Quantifying crowding-ventilation effect on respiratory infections Authors: Wei Jia, Pan Cheng, Jian Hang, Hua Qian, Yuguo Li Published: 2026 ABSTRACT Crowded and poorly ventilated indoor spaces drive outbreaks of respiratory infections such as coronavirus disease 2019 (COVID-19), often leading to superspreading events. While overcrowding heightens risk, its interplay with space size and ventilation remains underexplored. We introduce a framework to assess this risk, using effective clean flow rate, which combines clean airflow (outdoor air, filtration, ultraviolet germicidal irradiation) with volume-time air clearance (VTAC), i.e., dilution from indoor air volume per person over time, and intake fraction time, which quantifies aerosol exposure risk independent of infectious quanta generation. Analysis of real outbreak data from jails, earthquake shelters, and dormitories shows modest spaciousness (16-32 m3/person) increases effective clean flow by 8.7 to 17.6 L/s per person in low-ventilation settings (0.5 L/s per person, 1-hour exposure), reducing exposure. Current standards, such as American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) 62.1-2022, fall short in crowded spaces, heightening infection risks. Our model predicts infection patterns, showing VTAC is a critical yet overlooked factor in limiting long-range airborne transmission. These insights call for updated ventilation and spaciousness standards to strengthen public health strategies. Introduction Crowded spaces have long driven outbreaks of respiratory infections, from tuberculosis in 19th-century tenements to coronavirus disease 2019 (COVID-19) in modern jails, nursing homes, and shelters1,2. Overcrowding persists across diverse settings, including hospitals3, public transit4, and homes in both developed and developing regions5,6. Epidemiological studies show elevated rates of acute respiratory infections in densely packed environments, such as earthquake shelters, compared to less crowded settings7. However, the mechanisms linking crowding to heightened infection risk, particularly how indoor space size and ventilation interact, remain underexplored, limiting effective public health interventions. Crowding is typically measured by occupant density (persons/m2), floor area per person (m2/person) or persons per room8. We propose spaciousness, defined as indoor air volume per person (m3/person), as a critical metric for diluting infectious aerosols. While close contact within 1─2 meters can drive short-range inhalation transmission, infection risks do not drop to zero beyond this range9–11. This observation supports that long-range airborne transmission also plays a significant role in disease spread, particularly for pathogens with high quanta generation rates. During the COVID-19 pandemic, outdoor spaces and large indoor venues (e.g., airport terminals) exhibited low transmission12,13, while superspreading events thrived in crowded, poorly ventilated settings like the Skagit Valley Choir outbreak, with an 87% attack rate in a 252 m2 hall14. These patterns underscore the importance of spaciousness and ventilation on airborne transmission for respiratory viruses, including influenza, rhinovirus, and severe acute respiratory syndrome coronavirus 2 (SARS-CoV-2)15,16. Despite these insights, most studies on crowding overlook ventilation’s role. Current ventilation standards, e.g., the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) 62.1-2022, prescribe outdoor air rates primarily to dilute non-infectious pollutants (volatile organic compounds, particulate matter, and carbon dioxide) and perceived odor, typically using per-person rates scaled to expected occupancy and floor area. Because airborne pathogen emission is largely independent of floor area, these standards systematically under-ventilated crowded spaces (often ≤5 L/s per person), potentially elevating infection risk during respiratory outbreaks. This disconnect highlights a critical gap in understanding how space size and airflow together mitigate transmission. To address this, we introduce two metrics: the effective clean flow rate, which integrates clean air equivalents (e.g., outdoor air, filtration, ultraviolet germicidal irradiation) with volume-time air clearance (VTAC), i.e., the dilution effect of spaciousness over exposure time, and intake fraction time, which quantifies aerosol exposure risk independent of infectious quanta. Analyzing outbreak data from jails, earthquake shelters, and dormitories, we demonstrate how these metrics predict infection patterns, revealing that modest spaciousness significantly reduces risk in poorly ventilated settings. Our findings challenge existing standards and advocate for new guidelines that balance spaciousness and ventilation to curb respiratory infections, offering an approach to creating safer indoor environments for public health. Results Spaciousness enhances dilution in poorly ventilated settings To unravel how crowding fuels respiratory infections, we developed a framework centered on the effective clean flow rate, a metric that blends clean air equivalents (outdoor air, filtration, particle settling, and natural and artificial deactivation) with VTAC. Using a quasi-steady adaptation of the Wells-Riley equation17,18 (see “Methods”), we standardized this metric to compare aerosol dilution across diverse spaces, building on ASHRAE 241’s equivalent clean airflow concept19. Removal of respiratory infectious aerosols by clean air equivalents in a room is in analogue with that of carbon dioxide (CO2) from exhaled breath by ventilation air. To demonstrate VTAC, we modeled CO2 buildup from exhaled breath in two idealized settings: a crowded space with 1.8 m3/person and a spacious one with 72 m3/person, both ventilated at 10 L/s per person over a 4-h co-exposure period (Fig. 1a). Despite identical ventilation, the crowded space, with a high air change rate per hour (20 ACH), reaches CO2 equilibrium quickly, while the spacious space (0.5 ACH) shows slower buildup, reducing early aerosol exposure (Fig. 1b). This reveals spaciousness, via VTAC, as a powerful buffer against exhaled contaminants, particularly in the critical early hours of exposure.Fig. 1Modest spaciousness contributes significant additional dilution ability in poorly ventilated spaces.a Schematic of two spaciousness levels (1.8 and 72 m3/person). b CO2 concentration build-up profiles at a ventilation rate of 10 L/s per person and 4-h co-exposure for the two spaciousness levels shown in (a), corresponding to air change rates of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$n=$$\end{document}n= 0.5 and 20 h−1. c Effective clean flow rate as a function of spaciousness at three ventilation rates (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{c}=$$\end{document}qc= 0.5, 10, and 100 L/s per person; different colored lines) for 4-h co-exposure, with ventilation and volume-time air clearance (VTAC) asymptotes. The orange-shaded area (top-left, labeled “Crowded”) indicates relatively overcrowded conditions, while the cyan-shaded area (bottom-right, labeled “Spacious”) indicates relatively spacious conditions. d Effective clean flow rate at four typical spaciousness levels (2, 16, 32, and 64 m3/person) under two ventilation rates (0.5 and 10 L/s per person) and two co-exposure periods (1 and 4 h). e CO2 concentration profiles after the index case leaves the space (continuation of (b)) for the two spaciousness levels shown in (a). f Effective clean flow rate as a function of spaciousness with 4-h co-exposure followed by different post-exposure periods (0, 1, and 2 h) at a ventilation rate of 10 L/s per person, with ventilation and VTAC asymptotes. The orange-shaded area (left, labeled “Crowded”) indicates relatively overcrowded conditions, while the cyan-shaded area (right, labeled “Spacious”) indicates relatively spacious conditions. Volume-time air clearance (VTAC) is the additional dilution provided by indoor air volume per person over exposure time. Source data are available in the Source Data_Main.xlsx file on GitHub. Modest spaciousness contributes significant additional dilution ability in poorly ventilated spaces. a Schematic of two spaciousness levels (1.8 and 72 m3/person). b CO2 concentration build-up profiles at a ventilation rate of 10 L/s per person and 4-h co-exposure for the two spaciousness levels shown in (a), corresponding to air change rates of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$n=$$\end{document}n= 0.5 and 20 h−1. c Effective clean flow rate as a function of spaciousness at three ventilation rates (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{c}=$$\end{document}qc= 0.5, 10, and 100 L/s per person; different colored lines) for 4-h co-exposure, with ventilation and volume-time air clearance (VTAC) asymptotes. The orange-shaded area (top-left, labeled “Crowded”) indicates relatively overcrowded conditions, while the cyan-shaded area (bottom-right, labeled “Spacious”) indicates relatively spacious conditions. d Effective clean flow rate at four typical spaciousness levels (2, 16, 32, and 64 m3/person) under two ventilation rates (0.5 and 10 L/s per person) and two co-exposure periods (1 and 4 h). e CO2 concentration profiles after the index case leaves the space (continuation of (b)) for the two spaciousness levels shown in (a). f Effective clean flow rate as a function of spaciousness with 4-h co-exposure followed by different post-exposure periods (0, 1, and 2 h) at a ventilation rate of 10 L/s per person, with ventilation and VTAC asymptotes. The orange-shaded area (left, labeled “Crowded”) indicates relatively overcrowded conditions, while the cyan-shaded area (right, labeled “Spacious”) indicates relatively spacious conditions. Volume-time air clearance (VTAC) is the additional dilution provided by indoor air volume per person over exposure time. Source data are available in the Source Data_Main.xlsx file on GitHub. The effective clean flow rate quantifies this effect (Fig. 1c). In the crowded space, it matches clean air equivalents (~10 L/s per person). In the spacious space (64 m3/person), it surges to 16.6 L/s per person, with 6.6 L/s per person attributed to VTAC. At an extreme spaciousness of 1000 m3/person, the effective clean flow rate reaches 145.6 L/s per person, almost entirely due to VTAC. Crucially, modest spaciousness (increase from 2 to 32 m3/person) has the greatest impact in poorly ventilated settings (0.5 L/s per person, 4-h exposure), boosting effective clean flow rate from 0.7 to 4.8 L/s per person, a nearly seven-fold increase (Fig. 1d). For 1-h exposure, a spaciousness of 32 m3/person provides a VTAC of 17.8 L/s per person. In contrast, in a 4-h exposure setting with high ventilation rates (100 L/s per person), typical spaciousness levels contribute minimally (e.g., ~26% increase even at 300 m3/person), as physical airflow dominates dilution (Fig. 1c). We also examined exposure after an infected individual leaves the space (Fig. 1e). Using the quasi-steady approach, the effective clean flow rate decreases as post-exposure time extends (Fig. 1f), reflecting the persistence of aerosols in larger volumes with low ventilation. This underscores VTAC’s role in mitigating lingering risks in poorly ventilated environments. Intake fraction time links crowding to infection risk To directly assess exposure risk, we introduced intake fraction time (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt), defined as \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}=\frac{{q}_{{in}}\Delta t}{{q}_{e}}$$\end{document}iFt=qinΔtqe, where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{{in}}$$\end{document}qin is the inhalation rate in L/s , \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta t$$\end{document}Δt is exposure duration in hours, and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}$$\end{document}qe is the effective clean flow rate in L/s per person. This metric represents the equivalent time all susceptible individuals in the space are exposed to infected individuals’ exhaled aerosols, isolating the effects of crowding and dilution from quanta generation rate. Under low infection risk, secondary infections are approximated by \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt times the quanta generation rate. In 1-h exposure settings with poor ventilation (0.5 L/s per person), increasing spaciousness from 2 to 16 m3/person reduces \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt from 0.07 to below 0.02 h, a critical threshold for preventing secondary infections at a quanta generation rate of 50 quanta/h (Fig. 2a, b). Supplementary Note 4 showed that a realistic distribution of quanta generation rate predicted a threshold \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt between 0.01–0.02 h for the most common ASHRAE spaces. In well-ventilated spaces (10 L/s per person), the same increase has a smaller effect, highlighting that VTAC is most impactful when ventilation is inadequate.Fig. 2Modest spaciousness significantly reduces intake fraction time and infection risk.a Intake fraction time (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt) as a function of spaciousness at three clean air equivalent rates (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{c}=$$\end{document}qc= 0.5, 10 and 100 L/s per person; different colored lines) for two co-exposure periods (1 h: dotted lines; 4 h: solid lines). The effect of varying metabolic rate on \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt is shown in Supplementary Fig. 10. b Intake fraction time at four typical spaciousness levels (2, 16, 32 and 64 m3 per person) under two clean air equivalent rates (0.5 and 10 L/s per person) and two co-exposure periods (1 and 4 h). In a–b, the inhalation rate equals 0.1 L/s (at 1 metabolic equivalent). c Incidence rates of acute respiratory infections (#/10,000 person-days) versus spaciousness in earthquake shelters7. Green squares represent observed data points, and the green dotted line shows the fitted logarithmic regression with equation and coefficient of determination (R2) as indicated. d \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{f}$$\end{document}Cf-standardized incidence rate versus spaciousness levels in six datasets of respiratory infection outbreaks. Pink solid and dashed lines represent theoretical crowding factor (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{f}$$\end{document}Cf) curves for two co-exposure periods (4 and 12 h) at a clean air equivalent of 0.5 L/s per person and well-mixed condition (room-averaged air distribution effectiveness \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\varepsilon=1$$\end{document}ε=1), while the six symbols show observed \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{f}$$\end{document}Cf-standardized incidence rates from the six cited studies7,20–24. The effect of spatial non-uniformity is further provided in Supplementary Fig. 3. Source data are available in the Source Data_Main.xlsx on GitHub. Modest spaciousness significantly reduces intake fraction time and infection risk. a Intake fraction time (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt) as a function of spaciousness at three clean air equivalent rates (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{c}=$$\end{document}qc= 0.5, 10 and 100 L/s per person; different colored lines) for two co-exposure periods (1 h: dotted lines; 4 h: solid lines). The effect of varying metabolic rate on \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt is shown in Supplementary Fig. 10. b Intake fraction time at four typical spaciousness levels (2, 16, 32 and 64 m3 per person) under two clean air equivalent rates (0.5 and 10 L/s per person) and two co-exposure periods (1 and 4 h). In a–b, the inhalation rate equals 0.1 L/s (at 1 metabolic equivalent). c Incidence rates of acute respiratory infections (#/10,000 person-days) versus spaciousness in earthquake shelters7. Green squares represent observed data points, and the green dotted line shows the fitted logarithmic regression with equation and coefficient of determination (R2) as indicated. d \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{f}$$\end{document}Cf-standardized incidence rate versus spaciousness levels in six datasets of respiratory infection outbreaks. Pink solid and dashed lines represent theoretical crowding factor (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{f}$$\end{document}Cf) curves for two co-exposure periods (4 and 12 h) at a clean air equivalent of 0.5 L/s per person and well-mixed condition (room-averaged air distribution effectiveness \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\varepsilon=1$$\end{document}ε=1), while the six symbols show observed \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{f}$$\end{document}Cf-standardized incidence rates from the six cited studies7,20–24. The effect of spatial non-uniformity is further provided in Supplementary Fig. 3. Source data are available in the Source Data_Main.xlsx on GitHub. We validated this model using six datasets of respiratory infection outbreaks, i.e., influenza in military camps20,21, acute respiratory infections in earthquake shelters7, pneumococcal disease in jails22, common colds in dormitories23, and COVID-19 in prisons24. Because quanta generation rates differ significantly across pathogens and are heterogeneous even for the same pathogen, we normalized the observed incidence rates in each dataset to its most-crowded condition, eliminating the need for pathogen-specific generation rates (see Supplementary Note 2). Normalizing incidence rates to align with \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt, we found strong agreement with our predicted crowding factor at a typical poor ventilation rate of 0.5 L/s per person for 4- and 12-h exposures (Fig. 2c, d). For example, shelters with 35–40 m3/person or more showed significantly lower infection rates, a pattern unexplained by short-range airborne transmission alone (distances <2 meters), supporting the role of long-range airborne transmission in crowded settings. Reassessing ventilation standards for infection control The effective clean flow rate is bounded by two asymptotes: clean air equivalents \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{c}$$\end{document}qc and volume-time air clearance (VTAC, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{{vt}}=\frac{2{V}_{p}}{\Delta t\cdot 3.6}$$\end{document}qvt=2VpΔt⋅3.6), where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${V}_{p}$$\end{document}Vp is spaciousness in m3/person (Fig. 1c, f). Approximately \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}^{\frac{5}{4}}={q}_{c}^{\frac{5}{4}}+{q}_{{vt}}^{\frac{5}{4}}$$\end{document}qe54=qc54+qvt54 (Supplementary Method 3). At their intersection \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$({q}_{c}={q}_{{vt}})$$\end{document}(qc=qvt), the equivalence point occurs where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${V}_{p,c}=1.8{q}_{c}\Delta t$$\end{document}Vp,c=1.8qcΔt, and the effective clean flow rate is approximately 1.76 times the clean air equivalents (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}\approx 1.76{q}_{c}$$\end{document}qe≈1.76qc), and the approximate formula gives a coefficient of 1.74. For a ventilation rate of 0.5 L/s per person and a 4-h co-exposure, this point is at 3.6 m3/person, showing that even modest spaciousness significantly enhances dilution in low-ventilation settings. At high ventilation (100 L/s per person), the equivalence point shifts to 720 m3/person, far beyond typical indoor spaces, indicating ventilation’s dominance in such cases. For a targeted intake fraction time \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt, the spaciousness-ventilation pair graphs (Fig. 3a, c) can be used for design. In poor-ventilation settings, better spaciousness complements, and in crowded settings, better ventilation is essential. Poorly ventilated and crowded spaces should be avoided. A targeted \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt corresponds to a required effective clean flow rate, which can be delivered by either sufficient VTAC or sufficient clean air equivalent, and a combination of the two (Fig. 3b). Settings of 35–40 m3/person or more can achieve more than 19 L/s per person at a co-exposure time of 1 h (Fig. 3d), supporting the observed low infection (Fig. 2d), but decrease to 5–6 L/s per person at a co-exposure time of 4 h.Fig. 3Combining volume-time air clearance (VTAC) and clean air equivalent to achieve a certain intake fraction time (iFt) threshold under five co-exposure periods (0.5, 1, 2, 5, and 8 h).a Combinations of spaciousness and clean air equivalent required for \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt = 0.01 h. b VTAC versus clean air equivalents for \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt = 0.01 h. c Combinations of spaciousness and clean air equivalent for \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt = 0.02 h. In a–c, different colored lines represent the five co-exposure periods (0.5, 1, 2, 5, 8 h). Light red shading indicates settings that are either overcrowded or poorly ventilated, while dark red shading indicates settings that are both overcrowded and poorly ventilated. d Required spaciousness for targeted effective clean airflow with two co-exposure periods (1 and 4 h) when the clean air equivalent is 1 L/s per person. Source data are available in the Source Data_Main.xlsx file on GitHub. Combining volume-time air clearance (VTAC) and clean air equivalent to achieve a certain intake fraction time (iFt) threshold under five co-exposure periods (0.5, 1, 2, 5, and 8 h). a Combinations of spaciousness and clean air equivalent required for \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt = 0.01 h. b VTAC versus clean air equivalents for \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt = 0.01 h. c Combinations of spaciousness and clean air equivalent for \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt = 0.02 h. In a–c, different colored lines represent the five co-exposure periods (0.5, 1, 2, 5, 8 h). Light red shading indicates settings that are either overcrowded or poorly ventilated, while dark red shading indicates settings that are both overcrowded and poorly ventilated. d Required spaciousness for targeted effective clean airflow with two co-exposure periods (1 and 4 h) when the clean air equivalent is 1 L/s per person. Source data are available in the Source Data_Main.xlsx file on GitHub. We applied ASHRAE 62.125 and ASHRAE 24119 ventilation standards, assuming a 3-meter ceiling to estimate spaciousness across various occupancy categories, such as offices, lecture halls, and prisons. ASHRAE 62.1, designed for general indoor air quality, assigns lower ventilation rates to crowded spaces based on smaller surface areas (Fig. 4c), resulting in a wide intake fraction time range (0.00002–0.2 h, Fig. 4a). This variability is inadequate for infection control, as crowded settings require more, not less, ventilation to offset low spaciousness. ASHRAE 241, tailored for infectious disease control, reduces this range to 0.003-0.1 h (Fig. 4b), a notable improvement, but still fails to fully address crowding’s impact. The effect of age-, sex-, and weight-related variability in inhalation rate on intake fraction time is investigated in Supplementary Fig. 11. Lower outdoor air flow rates are assigned by ASHRAE 62.1 in crowded settings, although the corresponding air change rates are greater. The ASHRAE 62.1 air change rates in crowded settings are lower than the ASHRAE 241 values, as the latter provides a slightly greater clean air equivalent at low spaciousness (Supplementary Fig. 8 in Supplementary Note 5).Fig. 4Comparison of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) standards 62.1 and 241.a, b Estimated intake fraction time (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt) as a function of spaciousness for different space categories in ASHRAE 62.1 (a) and ASHRAE 241 (b). Different colored dots in (a) represent assigned exposure times (0.1, 0.5, 1.0, 2.0, 4.0 and 8.0 h), while all points in (b) are shown in yellow as no exposure time classification was applied in ASHRAE 241. The light red shading in (a, b) indicates the region where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt exceeds the 0.02 h threshold (justified in Supplementary Fig. 5). The effect of inhalation rate (age-, weight- and sex-dependent) on \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt is further provided in Supplementary Fig. 11. c, d Required minimum clean air equivalent (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{c}$$\end{document}qc) as a function of spaciousness for different space categories in ASHRAE 62.1 (c) and ASHRAE 241 (d). Blue dots indicate calculated values, and dashed lines represent linear regression fits with equations and coefficient of determination (R2) as indicated. The clean air equivalent (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{c}$$\end{document}qc) applied in (a, b) includes contributions from surface deposition, natural virus deactivation, and the minimum outdoor or equivalent clean airflow rates specified by the standards. Detailed values are provided in Supplementary Tables 4, 5. Source data are available in the Source Data_Main.xlsx file on GitHub. Comparison of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) standards 62.1 and 241. a, b Estimated intake fraction time (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt) as a function of spaciousness for different space categories in ASHRAE 62.1 (a) and ASHRAE 241 (b). Different colored dots in (a) represent assigned exposure times (0.1, 0.5, 1.0, 2.0, 4.0 and 8.0 h), while all points in (b) are shown in yellow as no exposure time classification was applied in ASHRAE 241. The light red shading in (a, b) indicates the region where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt exceeds the 0.02 h threshold (justified in Supplementary Fig. 5). The effect of inhalation rate (age-, weight- and sex-dependent) on \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt is further provided in Supplementary Fig. 11. c, d Required minimum clean air equivalent (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{c}$$\end{document}qc) as a function of spaciousness for different space categories in ASHRAE 62.1 (c) and ASHRAE 241 (d). Blue dots indicate calculated values, and dashed lines represent linear regression fits with equations and coefficient of determination (R2) as indicated. The clean air equivalent (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{c}$$\end{document}qc) applied in (a, b) includes contributions from surface deposition, natural virus deactivation, and the minimum outdoor or equivalent clean airflow rates specified by the standards. Detailed values are provided in Supplementary Tables 4, 5. Source data are available in the Source Data_Main.xlsx file on GitHub. To address this, we propose revised ventilation rates targeting an intake fraction time of 0.02 h (for quanta generation rate of 50 quanta/h), which requires higher ventilation in crowded settings (Supplementary Tables 4, 5, Supplementary Fig. 9 in Supplementary Note 6). For example, a space with 2 m3/person and 4-h exposure needs ~20 L/s per person (at 1 MET) to meet this threshold, compared to ASHRAE 62.1’s typical 2.5 L/s per person. This highlights a critical flaw in current standards, where crowded spaces like jails or shelters are under-ventilated, exacerbating infection risk. Discussion For centuries, crowded spaces have been hotspots for respiratory infections, from tuberculosis in 19th-century slums to COVID-19 in modern jails, nursing homes, and shelters1,2. Our study offers a framework to explain this link, showing how spaciousness—indoor air volume per person (m3/person)—works alongside ventilation to dilute infectious aerosols, especially in poorly ventilated environments. We introduced two metrics: the effective clean flow rate and intake fraction time. These metrics illuminate why cramped, stuffy settings exacerbate outbreaks while larger, well-ventilated spaces curb transmission, providing a mechanistic basis for a long-standing public health challenge. Our results demonstrate that modest spaciousness (16–32 m3/person) can boost the effective clean flow rate by 8.7 to 17.6 L/s per person in low-ventilation settings (0.5 L/s per person and 1-h exposure), reducing \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt from 0.07 to below 0.02 h—a critical threshold for preventing secondary infections at a quanta generation rate of 50 quanta/h (Fig. 2a, b). This effect is evident in outbreaks like the Skagit Valley Choir event, where a spacious 252 m2 hall (4.1 m3/person, <1 ACH) saw an 87% attack rate due to poor ventilation and prolonged singing14. Similarly, a Guangzhou restaurant outbreak (145 m2, ~1.6 m3/person, ~0.5 ACH) reported 9 cases, driven by stagnant air despite ample space26. In contrast, airplane cabins with high ventilation (15-20 ACH) and low spaciousness (~1.5 m3/person) had low transmission rates27, as ventilation dominated12. These examples highlight VTAC’s pivotal role when ventilation is weak, reducing airborne inhalation exposure beyond the close range. Crowding is traditionally measured by occupant density (persons/m2), floor area per person, or persons per room8. Our focus on spaciousness captures the air volume available for dilution, distinct from occupancy’s effect of increasing susceptible individuals. Earthquake shelter data showed lower infection rates at 35-40 m3/person7, a pattern not fully explained by short-range airborne transmission (distances <2 meters), supporting long-range airborne transmission16. Prison outbreaks, with <1 m3/person and 4–6 ACH, had infection rates three times the general population, underscoring the combined risk of crowding and poor ventilation24. The close alignment of our model with these real-world datasets validates the predictive power of VTAC and offers new mechanistic insight for infection control. Current ventilation standards, such as ASHRAE 62.1, paradoxically assign lower per-person ventilation rates to crowded spaces with smaller surface areas, yielding \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt spanning four orders of magnitude (0.00002–0.2 h, Fig. 4a). Even the infection-control-oriented ASHRAE 241 narrows this range only modestly (0.003-0.1 h, Fig. 4b) and still under-ventilates high-density settings like jails and shelters. For 1-h exposure setting, we propose either a minimum spaciousness of 35–40 m3/person (~12–13 m2/person at 3 m ceiling height for baseline ventilation of 0.5 L/s per person) or equivalently higher ventilation rates (e.g., ≥20 L/s per person at 2 m3/person) is required to achieve a target \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt of 0.02 h and minimize secondary infections for pathogens like COVID-19 or influenza. This threshold aligns with observed low transmission in spacious emergency facilities ( ~ 413 m3/patient)13 and elevated community transmission in Hong Kong’s densely subdivided flats (average 5.3 m2/person)28. These findings suggest standards must prioritize both spaciousness and ventilation, especially where airflow is limited. Designing substantially larger spaces isn’t always feasible—greater air volumes increase construction costs, energy use, and land demands29. Nevertheless, our framework shows that targeted interventions can achieve comparable protection: in existing crowded buildings, portable High-Efficiency Particulate Air (HEPA) filtration or upgraded Heating, Ventilation, and Air Conditioning (HVAC) systems can compensate for low VTAC, whereas new high-occupancy designs (hospitals, schools, transit hubs, emergency shelters) can prioritise generous air volume to reduce long-term reliance on mechanical ventilation and energy use. Policymakers and building-code authorities should therefore integrate both spaciousness and ventilation requirements into standards, particularly for vulnerable settings where crowding is unavoidable. Air change rate alone is also misleading. For instance, 12 ACH recommendation by most existing guidelines translates to 80 L/s in a 4 × 2 × 3 m3 room but 320 L/s in a 6 × 4 × 4 m3 room, yielding four-fold lower exposure in the larger space30–32. Our study has limitations. We assumed uniform air mixing, which may not hold in settings with strong air stratification or directional flows, as seen in some outbreaks26,33. However, the effect of non-uniformity on clean air equivalent can be adjusted by mean air distribution effectiveness, whereas VTAC itself remains unaffected (Supplementary Note 1). Quanta generation rates are heterogeneous, varying with the immunity of infectors and susceptible individuals, as well as respiratory activities34. This impacts infection risk estimates for a given \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt. Crowding also affects the interpersonal distance and close contact duration in terms of short-range airborne transmission35. Future work should validate effective clean flow rate and intake fraction time across diverse real-world environments (offices, transit, or informal settlements) and incorporate variable quanta rates, non-uniform mixing, and multi-route transmission through field studies and advanced modeling (e.g., computational fluid dynamics). Integrating these factors could refine our understanding of aerosol dynamics. In conclusion, spaciousness, through VTAC, and ventilation are deeply intertwined, with even modest air volume per person serving as a critical buffer against respiratory infection when ventilation is limited. The effective clean flow rate and intake fraction time metrics introduced here provide a unified, mechanistic framework to predict exposure and guide evidence-based ventilation standards. By explicitly accounting for both spaciousness and airflow, we can move beyond air-change-rate-centric guidelines and design resilient indoor environments that substantially reduce transmission risk for COVID-19, influenza, and future aerosol-borne pathogens36,37. Methods To investigate how crowding drives respiratory infection risk, we developed a framework to quantify the dilution of infectious aerosols in indoor spaces, focusing on the interplay between spaciousness (indoor air volume per person) and ventilation. Our approach introduces two metrics: the effective clean flow rate \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}$$\end{document}qe, which integrates clean air equivalents with VTAC, and intake fraction time \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt, which measures airborne exposure risk independent of infectious quanta. Below, we outline the mathematical modeling, outbreak data analysis, ventilation standards application, and key assumptions used to develop and validate these metrics. No ethics approval was required for this research, as the study involved only mathematical modeling and secondary analysis of publicly available, aggregated epidemiological data from the literature, with no new human participants or identifiable individual-level data. Written informed consent was therefore not applicable. Modeling effective clean flow rate We modeled a well-mixed room with volume \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V$$\end{document}V (m3) containing \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$m$$\end{document}m infectors, each emitting infectious quanta at rate \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${Q}_{i}$$\end{document}Qi (quanta/h), where the total quanta generation rate is \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$Q={\sum }_{i=1}^{m}{Q}_{i}$$\end{document}Q=∑i=1mQi. Clean air equivalents, including outdoor air, filtration, deposition, natural and artificial virus deactivation, are denoted \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{C}$$\end{document}qC (L/s), representing the room’s total clean air flow. Uniform mixing assumes a consistent infectious quanta concentration throughout the room. The temporal concentration \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$c$$\end{document}c (quanta/m3) is governed by \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\frac{{dc}}{{dt}}=-{nc}+\frac{Q}{V}$$\end{document}dcdt=−nc+QV, and the concentration \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$c$$\end{document}c evolves as described by Peng et al.38:Co-exposure (infectors enter at \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$t=0$$\end{document}t=0): With a constant quanta generation rate \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$Q$$\end{document}Q, the concentration is:1\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$c=\frac{Q}{{q}_{C}}\left(1-{e}^{-{nt}}\right)$$\end{document}c=QqC1−e−ntPost-exposure (infectors leave at \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$t=0$$\end{document}t=0, initial concentration \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${c}_{i}$$\end{document}ci). The concentration decays as:2\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$c={c}_{i}{e}^{-{nt}}$$\end{document}c=cie−ntHere, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$n=\frac{3.6{q}_{C}}{V}$$\end{document}n=3.6qCV, with \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{C}$$\end{document}qC in L/s and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V$$\end{document}V in m3, is the air change rate (ACH, 1/h). At steady state (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${nt}\to {\infty }$$\end{document}nt→∞), \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{C}$$\end{document}qC governs dilution; When post-exposure exit, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$n$$\end{document}n drives concentration decay. Co-exposure (infectors enter at \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$t=0$$\end{document}t=0): With a constant quanta generation rate \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$Q$$\end{document}Q, the concentration is:1\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$c=\frac{Q}{{q}_{C}}\left(1-{e}^{-{nt}}\right)$$\end{document}c=QqC1−e−nt Co-exposure (infectors enter at \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$t=0$$\end{document}t=0): With a constant quanta generation rate \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$Q$$\end{document}Q, the concentration is:1\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$c=\frac{Q}{{q}_{C}}\left(1-{e}^{-{nt}}\right)$$\end{document}c=QqC1−e−nt Post-exposure (infectors leave at \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$t=0$$\end{document}t=0, initial concentration \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${c}_{i}$$\end{document}ci). The concentration decays as:2\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$c={c}_{i}{e}^{-{nt}}$$\end{document}c=cie−ntHere, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$n=\frac{3.6{q}_{C}}{V}$$\end{document}n=3.6qCV, with \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{C}$$\end{document}qC in L/s and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V$$\end{document}V in m3, is the air change rate (ACH, 1/h). At steady state (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${nt}\to {\infty }$$\end{document}nt→∞), \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{C}$$\end{document}qC governs dilution; When post-exposure exit, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$n$$\end{document}n drives concentration decay. Post-exposure (infectors leave at \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$t=0$$\end{document}t=0, initial concentration \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${c}_{i}$$\end{document}ci). The concentration decays as:2\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$c={c}_{i}{e}^{-{nt}}$$\end{document}c=cie−ntHere, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$n=\frac{3.6{q}_{C}}{V}$$\end{document}n=3.6qCV, with \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{C}$$\end{document}qC in L/s and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V$$\end{document}V in m3, is the air change rate (ACH, 1/h). At steady state (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${nt}\to {\infty }$$\end{document}nt→∞), \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{C}$$\end{document}qC governs dilution; When post-exposure exit, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$n$$\end{document}n drives concentration decay. For susceptible individuals, we modeled two exposure scenarios:Scenario S1 (Co-exposure): Susceptibles and infectors share the space for \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta t$$\end{document}Δt hours. The inhaled quanta dose \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${d}_{j}$$\end{document}dj for person \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$j$$\end{document}j is:3\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${d}_{j}={q}_{{in},j}{\int }_{t=0}^{\Delta t}c{dt}=\frac{{q}_{{in},j}Q}{{q}_{C}}\Delta t\left(1-{C}_{T}\right)$$\end{document}dj=qin,j∫t=0Δtcdt=qin,jQqCΔt1−CTwhere \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{{in},j}$$\end{document}qin,j is the inhalation rate (L/s), and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{T}=\frac{1-{e}^{-n\Delta t}}{n\Delta t}$$\end{document}CT=1−e−nΔtnΔt is the transient correction factor accounting for non-steady-state conditions (Supplementary Method 1).Scenario S2 (Co-exposure plus post-exposure): Susceptibles remain for \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta {t}_{0}$$\end{document}Δt0 hours after infectors leave:4\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${d}_{j}=\frac{{q}_{{in},j}Q}{{q}_{C}}\Delta t\left(1-{C}_{T}\right)+\frac{{q}_{{in},j}Q}{{q}_{C}}\left(1-{e}^{-n\Delta t}\right){C}_{T0}\Delta {t}_{0}$$\end{document}dj=qin,jQqCΔt1−CT+qin,jQqC1−e−nΔtCT0Δt0where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{T}=\frac{1-{e}^{-n\Delta t}}{n\Delta t}$$\end{document}CT=1−e−nΔtnΔt and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{T0}=\frac{1-{e}^{-n\Delta {t}_{0}}}{n\Delta {t}_{0}}$$\end{document}CT0=1−e−nΔt0nΔt0. Scenario S1 (Co-exposure): Susceptibles and infectors share the space for \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta t$$\end{document}Δt hours. The inhaled quanta dose \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${d}_{j}$$\end{document}dj for person \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$j$$\end{document}j is:3\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${d}_{j}={q}_{{in},j}{\int }_{t=0}^{\Delta t}c{dt}=\frac{{q}_{{in},j}Q}{{q}_{C}}\Delta t\left(1-{C}_{T}\right)$$\end{document}dj=qin,j∫t=0Δtcdt=qin,jQqCΔt1−CTwhere \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{{in},j}$$\end{document}qin,j is the inhalation rate (L/s), and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{T}=\frac{1-{e}^{-n\Delta t}}{n\Delta t}$$\end{document}CT=1−e−nΔtnΔt is the transient correction factor accounting for non-steady-state conditions (Supplementary Method 1). Scenario S1 (Co-exposure): Susceptibles and infectors share the space for \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta t$$\end{document}Δt hours. The inhaled quanta dose \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${d}_{j}$$\end{document}dj for person \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$j$$\end{document}j is:3\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${d}_{j}={q}_{{in},j}{\int }_{t=0}^{\Delta t}c{dt}=\frac{{q}_{{in},j}Q}{{q}_{C}}\Delta t\left(1-{C}_{T}\right)$$\end{document}dj=qin,j∫t=0Δtcdt=qin,jQqCΔt1−CTwhere \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{{in},j}$$\end{document}qin,j is the inhalation rate (L/s), and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{T}=\frac{1-{e}^{-n\Delta t}}{n\Delta t}$$\end{document}CT=1−e−nΔtnΔt is the transient correction factor accounting for non-steady-state conditions (Supplementary Method 1). Scenario S2 (Co-exposure plus post-exposure): Susceptibles remain for \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta {t}_{0}$$\end{document}Δt0 hours after infectors leave:4\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${d}_{j}=\frac{{q}_{{in},j}Q}{{q}_{C}}\Delta t\left(1-{C}_{T}\right)+\frac{{q}_{{in},j}Q}{{q}_{C}}\left(1-{e}^{-n\Delta t}\right){C}_{T0}\Delta {t}_{0}$$\end{document}dj=qin,jQqCΔt1−CT+qin,jQqC1−e−nΔtCT0Δt0where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{T}=\frac{1-{e}^{-n\Delta t}}{n\Delta t}$$\end{document}CT=1−e−nΔtnΔt and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{T0}=\frac{1-{e}^{-n\Delta {t}_{0}}}{n\Delta {t}_{0}}$$\end{document}CT0=1−e−nΔt0nΔt0. Scenario S2 (Co-exposure plus post-exposure): Susceptibles remain for \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta {t}_{0}$$\end{document}Δt0 hours after infectors leave:4\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${d}_{j}=\frac{{q}_{{in},j}Q}{{q}_{C}}\Delta t\left(1-{C}_{T}\right)+\frac{{q}_{{in},j}Q}{{q}_{C}}\left(1-{e}^{-n\Delta t}\right){C}_{T0}\Delta {t}_{0}$$\end{document}dj=qin,jQqCΔt1−CT+qin,jQqC1−e−nΔtCT0Δt0where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{T}=\frac{1-{e}^{-n\Delta t}}{n\Delta t}$$\end{document}CT=1−e−nΔtnΔt and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{T0}=\frac{1-{e}^{-n\Delta {t}_{0}}}{n\Delta {t}_{0}}$$\end{document}CT0=1−e−nΔt0nΔt0. We reformulated this as a pseudo-steady form to define the effective clean flow rate \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}$$\end{document}qe (L/s per person)18 when the infection risk is relatively low:5\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${N}_{\iota }\approx {{\rm{Q}}}\frac{{q}_{{in}}}{{q}_{e}}\Delta t$$\end{document}Nι≈QqinqeΔtwhere \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}=\frac{{q}_{c}}{1-{C}_{T}}$$\end{document}qe=qc1−CT for S1, and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}=\frac{{q}_{c}}{1-{C}_{T}{e}^{-n\Delta {t}_{0}}}$$\end{document}qe=qc1−CTe−nΔt0 for S2, with \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{c}=\frac{{q}_{C}}{{N}_{\sigma }}$$\end{document}qc=qCNσ (clean air equivalent per person). The effective clean flow rate has two asymptotes (Supplementary Method 2):VTAC asymptote: As \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$n\Delta t\to 0$$\end{document}nΔt→0, for S1, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}\approx {q}_{{vt}}=\frac{2{V}_{p}}{\Delta t\cdot 3.6}$$\end{document}qe≈qvt=2VpΔt⋅3.6, where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${V}_{p}=V/{N}_{\sigma }$$\end{document}Vp=V/Nσ (m3/person) is spaciousness, defining the volume-time air clearance (VTAC) with exposure time \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta t$$\end{document}Δt. For S2, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}\approx {q}_{{vt}}=\frac{2{V}_{p}}{\left(\Delta t+2\Delta {t}_{0}\right)\cdot 3.6}$$\end{document}qe≈qvt=2VpΔt+2Δt0⋅3.6, where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta {t}_{0}$$\end{document}Δt0 is the post-exposure time after infectors leave.Ventilation asymptote: As \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$n\Delta t\to {\infty }$$\end{document}nΔt→∞, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}\approx {q}_{c}$$\end{document}qe≈qc for both S1 and S2. VTAC asymptote: As \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$n\Delta t\to 0$$\end{document}nΔt→0, for S1, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}\approx {q}_{{vt}}=\frac{2{V}_{p}}{\Delta t\cdot 3.6}$$\end{document}qe≈qvt=2VpΔt⋅3.6, where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${V}_{p}=V/{N}_{\sigma }$$\end{document}Vp=V/Nσ (m3/person) is spaciousness, defining the volume-time air clearance (VTAC) with exposure time \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta t$$\end{document}Δt. For S2, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}\approx {q}_{{vt}}=\frac{2{V}_{p}}{\left(\Delta t+2\Delta {t}_{0}\right)\cdot 3.6}$$\end{document}qe≈qvt=2VpΔt+2Δt0⋅3.6, where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta {t}_{0}$$\end{document}Δt0 is the post-exposure time after infectors leave. VTAC asymptote: As \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$n\Delta t\to 0$$\end{document}nΔt→0, for S1, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}\approx {q}_{{vt}}=\frac{2{V}_{p}}{\Delta t\cdot 3.6}$$\end{document}qe≈qvt=2VpΔt⋅3.6, where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${V}_{p}=V/{N}_{\sigma }$$\end{document}Vp=V/Nσ (m3/person) is spaciousness, defining the volume-time air clearance (VTAC) with exposure time \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta t$$\end{document}Δt. For S2, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}\approx {q}_{{vt}}=\frac{2{V}_{p}}{\left(\Delta t+2\Delta {t}_{0}\right)\cdot 3.6}$$\end{document}qe≈qvt=2VpΔt+2Δt0⋅3.6, where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta {t}_{0}$$\end{document}Δt0 is the post-exposure time after infectors leave. Ventilation asymptote: As \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$n\Delta t\to {\infty }$$\end{document}nΔt→∞, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}\approx {q}_{c}$$\end{document}qe≈qc for both S1 and S2. Ventilation asymptote: As \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$n\Delta t\to {\infty }$$\end{document}nΔt→∞, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}\approx {q}_{c}$$\end{document}qe≈qc for both S1 and S2. This framework, inspired by ASHRAE 241’s equivalent clean air concept19, enables comparison of dilution across spaces by integrating clean air equivalents and VTAC. Modeling intake fraction time To quantify airborne exposure risk, we defined intake fraction time: \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}=\frac{{q}_{{in}}\Delta t}{{q}_{e}}$$\end{document}iFt=qinΔtqe, so the mean number of the newly infected \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${N}_{\iota }\approx {{iF}}_{t}\cdot Q$$\end{document}Nι≈iFt⋅Q. This metric represents the equivalent time all susceptible individuals in the space are exposed to infectors’ exhaled aerosols (or quanta), allowing direct comparison across spaces. A threshold \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt (e.g., 0.02 h for \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$Q$$\end{document}Q = 50 quanta/h) targets \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${N}_{\iota } < 1$$\end{document}Nι<1, guiding infection control by balancing ventilation and spaciousness. We assumed a constant inhalation rate \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{{in}}$$\end{document}qin = 0.1 L/s at 1 MET (resting metabolic rate)39. Additionally, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\frac{{q}_{{in}}}{{q}_{e}}$$\end{document}qinqe is somehow a concept of rebreathed fraction40, with \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{c}$$\end{document}qc replaced by \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}$$\end{document}qe. Analysis of ventilation standards We applied outdoor air rates and occupancy data from ASHRAE 62.125 and equivalent clean airflow from ASHRAE 24119 to assess their effectiveness for infection control. We further combined contributions from surface deposition (0.3 1/h) and natural virus deactivation (0.63 1/h) as clean air equivalent \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{c}$$\end{document}qc (see parameter justifications in Supplementary Note 3)14. Spaciousness was estimated assuming a 3-meter ceiling height across settings like offices, lecture halls, and prisons in Supplementary Tables 4, 5, Fig. 4, and Supplementary Figs. 6–9. We assigned six exposure times (0.1, 0.5, 1, 2, 4, 8 h) and metabolic rates39, with inhalation rate \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{q}_{{in}}=q}_{{in},0}\times {{\rm{MET}}}$$\end{document}qin=qin,0×MET, where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{{in},0}=0.1$$\end{document}qin,0=0.1 L/s at 1 MET41. These data were used to calculate \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{e}$$\end{document}qe, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${q}_{{vt}}$$\end{document}qvt and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt, evaluating how standards address crowding’s impact on transmission risk. Outbreak data analysis We conducted a literature search to identify datasets with at least three crowding levels (e.g., floor area or air volume per person) and corresponding respiratory infection incidences. Six datasets met these criteria:Influenza in military camps20,21.Acute respiratory infections in earthquake shelters7.Pneumococcal disease in jails22.COVID-19 in prisons24, with floor area estimated from 60 ft² per prisoner at 70%, 85%, and 105% design capacity.Common colds with measured air volume, ventilation, and infection incidence23. Influenza in military camps20,21. Influenza in military camps20,21. Acute respiratory infections in earthquake shelters7. Acute respiratory infections in earthquake shelters7. Pneumococcal disease in jails22. Pneumococcal disease in jails22. COVID-19 in prisons24, with floor area estimated from 60 ft² per prisoner at 70%, 85%, and 105% design capacity. COVID-19 in prisons24, with floor area estimated from 60 ft² per prisoner at 70%, 85%, and 105% design capacity. Common colds with measured air volume, ventilation, and infection incidence23. Common colds with measured air volume, ventilation, and infection incidence23. Infection incidence rates in each outbreak dataset were normalized to its most-crowded condition, i.e., \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{f}$$\end{document}Cf-standardized incidence rate, enabling direct comparison with the predicted crowding factor (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${C}_{f}$$\end{document}Cf) from our model at a typical poor clean air equivalent of 0.5 L/s per person and exposure durations of 4 and 12 h (detailed derivation in Supplementary Note 2). We validated the model by comparing predicted \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{iF}}_{t}$$\end{document}iFt with observed infection patterns, focusing on settings like shelters (5–35 m3/person) and prisons ( < 1 m3/person). Model assumptions and limitations The model assumes uniform air mixing, constant quanta generation rates across infectors, and constant inhalation rates (e.g., 0.1 L/s for a resting adult at 1 MET) in the main text. Real-world settings may exhibit non-uniform mixing, as seen in outbreaks like a restaurant26,33, or variable quanta generation rates due to activities like singing14. Non-uniform concentration distributions and individual exposure variations were partly explored using a generalized Wells-Riley equation to account for spatial and temporal heterogeneity in Jia et al.18. We also extend this work by investigating the effects of non-uniform air mixing (Supplementary Notes 1, 2), heterogeneous quanta generation (Supplementary Note 4), and individual-specific inhalation rates (Supplementary Note 7). All data analysis, modeling, and visualization were performed using MATLAB (R2023a, MathWorks) and Microsoft Excel (365, Microsoft). Computational fluid dynamics (CFD) simulations were conducted using ANSYS Fluent (2024 R2, ANSYS Inc.), and final figure assembly was carried out using Microsoft PowerPoint (365, Microsoft). Reporting summary Further information on research design is available in the Nature Portfolio Reporting Summary linked to this article. Supplementary information Supplementary Information Peer Review file Reporting Summary Supplementary Information Peer Review file Reporting Summary