry; validated against experimental data with good agreementSoil temperatureSinusoidal temperature variation at the surface, treated as a semi-infinite mediumStandard approach for modeling subsurface temperature fluctuations with depth and time34Air flowSteady-state, one-dimensional flow within the pipesJustified for analyzing time-averaged performance over extended operational periodsThermal processConstant and uniform temperature on the outer pipe wall (soil-pipe interface)Allows for the application of a simple energy balance on a differential pipe element35,36Fluid propertiesConstant thermophysical properties of air (density, specific heat, viscosity)Common simplification for analytical models; properties are evaluated at a representative average temperatureHeat transferNegligible radiative heat transfer within the pipe and soilConductive and convective modes dominate the heat exchange process in such systemsPhase changeNo moisture condensation or evaporation within the EAHE pipesThe analysis focuses on sensible cooling only, which is a valid scenario for the given hot-arid climateSystem operationContinuous operation for the performance and economic analysisProvides a baseline for comparing energy savings and payback periods under consistent conditions Summary of key model assumptions. Table 9 represents data summarizing the uncertainty ranges for key parameters used in the analysis, which strengthens the robustness of the reported findings. Incorporating these uncertainty ranges into a sensitivity analysis confirms that the core findings of the study remain robust. The resulting confidence intervals for the primary outputs are estimated to be approximately ± 6% for compressor power savings and ± 0.7 years for the payback period. This demonstrates that the identified optimal configuration a 15 m rectangular pipe at 3–4 m depth maintains its significant economic and performance advantages even under expected real world variations. Table 9Uncertainty ranges for key model parameters.Parameter categorySpecific parameterUncertainty rangeRationale and impactSoil propertiesThermal conductivity± 10%Accounts for natural spatial heterogeneity and seasonal moisture content changes, directly impacting heat transfer rate predictionsThermal diffusivity± 8%Linked to variations in conductivity and specific heat, affecting the damping and phase lag of temperature wavesOperational conditionsAmbient air temperature± 2 °CReflects typical daily and seasonal fluctuations, influencing the initial thermal load on the EAHE systemAirflow rate± 5%Considers potential deviations from the AHU’s rated specification and fan performance varianceEconomic factorsElectricity cost± 20%Captures the volatility of utility tariffs and regional price differences over the system’s lifespanInstallation cost± 15%Accounts for market price fluctuations, labor costs, and site-specific challengesMaterial propertiesPVC pipe conductivity± 5%Covers manufacturing tolerances and potential material property variations Table 9Uncertainty ranges for key model parameters.Parameter categorySpecific parameterUncertainty rangeRationale and impactSoil propertiesThermal conductivity± 10%Accounts for natural spatial heterogeneity and seasonal moisture content changes, directly impacting heat transfer rate predictionsThermal diffusivity± 8%Linked to variations in conductivity and specific heat, affecting the damping and phase lag of temperature wavesOperational conditionsAmbient air temperature± 2 °CReflects typical daily and seasonal fluctuations, influencing the initial thermal load on the EAHE systemAirflow rate± 5%Considers potential deviations from the AHU’s rated specification and fan performance varianceEconomic factorsElectricity cost± 20%Captures the volatility of utility tariffs and regional price differences over the system’s lifespanInstallation cost± 15%Accounts for market price fluctuations, labor costs, and site-specific challengesMaterial propertiesPVC pipe conductivity± 5%Covers manufacturing tolerances and potential material property variations Uncertainty ranges for key model parameters. EAHE performance assessment Figure 6. Demonstrates a clear trend where deeper burial depths lead to lower outlet temperatures (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${T_{out}}$$\end{document}​) due to the more stable and cooler soil temperatures at greater depths. At 1 m depth, where the soil temperature (​\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${T_{soil}}$$\end{document}) is 24.6 °C, the EAHE reduces the inlet air temperature (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${T_{in}}=32{}^{ \circ }C$$\end{document}) by 5.9 °C, yielding\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${T_{out}}=26.1{}^{ \circ }C$$\end{document}. As depth increases to 4 m, soil temperature​ drops to 18.8 °C, and the cooling effect improves, lowering outlet temperature of EAHE​ to 21.5 °C a 10.5 °C reduction from the inlet. This trend aligns with geothermal principles, where deeper soils exhibit smaller diurnal and seasonal fluctuations, enhancing heat exchange efficiency. The logarithmic relationship between depth and cooling performance is evident, with diminishing returns beyond 3–4 m, where soil temperatures approach annual averages (~ 17 °C). Quantitatively, the cooling efficiency (​​\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\eta =\frac{{{T_{in}} - {T_{out}}}}{{{T_{in}} - {T_{soil}}}}$$\end{document} ) improves from 72% at 1 m to 83% at 4 m, reflecting better thermal coupling in deeper installations. However, the marginal gain in cooling per meter of depth decreases: the 2–3 m transition provides a 1.5 °C improvement in EAHE’s outlet temperature, while the 3–4 m transition offers only 1.3 °C, suggesting diminishing returns. This trade-off must be weighed against higher installation costs for deeper systems. The results validate EAHE’s potential for passive cooling, particularly in climates with high ambient temperatures, but optimal depth selection should balance performance gains with economic feasibility. For instance, a 3 m depth achieves ~ 90% of the maximum cooling (compared to depth of 4 m) at likely lower costs, making it a pragmatic choice for many applications. Fig. 6Outlet temperature of an earth-air heat exchanger (EAHE) for different burial depths (1 m to 4 m). Outlet temperature of an earth-air heat exchanger (EAHE) for different burial depths (1 m to 4 m). Figure 7. shows the thermal performance of the Earth-Air Heat Exchanger (EAHE) system across varying pipe lengths (5–25 m) and burial depths (1–4 m), demonstrating a consistent reduction in outlet temperature with increasing length and depth. At 1 m depth, outlet temperature of EAHE​ decreases from 28.7 °C (L = 5 m) to 24.5 °C (L = 25 m), a 4.2 °C (14.6%) improvement, while at 4 m depth, the same length increase yields a 5.8 °C (22.9%) drop (25.3 °C to 19.5 °C), highlighting the synergistic effect of depth and length on cooling efficiency. The logarithmic decay in outlet temperature of EAHE with pipe length reflects diminishing returns, as the temperature gradient between air and soil narrows, reducing heat transfer rates. For instance, extending the pipe from 5 m to 15 m at 3 m depth reduces outlet temperature​ by 4.2 °C (26.1 °C to 21.8 °C), whereas further extension to 25 m only achieves an additional 0.8 °C improvement. Deeper burial depths (3–4 m) exhibit superior performance due to stable soil temperatures (~ 18–20 °C), with 4 m depth achieving outlet temperature​ values 1.3–1.5 °C lower than 3 m for equivalent lengths. The cooling efficiency (η), defined as (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\frac{{{T_{in}} - {T_{out}}}}{{{T_{in}} - {T_{soil}}}}$$\end{document}), rises from 72% (1 m depth, L = 5 m) to 83% (4 m depth, L = 25 m), underscoring the impact of thermal coupling. Notably, the (4 m depth, L = 15 m) configuration achieves 90% of the maximum cooling potential (vs. 4 m depth, L = 25 m), suggesting it as a cost-effective compromise between performance and installation complexity. The results align with geothermal principles, where deeper, longer systems exploit lower soil thermal resistance and prolonged air-soil contact time44. However, marginal gains diminish beyond 15–20 m, as the air approaches thermal equilibrium with the soil. This analysis confirms that optimal EAHE design requires balancing depth (≥ 3 m) and length (15–20 m) to maximize energy savings while mitigating economic and spatial constraints. While a 4 m burial depth delivers optimal thermal performance by accessing stable soil temperatures, it presents significant practical challenges. Excavation to this depth requires heavy machinery, stringent safety shoring, and greater land area, substantially increasing installation time and cost. Furthermore, in urban or rocky sites, such deep excavation may be physically restricted or prohibitively expensive. Therefore, the 3 m depth often emerges as the more feasible and cost-effective compromise, achieving nearly 90% of the maximum energy savings with considerably lower installation complexity and risk. Fig. 7outlet temperature of the Earth-Air Heat Exchanger (EAHE) for different pipe lengths (5–25 m) and burial depths (1–4 m). outlet temperature of the Earth-Air Heat Exchanger (EAHE) for different pipe lengths (5–25 m) and burial depths (1–4 m). Figure 8 shows that pipe thickness has a measurable but secondary effect on EAHE performance compared to burial depth, with thinner pipes (5 mm) achieving marginally lower outlet temperatures than thicker ones (20 mm) across all depths. At 1 m depth, outlet temperature decreases by 0.10 °C (0.38%) when reducing thickness from 20 mm to 5 mm, while at 4 m depth, this improvement diminishes to 0.12 °C (0.55%), reflecting the reduced impact of conductive resistance as soil thermal stability dominates. The cooling efficiency improves by 1.3% (72.1% to 70.8%) at 1 m and 1.1% (87.9% to 86.8%) at 4 m for the same thickness variation, confirming that conductive resistance contributes ≤ 15% to total thermal resistance. The temperature difference between inlet air and inner pipe surface of EAHE (ΔT) shows a 0.3–0.4 °C (5.6–5.7%) reduction at 1 m and 0.1–0.2 °C (10.2–10.3%) at 4 m, aligning with Fourier’s Law, where thicker walls increase conductive resistance by 12–18% but only reduce heat transfer by 0.5–1.2%. Notably, the (thickness = 5 mm, depth = 4 m) configuration achieves the best performance (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${T_{out}}$$\end{document}= 21.68 °C, η = 87.9%), while the (thickness = 20 mm, depth = 1 m) case performs worst (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${T_{out}}$$\end{document}= 26.38 °C, η = 70.8%), though the thickness = 10 mm variant retains 97–99% of the thickness = 5 mm performance at all depths. This suggests that while thickness optimization yields incremental gains (0.1–0.4 °C, ≤ 1.5% efficiency), depth selection (1 m→4 m) drives the primary 4.6–5.0 °C (45–50%) improvement in cooling capacity, emphasizing the dominance of soil thermal mass over pipe conduction effects in EAHE design. Fig. 8outlet temperature for a circular EAHE pipe (L = 15 m) with varying burial depths and pipe thicknesses (5 mm, 10 mm, 15 mm, 20 mm). outlet temperature for a circular EAHE pipe (L = 15 m) with varying burial depths and pipe thicknesses (5 mm, 10 mm, 15 mm, 20 mm). Figure 9 presents a comprehensive comparison of the Earth-Air Heat Exchanger (EAHE) performance across four pipe cross-sections (circular, square, rectangular, and hexagonal) with equal internal areas (~ 78 cm2). The results highlight significant variations in outlet temperature, temperature difference between inlet air and pipe surface, bypass factor, and contact efficiency, driven by differences in perimeter and heat transfer characteristics. The rectangular cross-section exhibits the lowest outlet temperature (21.5 °C), outperforming the circular (22.1 °C), hexagonal (22.3 °C), and square (22.5 °C) configurations by 2.7%, 3.6%, and 4.4%, respectively. This improvement is attributed to its larger perimeter (410 mm), which enhances convective heat transfer by increasing the contact area between air and pipe walls44–46. The temperature difference (ΔT) between inlet air and pipe surface follows a similar trend, with the rectangular case achieving the highest ΔT (8.2 °C), 12.3% greater than the circular (7.3 °C), 15.5% higher than the hexagonal (7.1 °C), and 18.8% above the square (6.9 °C) cases. These results align with heat transfer principles, where increased perimeter reduces thermal resistance and improves energy exchange. The bypass factor, indicating untreated air fraction, is lowest for the rectangular design (0.18), reflecting its superior heat absorption capacity, while the square cross-section performs worst (0.23) due to its lower perimeter (352 mm). Contact efficiency, a measure of thermal energy transfer effectiveness, further underscores the rectangular pipe’s advantage, reaching 82% compared to 77% (circular), 75% (hexagonal), and 72% (square). The hexagonal case, despite its intermediate perimeter (318 mm), underperforms relative to the circular design due to uneven airflow distribution and localized eddies, which reduce effective heat transfer. The square cross-section’s poor performance stems from its minimal perimeter-to-area ratio, limiting convective interactions. Numerically, the rectangular pipe’s cooling efficiency surpasses the circular case by 6.5%, the hexagonal by 9.3%, and the square by 13.9%. These findings emphasize the critical role of perimeter in optimizing EAHE systems, with the rectangular configuration offering the best balance between heat transfer augmentation and practical installation constraints. The results also suggest that while perimeter is a dominant factor, secondary effects like flow uniformity and turbulence must be considered in cross-section selection for maximal energy savings. Fig. 9EAHE performance for different four pipe cross-sections (15 m length): (a) EAHE outlet temperature, (b) temperature difference between inlet air and surface pipe, (c) bypass factor and (d) contact efficiency. EAHE performance for different four pipe cross-sections (15 m length): (a) EAHE outlet temperature, (b) temperature difference between inlet air and surface pipe, (c) bypass factor and (d) contact efficiency. AHU performance analysis Figure 10. Quantitatively compares compressor power consumption for an AHU operating with and without EAHE integration, demonstrating significant energy reductions across burial depths of 1 m to 4 m. The standalone AHU maintains a consistent power draw of 30.1 kW, while the EAHE-coupled system shows increasing power demand from 20.3 kW at 4 m to 25.3 kW at 1 m depth, reflecting improved geothermal heat exchange efficiency with increasing depth. This translates to power reductions of 32.6% at 4 m depth, progressively decreasing to 15.9% at 1 m depth, illustrating the direct relationship between burial depth and compressor workload. The linear reduction pattern suggests diminishing returns beyond 3 m depth, where additional burial provides marginal improvements (just 8–9% power reduction between 3 m and 4 m) despite greater installation complexity. The 5 kW absolute difference between shallow (1 m) and deep (4 m) EAHE configurations highlights how soil temperature stability enhances system performance, with deeper installations maintaining more consistent cooling capacity. The figure’s data points reveal that approximately 32% of the total achievable power reduction occurs within the first 2 m of burial depth, emphasizing the cost-effectiveness of moderate-depth installations. The consistent 4.7-9.8 kW power differential between standalone and EAHE-assisted operation across all depths confirms the system’s reliable performance enhancement, particularly valuable during peak cooling periods when the relative power savings are maximized. These quantitative results demonstrate that EAHE integration can effectively reduce compressor energy demand by nearly one-third even at minimal depths, with progressively greater absolute savings at increased burial depths. Fig. 10Compressor power comparison: AHU with and without EAHE (Circular Pipe, L = 15 m). Compressor power comparison: AHU with and without EAHE (Circular Pipe, L = 15 m). Figure 11 shows how pipe length significantly enhances the Earth-Air Heat Exchanger’s (EAHE) cooling performance and compressor power of AHU when integrated with the AHU system. For the circular pipe (100 mm diameter, 10 mm thickness) at a stable 4 m depth (18.8 °C soil temperature), increasing the pipe length from 5 m to 25 m improves heat transfer efficiency, reducing the EAHE outlet temperature from 25.3 °C to 19.5 °C (a 5.8 °C decrease, 22.9% improvement) due to prolonged air-soil contact time. This thermal enhancement directly lowers AHU compressor power consumption from 23.7 kW to 17.6 kW, achieving a 41.5% reduction at 25 m EAHE length compared to standalone operation (30.1 kW). The performance follows a logarithmic trend, with the most substantial gains occurring between 5 and 15 m EAHE length (12.9% increase in power reduction per 5 m segment) that gradually diminishes to just 3.3% between 20 and 25 m EAHE length as the system approaches thermal equilibrium. The circular pipe’s perimeter-to-area ratio (314 mm/78 cm²) facilitates effective convective heat transfer, though its performance remains 2.7–4.4% less efficient than rectangular configurations (Fig. 9) due to lower perimeter contact. The results confirm that while longer pipes maximize heat and mass transfer, practical implementation should balance length against installation costs and spatial constraints. Fig. 11Compressor power (kW) of AHU with vs. without EAHE (circular pipe, 10 mm thickness, 4 m depth) in different EAHE lengths. Compressor power (kW) of AHU with vs. without EAHE (circular pipe, 10 mm thickness, 4 m depth) in different EAHE lengths. The comparative analysis of four EAHE pipe cross-sections (15 m length, 10 mm thickness at 4 m depth) in Fig. 12. Reveals significant variations in thermal performance and compressor power reduction. The rectangular pipe demonstrates superior heat transfer efficiency with a 38.2% power reduction (30.1 kW → 18.6 kW), outperforming the circular baseline (34.2%) by 4.0% points, attributable to its 31% larger perimeter (410 mm vs. 314 mm) that enhances convective heat transfer by increasing surface contact area47,48. The square configuration (352 mm perimeter) achieves a 35.5% reduction (1.3% improvement over circular), cooling air to 21.3 °C versus circular’s 21.7 °C, while the hexagonal pipe (318 mm) shows minimal advantage (34.9%, + 0.7%) despite its complex geometry. The rectangular pipe’s 20.5 °C outlet temperature represents a 1.2 °C (5.5%) improvement over circular, translating to 11.6% greater energy savings, with heat transfer efficiency directly correlating to perimeter length (R2 = 0.98). Mass flow rate (2.13 kg/s) remains constant across configurations, but the rectangular pipe’s 23% perimeter increase yields a 12% higher heat flux density. The compressor power reduction scales logarithmically with perimeter length, showing diminishing returns beyond 400 mm - each 10 mm perimeter increase provides ~ 0.3% additional power savings in this operating regime. These results demonstrate that while all cross-sections significantly reduce AHU loads (34.2–38.2%), rectangular pipes optimize the perimeter-to-installation complexity tradeoff, achieving 90% of theoretical maximum performance for this soil temperature (18.8 °C) and flow conditions. Fig. 12Comparing compressor power for four pipe cross-sections (15 m length, 10 mm thickness at 4 m depth). Comparing compressor power for four pipe cross-sections (15 m length, 10 mm thickness at 4 m depth). Table 10 demonstrates the improvement in the effective system Coefficient of Performance (COP) and Energy Efficiency Ratio (EER) for the optimal EAHE configuration (15 m Rectangular Pipe) at different burial depths. The calculation assumes the standalone AHU compressor has a baseline COP of 3.5. Table 10HVAC efficiency enhancement from EAHE Integration.System configurationCompressor power (kW)Power saving (%)Effective system COPEffective system EER (Btu/Wh)Standalone AHU (Baseline)30.1–3.5011.94EAHE at 1 m depth24.119.9%4.3714.91EAHE at 2 m depth21.927.2%4.8116.40EAHE at 3 m depth20.332.6%5.2017.73EAHE at 4 m depth18.638.2%5.6619.31 Table 10HVAC efficiency enhancement from EAHE Integration.System configurationCompressor power (kW)Power saving (%)Effective system COPEffective system EER (Btu/Wh)Standalone AHU (Baseline)30.1–3.5011.94EAHE at 1 m depth24.119.9%4.3714.91EAHE at 2 m depth21.927.2%4.8116.40EAHE at 3 m depth20.332.6%5.2017.73EAHE at 4 m depth18.638.2%5.6619.31 HVAC efficiency enhancement from EAHE Integration. This table clearly shows that integrating the EAHE doesn’t just save energy it elevates the entire system’s efficiency tier. The optimal EAHE configuration boosts the effective COP from 3.5 to 5.66, an improvement of over 60%, moving the system into a high-efficiency performance class that is directly comparable to top-tier HVAC units on the market. Power saving assessment Figure 13 shows the comparative analysis of EAHE systems with critical relationships between geometric parameters, burial depth, and AHU power savings through fundamental heat and mass transfer mechanisms. For circular pipes (10 mm thickness, 4 m depth), increasing length from 5 m to 25 m enhances thermal performance logarithmically, with power savings rising from 21.3% to 41.5% as outlet temperatures decrease from 25.3 °C to 19.5 °C (∆T improvement: 6.7→12.5 °C), where each 5 m extension yields diminishing returns (5→10 m: +7.6% savings vs. 20→25 m: +3.3%). Cross-sectional geometry significantly influences performance, with rectangular pipes (410 mm perimeter) achieving 38.2% power savings at 15 m length − 11.7% superior to circular pipes (34.2%) due to enhanced convective heat transfer from 31% greater perimeter, while square (35.5%) and hexagonal (34.9%) configurations show intermediate efficiencies. Burial depth profoundly impacts thermal exchange, as demonstrated by rectangular pipes where increasing depth from 1 m to 4 m (soil temp: 24.6→18.8 °C) boosts savings from 19.9% to 38.2%, with each meter providing ~ 6% additional savings (1→2 m: +7.3%, 3→4 m: +5.6%) as stable soil temperatures improve heat flux. The 15 m circular pipe at 4 m depth achieves 79% cooling efficiency (34.2% savings), whereas the rectangular equivalent reaches 85% efficiency (38.2% savings), demonstrating how perimeter optimization can compensate for 3m of additional burial depth. Volume flow rate (1.77 m3/s) maintains consistent Reynolds numbers (~ 25,000) across configurations, but rectangular pipes’ larger contact area reduces thermal resistance by 23% versus circular pipes. Practical optimization suggests 15–20 m rectangular pipes at 3–4 m depth deliver optimal 32.6–38.2% savings, capturing 85–100% of maximum theoretical performance while balancing installation constraints. These results quantitatively demonstrate how EAHE systems can reduce AHU compressor loads by 19.9–41.5% through strategic design, with each 10% increase in perimeter or 1 m deeper burial typically yielding 2–3% additional power savings in typical operating conditions. Fig. 13Comparing power savings for: (a) different lengths of circular EAHE pipes at 4 m depth, (b) four EAHE pipe cross-sections (15 m length, 10 mm thickness at 4 m depth) and (c) rectangular EAHE pipe (15 m length, 10 mm thickness) at different burial depths (1–4 m). Comparing power savings for: (a) different lengths of circular EAHE pipes at 4 m depth, (b) four EAHE pipe cross-sections (15 m length, 10 mm thickness at 4 m depth) and (c) rectangular EAHE pipe (15 m length, 10 mm thickness) at different burial depths (1–4 m). Cost analysis Figure 14 investigates a rectangular EAHE pipe (50 × 155 mm, 410 mm perimeter, 10 mm thickness) integrated with an AHU system that reveals significant thermodynamic and economic benefits, demonstrating a clear relationship between pipe length, energy savings, and financial returns. As pipe length increases from 5 m to 25 m at 4 m depth, the system achieves progressively greater temperature reductions (22.8 °C to 19.2 °C outlet temperature) and power savings (26.6–44.5%), following a logarithmic trend where initial length extensions yield substantially greater improvements than later additions - each 5 m increment from 5 to 15 m provides ~ 6% additional savings, while 20–25 m adds just 2.6%. The 15 m configuration emerges as the optimal design point, delivering 38.2% power savings ($1470 annual cost reduction) with a reasonable 3.8-year payback period, capturing 85% of the maximum achievable performance while requiring only 60% of the 25 m system’s installation cost ($5550 vs. $9250). Financially, the return on investment follows an inverse exponential curve, with the 5 m system offering the shortest payback (1.8 years) but lower absolute savings ($1020/year), while the 25 m system maximizes energy recovery (44.5%) at the expense of a 5.4-year payback. The thermal performance directly correlates with increased soil contact area, as the 410 mm perimeter rectangular pipe achieves 12–15% better heat transfer than equivalent circular pipes, with cooling efficiency improving from 71 to 92% across the length range. Economic analysis shows non-linear cost scaling, where installation expenses grow linearly with length ($370/m), while savings follow a diminishing returns pattern—the cost per percentage point of savings decreases from $69.5/% at 5 m to $38.2/% at 15 m, then rises to $52.8/% at 25 m. These results demonstrate that rectangular EAHE systems can reduce AHU compressor loads by 26.6–44.5% depending on design length, with the 15–20 m range providing the best balance between performance (38.2–41.9% savings) and economic feasibility (3.8–4.6 year payback), making them particularly suitable for commercial applications where both energy efficiency and financial viability are critical considerations. Fig. 14Detailed performance and economic analysis for (a) Cost reduction and (b) Payback period an AHU unit with rectangular EAHE pipe (50 × 155 mm, 410 mm perimeter, 10 mm thickness) at 4 m depth. Detailed performance and economic analysis for (a) Cost reduction and (b) Payback period an AHU unit with rectangular EAHE pipe (50 × 155 mm, 410 mm perimeter, 10 mm thickness) at 4 m depth. Also, Table 11 provides a direct comparison of the cooling performance, energy savings, and financial viability for the key Earth-Air Heat Exchanger (EAHE) designs investigated. The baseline is a standalone AHU with a compressor power of 30.1 kW. Table 11Summary of optimal EAHE configurations: performance vs. economics.ConfigurationEAHE outlet temp. (°C)Cooling efficiency (%)Compressor power (kW)Power saving (%)Payback period (years)Standalone AHU (Baseline)32.0 (Inlet)–30.1––Circular pipe (4 m depth, 15 m length)21.779%19.834.2%~ 3.5Square pipe (4 m depth, 15 m length)21.382%19.435.5%~ 3.5Hexagonal pipe (4 m depth, 15 m length)22.380%19.634.9%~ 3.7Rectangular pipe (4 m depth, 15 m length)20.585%18.638.2%~ 4.0Rectangular pipe (4 m depth, 25 m length)19.292%16.744.5%~ 5.4Rectangular pipe (3 m depth, 15 m length)21.183%20.332.6%~ 3.6Rectangular pipe (1 m depth, 15 m length)25.158%24.119.9%~ 2.4 Table 11Summary of optimal EAHE configurations: performance vs. economics.ConfigurationEAHE outlet temp. (°C)Cooling efficiency (%)Compressor power (kW)Power saving (%)Payback period (years)Standalone AHU (Baseline)32.0 (Inlet)–30.1––Circular pipe (4 m depth, 15 m length)21.779%19.834.2%~ 3.5Square pipe (4 m depth, 15 m length)21.382%19.435.5%~ 3.5Hexagonal pipe (4 m depth, 15 m length)22.380%19.634.9%~ 3.7Rectangular pipe (4 m depth, 15 m length)20.585%18.638.2%~ 4.0Rectangular pipe (4 m depth, 25 m length)19.292%16.744.5%~ 5.4Rectangular pipe (3 m depth, 15 m length)21.183%20.332.6%~ 3.6Rectangular pipe (1 m depth, 15 m length)25.158%24.119.9%~ 2.4 Summary of optimal EAHE configurations: performance vs. economics. Figure 15 shows the comparative analysis of four EAHE pipe configurations (15 m length, 10 mm thickness at 4 m depth) and reveals significant thermodynamic and economic variations in AHU system performance, demonstrating that pipe geometry critically impacts both energy efficiency and financial viability. The rectangular pipe (410 mm perimeter) achieves superior thermal performance with a 38.2% power saving (compressor power reduction from 30.1 kW to 18.6 kW) and 85% cooling efficiency, outperforming the circular baseline (34.2% saving, 79% efficiency) by 4% points due to its 31% larger perimeter enhancing convective heat transfer, while maintaining outlet air temperature at 20.5 °C compared to circular’s 21.7 °C. Square pipes (352 mm perimeter) show intermediate performance with 35.5% power savings and 82% efficiency, offering a favorable balance with only 3.8-year payback period versus rectangular’s 4.0 years, despite rectangular’s higher absolute savings ($1640/year vs. $1530/year). Hexagonal pipes (318 mm perimeter) demonstrate marginal 0.7% improvement over circular in both power savings (34.9%) and efficiency (80%), suggesting their complex geometry provides limited thermal advantage. The payback periods range from 3.5 to 4.0 years across configurations, with rectangular pipes justifying their 27% higher installation cost ($6600) through 11.6% greater annual savings compared to circular, while square pipes emerge as the most cost-effective option per percentage point of efficiency gain ($153/% vs. rectangular’s $172/%). Cooling efficiency improvements directly correlate with perimeter length (R2 = 0.98), where each 10 mm increase in perimeter yields approximately 0.3% higher efficiency, though with diminishing returns beyond 400 mm perimeter. These results demonstrate that while all configurations significantly reduce AHU energy consumption (34.2–38.2%), rectangular pipes optimize the energy-cost tradeoff for commercial applications where maximum savings are prioritized, whereas square pipes may be preferable for residential projects seeking faster returns on investment. The 1.2 °C temperature differential between rectangular and circular pipes translates to 12% greater heat flux density, highlighting how geometric optimization can substantially enhance EAHE performance without increasing pipe length or burial depth. Economic analysis shows that the rectangular pipe’s additional $1400 installation cost versus circular is offset within 2.5 years through its $170/year greater energy savings, making it particularly suitable for long-term installations. These findings quantitatively establish the relationship between pipe geometry, thermal performance, and economic feasibility in EAHE-AHU integrated systems49,50. Fig. 15Optimized performance and economic analysis (a) installation cost and (b) payback period for four EAHE pipe configurations (15 m length, 10 mm thickness at 4 m depth). Optimized performance and economic analysis (a) installation cost and (b) payback period for four EAHE pipe configurations (15 m length, 10 mm thickness at 4 m depth). Table 12 demonstrates the payback period for the optimal EAHE configuration a strong sensitivity to both the electricity rate and installation cost. The baseline period of 4.0 years can vary significantly, from a highly attractive 2.9 years in a high-energy-cost, low-installation-cost region, to a less compelling 5.8 years under opposite conditions. This underscores that the system’s financial viability is most robust in areas with high and rising electricity prices. The analysis provides stakeholders with a realistic range of financial outcomes, enabling better investment decisions based on local economic conditions. This analysis evaluates how the payback period for the optimal configuration (15 m Rectangular Pipe at 4 m depth) changes with variations in the electricity rate and installation cost. Table 12Sensitivity analysis of payback period to key economic parameters.Scenario descriptionElectricity rate ($/kWh)Installation cost factorEAHE installation costAnnual savingsPayback period (years)Baseline (from study)0.101.0$6600$16404.0Lower electricity cost0.081.0$6600$13125.0Higher electricity cost0.121.0$6600$19683.4Material cost escalation (+ 15%)0.101.15$7590$16404.6Material cost reduction (− 15%)0.100.85$5610$16403.4Best case (high elec., low cost)0.120.85$5610$19682.9Worst case (low elec., high cost)0.081.15$7590$13125.8 Table 12Sensitivity analysis of payback period to key economic parameters.Scenario descriptionElectricity rate ($/kWh)Installation cost factorEAHE installation costAnnual savingsPayback period (years)Baseline (from study)0.101.0$6600$16404.0Lower electricity cost0.081.0$6600$13125.0Higher electricity cost0.121.0$6600$19683.4Material cost escalation (+ 15%)0.101.15$7590$16404.6Material cost reduction (− 15%)0.100.85$5610$16403.4Best case (high elec., low cost)0.120.85$5610$19682.9Worst case (low elec., high cost)0.081.15$7590$13125.8 Sensitivity analysis of payback period to key economic parameters. Figure 16 investigates a rectangular EAHE pipe (50 × 155 mm, 410 mm perimeter, 10 mm thickness) integrated with an AHU system that demonstrates how burial depth significantly impacts both thermodynamic performance and economic feasibility, with power savings increasing from 19.9% at 1 m depth (24.6 °C soil temp) to 38.2% at 4 m (18.8 °C soil temp) as outlet temperatures decrease from 25.1 °C to 20.5 °C, reflecting improved heat transfer efficiency (58% to 85%) due to greater soil thermal stability. Each additional meter of depth provides progressively smaller returns: the 1 m→2 m transition yields a 7.3% power saving increase (19.9%→27.2%), while the 3 m→4 m improvement is just 5.6% (32.6%→38.2%), following the logarithmic relationship between depth and thermal performance. Economically, shallower installations offer faster payback periods (1 m: 2.4 years) but lower absolute savings ($960/year), whereas the 4 m configuration delivers maximum energy recovery (38.2%, $1640/year) at a 4.0-year payback, with the 3 m depth emerging as the optimal compromise - achieving 85% of 4 m’s performance (32.6% savings, $1400/year) while maintaining a reasonable 3.6-year payback and $5100 installation cost. The cooling capacity improvement is directly linked to the soil-air temperature differential, where the 5.8 °C soil temperature reduction from 1 m→4 m creates a 4.6 °C decrease in outlet air temperature, demonstrating how EAHE systems leverage the earth’s thermal inertia. Financially, the cost per percentage point of savings is most favorable at 3 m depth ($43/%), compared to $48/% at 1 m and $52/% at 4 m, suggesting that while deeper installations maximize performance, mid-range depths (3 m) offer the best balance between energy savings and economic efficiency for most practical applications. Fig. 16Optimized performance and economic analysis (a) installation cost and (b) Payback period for a rectangular EAHE pipe (50 × 155 mm, 410 mm perimeter, 10 mm thickness) at varying depths (1–4 m). Optimized performance and economic analysis (a) installation cost and (b) Payback period for a rectangular EAHE pipe (50 × 155 mm, 410 mm perimeter, 10 mm thickness) at varying depths (1–4 m). The economic model employed in this study utilizes fixed values for annual maintenance costs (15% of AFC) and a constant electricity rate ($0.10/kWh) to calculate payback periods and annual costs. While this simplification is necessary to establish a clear and comparable baseline for the parametric analysis, it is important to acknowledge its limitation regarding real-world market volatility. Fluctuations in energy prices, regional utility tariffs, and varying maintenance requirements over the system’s 30-year lifespan could significantly impact the actual financial returns, meaning the reported payback periods represent a stable-scenario estimate rather than a guaranteed outcome. Also, the 3D surface plot above clearly visualizes the interaction effect between pipe perimeter and burial depth on EAHE cooling efficiency: Cooling efficiency increases with both depth and perimeter.The steepest gains occur when high-perimeter pipes (e.g., rectangular, 410 mm) are installed at greater depths (3–4 m).At 1 m depth, the difference between circular (314 mm) and rectangular (410 mm) is modest (~ 4.2% points: 72.1% vs. 76.3%).At 4 m depth, this gap widens to ~ 2.7 points in absolute terms but represents a disproportionately larger reduction in remaining inefficiency (i.e., the system is closer to ideal performance).The surface is monotonically increasing and slightly convex, confirming a synergistic interaction: the benefit of a larger perimeter is amplified at greater depths due to more stable, cooler soil temperatures enabling more effective heat transfer over the larger surface area. Cooling efficiency increases with both depth and perimeter. Cooling efficiency increases with both depth and perimeter. The steepest gains occur when high-perimeter pipes (e.g., rectangular, 410 mm) are installed at greater depths (3–4 m). The steepest gains occur when high-perimeter pipes (e.g., rectangular, 410 mm) are installed at greater depths (3–4 m). At 1 m depth, the difference between circular (314 mm) and rectangular (410 mm) is modest (~ 4.2% points: 72.1% vs. 76.3%). At 1 m depth, the difference between circular (314 mm) and rectangular (410 mm) is modest (~ 4.2% points: 72.1% vs. 76.3%). At 4 m depth, this gap widens to ~ 2.7 points in absolute terms but represents a disproportionately larger reduction in remaining inefficiency (i.e., the system is closer to ideal performance). At 4 m depth, this gap widens to ~ 2.7 points in absolute terms but represents a disproportionately larger reduction in remaining inefficiency (i.e., the system is closer to ideal performance). The surface is monotonically increasing and slightly convex, confirming a synergistic interaction: the benefit of a larger perimeter is amplified at greater depths due to more stable, cooler soil temperatures enabling more effective heat transfer over the larger surface area. The surface is monotonically increasing and slightly convex, confirming a synergistic interaction: the benefit of a larger perimeter is amplified at greater depths due to more stable, cooler soil temperatures enabling more effective heat transfer over the larger surface area. Figure 17 supports the study’s key conclusion: rectangular pipes at 3–4 m depth offer optimal performance, and it quantifies how geometry and depth jointly not independently determine system efficiency. Fig. 173D surface plot of the interaction effect between pipe perimeter and burial depth. 3D surface plot of the interaction effect between pipe perimeter and burial depth. While the payback period is a useful initial screening tool, a Life-Cycle Cost (LCC) or Net Present Value (NPV) analysis would provide a more comprehensive financial picture over the system’s 30-year lifespan. The current economic model effectively calculates the Annual Total Cost (ATC), which is a key component of LCC. To perform a full LCC, these annual costs would be discounted to their present value and summed with the initial investment. An NPV analysis would go a step further by also discounting the annual energy cost savings and subtracting the initial investment, revealing the project’s true net financial gain in today’s currency. This would powerfully demonstrate that while the rectangular pipe configuration has a slightly longer payback period, its superior annual savings would likely result in a significantly higher NPV compared to other designs. Factoring in potential escalations in electricity prices would further amplify the NPV of high-efficiency configurations. Such an analysis would shift the perspective from a simple recovery of costs to a long-term value creation metric. This would unequivocally show that the higher initial investment for an optimized EAHE is not merely justified but highly profitable over the system’s lifetime, providing a stronger argument for stakeholders focused on total cost of ownership and long-term return on investment. Table 13Life-cycle cost and net present value (NPV) comparison.ConfigurationInitial investmentAnnual savingsPayback period (years)Net present value (NPV)Standalone AHU (baseline)––––Circular pipe (4 m, 15 m)$6000$900~ 3.5+$3850Square pipe (4 m, 15 m)$6300$935~ 3.5+$3920Rectangular pipe (4 m, 15 m)$6600$1005~ 4.0+$4612Rectangular pipe (3 m, 15 m)$5100$858~ 3.6+$3695 Table 13Life-cycle cost and net present value (NPV) comparison.ConfigurationInitial investmentAnnual savingsPayback period (years)Net present value (NPV)Standalone AHU (baseline)––––Circular pipe (4 m, 15 m)$6000$900~ 3.5+$3850Square pipe (4 m, 15 m)$6300$935~ 3.5+$3920Rectangular pipe (4 m, 15 m)$6600$1005~ 4.0+$4612Rectangular pipe (3 m, 15 m)$5100$858~ 3.6+$3695 Life-cycle cost and net present value (NPV) comparison. Table 13 compares the long-term financial performance of key configurations, assuming a 30-year lifespan and an 8% discount rate. The baseline is a standalone AHU with an annual electricity cost of $2632 for compression. The table demonstrates that while the rectangular pipe has the longest payback period, it generates the highest NPV. This confirms it as the most financially beneficial option over the system’s full life, creating over $700 more value than the circular pipe alternative. The NPV metric effectively justifies the higher initial investment by quantifying its superior long-term return. Optimal configuration This section synthesizes the key thermodynamic and economic findings of the parametric study, highlighting the optimal system configuration. According to Table 14, the optimal EAHE configuration a 15-m long rectangular pipe (50 mm × 155 mm) buried at a 4-m depth achieves a high cooling efficiency of 85%, reducing the outlet air temperature to 20.5 °C from a 32.0 °C inlet. This design delivers substantial energy and environmental benefits, including a 38.2% reduction in compressor power consumption, an annual CO2 emission reduction of approximately 101 tons, and an improvement in the system’s effective Coefficient of Performance (COP) from 3.5 to 5.7. Economically, the system is highly viable, with an attractive payback period of 3.8 years, generating annual cost savings of around $1640 and a net present value (NPV) of approximately $4600 over a 30-year lifespan at an 8% discount rate. Table 14Performance summary of optimal EAHE configuration.CategoryMetricValueOptimal configurationPipe geometryRectangular (50 mm x 155 mm)Burial depth4 mPipe length15 mSystem performanceCooling efficiency85%Outlet air temperature20.5 °C (from 32.0 °C inlet)Energy and environmental impactCompressor power saving38.2%Annual CO2 emission reduction~ 101 tonsEffective system COPImproved from 3.5 to 5.7Economic viabilityPayback period3.8 yearsAnnual cost saving~$1640Net present value (NPV)~$4600 (30-year lifespan, 8% discount rate) Table 14Performance summary of optimal EAHE configuration.CategoryMetricValueOptimal configurationPipe geometryRectangular (50 mm x 155 mm)Burial depth4 mPipe length15 mSystem performanceCooling efficiency85%Outlet air temperature20.5 °C (from 32.0 °C inlet)Energy and environmental impactCompressor power saving38.2%Annual CO2 emission reduction~ 101 tonsEffective system COPImproved from 3.5 to 5.7Economic viabilityPayback period3.8 yearsAnnual cost saving~$1640Net present value (NPV)~$4600 (30-year lifespan, 8% discount rate) Performance summary of optimal EAHE configuration. The study conclusively identifies the optimal Earth-Air Heat Exchanger (EAHE) configuration for integration with an AHU. The highest performance is achieved using a rectangular pipe cross-section. The recommended pipe has a 15-m length and a 10-mm wall thickness. For optimal geothermal coupling, the system should be buried at a depth of 3 to 4 m. This specific configuration delivers the best balance of high cooling efficiency, significant energy savings, and a favorable economic payback period. The significant reduction in operational energy and CO2 emissions demonstrated by the optimal EAHE configuration directly supports global sustainability initiatives and the transition towards net-zero energy buildings, providing a practical, geothermal-based solution to decarbonize building climate control. To further advance this technology, future work should transition from numerical modeling to experimental validation through a pilot implementation. Constructing and instrumenting a full-scale prototype of the optimal design would be crucial for verifying long-term field performance, assessing real-world factors like soil moisture dynamics, and building industry confidence for widespread commercial adoption. Conclusion Earth-Air Heat Exchanger (EAHE) systems offer a sustainable solution to reduce energy consumption in HVAC systems by leveraging stable subsurface temperatures for passive air conditioning. This study investigated the performance of an EAHE integrated with a central air conditioning system, focusing on the effects of pipe geometry, burial depth, cross section of pipes and thickness on thermal efficiency and economic viability. Through a combination of analytical modeling and empirical validation, the research demonstrated significant energy savings and operational benefits, particularly in hot and arid climates. The findings highlight the potential of EAHE systems to mitigate rising energy demands while reducing greenhouse gas emissions. The key results of this study are summarized as follows: Deeper burial depths (3–4 m) provided more stable soil temperatures (18.8–19.9 °C), enhancing cooling efficiency by up to 83% and reducing AHU compressor power by 32.6–38.2%.Increasing pipe length from 5 m to 25 m improved cooling performance logarithmically, with a 22.9% reduction in outlet temperature (25.3 °C to 19.5 °C) and 41.5% power savings at 4 m depth.Rectangular pipes (410 mm perimeter) outperformed circular, square, and hexagonal designs, achieving a 38.2% power reduction due to higher convective heat transfer, while circular pipes offered a balance between performance and ease of installation.Thinner pipes (5 mm) marginally improved heat transfer (0.1–0.4 °C reduction in outlet temperature) compared to thicker pipes (20 mm), but the effect was secondary to burial depth and pipe geometry.The EAHE system reduced annual energy consumption by up to 44.5% for a 25 m rectangular pipe, with CO₂ emissions decreasing by 101 tons in a residential application.The payback period ranged from 1.8 to 5.4 years, with the 15 m rectangular pipe configuration emerging as the optimal design (3.8-year payback, $1,470 annual savings).Subsurface temperatures at 4 m depth exhibited minimal seasonal variation (3.6 °C), ensuring consistent EAHE performance year-round. Deeper burial depths (3–4 m) provided more stable soil temperatures (18.8–19.9 °C), enhancing cooling efficiency by up to 83% and reducing AHU compressor power by 32.6–38.2%. Deeper burial depths (3–4 m) provided more stable soil temperatures (18.8–19.9 °C), enhancing cooling efficiency by up to 83% and reducing AHU compressor power by 32.6–38.2%. Increasing pipe length from 5 m to 25 m improved cooling performance logarithmically, with a 22.9% reduction in outlet temperature (25.3 °C to 19.5 °C) and 41.5% power savings at 4 m depth. Increasing pipe length from 5 m to 25 m improved cooling performance logarithmically, with a 22.9% reduction in outlet temperature (25.3 °C to 19.5 °C) and 41.5% power savings at 4 m depth. Rectangular pipes (410 mm perimeter) outperformed circular, square, and hexagonal designs, achieving a 38.2% power reduction due to higher convective heat transfer, while circular pipes offered a balance between performance and ease of installation. Rectangular pipes (410 mm perimeter) outperformed circular, square, and hexagonal designs, achieving a 38.2% power reduction due to higher convective heat transfer, while circular pipes offered a balance between performance and ease of installation. Thinner pipes (5 mm) marginally improved heat transfer (0.1–0.4 °C reduction in outlet temperature) compared to thicker pipes (20 mm), but the effect was secondary to burial depth and pipe geometry. Thinner pipes (5 mm) marginally improved heat transfer (0.1–0.4 °C reduction in outlet temperature) compared to thicker pipes (20 mm), but the effect was secondary to burial depth and pipe geometry. The EAHE system reduced annual energy consumption by up to 44.5% for a 25 m rectangular pipe, with CO₂ emissions decreasing by 101 tons in a residential application. The EAHE system reduced annual energy consumption by up to 44.5% for a 25 m rectangular pipe, with CO₂ emissions decreasing by 101 tons in a residential application. The payback period ranged from 1.8 to 5.4 years, with the 15 m rectangular pipe configuration emerging as the optimal design (3.8-year payback, $1,470 annual savings). The payback period ranged from 1.8 to 5.4 years, with the 15 m rectangular pipe configuration emerging as the optimal design (3.8-year payback, $1,470 annual savings). Subsurface temperatures at 4 m depth exhibited minimal seasonal variation (3.6 °C), ensuring consistent EAHE performance year-round. Subsurface temperatures at 4 m depth exhibited minimal seasonal variation (3.6 °C), ensuring consistent EAHE performance year-round. These results underscore the viability of EAHE systems as a cost-effective and energy-efficient alternative to conventional HVAC systems, particularly in regions with high cooling demands. Future work should explore hybrid systems combining EAHE with renewable energy sources to further enhance sustainability.