Techno‐Economic Assessment of a Hydrogen‐Assisted Hybrid Renewable Microgrid with Fuel Cells for Off‐Grid Electrification Authors: Taib Hasan, Prapti Das, Md. Feroz Ali, Md Shafiul Alam, Mohammad Ali, Imil Hamda Imran Published: 2026 ABSTRACT ABSTRACTRural electrification in coastal Bangladesh faces challenges from geographic isolation, weak grid access, and growing energy demand. This study designs and evaluates an off‐grid hybrid renewable microgrid for Char Ishwar, Noakhali, using HOMER Pro (version 3.14.2). The proposed system integrates solar photovoltaic (PV), wind turbine (WT), battery energy storage system (BESS), electrolyzer, hydrogen (H2) storage tank, and fuel cell (FC) to enhance reliability and mitigate renewable intermittency. Three configurations were analyzed: Case A (PV–WT–BESS–Converter–Electrolyzer–FC–H2 Tank), Case B (WT‐based), and Case C (PV‐based), supplying electricity to 180 rural households. Case A emerged as the optimal solution, achieving a cost of energy (COE) of $0.139/kWh, a net present cost (NPC) of $1.28 million, and a capital cost of $594,206. The system achieved near‐zero net CO2 emissions of –3.79 kg/year, a value arising from HOMER Pro's baseline emission offset accounting, wherein avoided emissions from near‐100% renewable generation are credited against the assumed grid emission factor, rather than implying physical carbon sequestration, highlighting the substantial environmental benefits of green hydrogen integration. Comprehensive sensitivity analysis shows wind speed and load demand strongly influence system economics, validating configuration robustness and enabling sustainable, reliable, cost‐effective electrification for coastal Bangladesh. Abbreviations Battery Energy Storage System Cumulative Distribution Function Cost of Energy Duration Curve Demand‐Side Management Fuel Cell Global Horizontal Irradiation Hybrid Optimization of Multiple Energy Resources Hybrid Renewable Energy System Infrastructure Development Company Limited Levelized Cost of Energy Levelized Cost of Hydrogen National Aeronautics and Space Administration Net Present Cost National Renewable Energy Laboratory Non‐dominated Sorting Genetic Algorithm II Power‐to‐Gas‐to‐Power Payback Time in Monetary Terms Photovoltaic Renewable Fraction State of Charge Surface Meteorology and Solar Energy Wind Turbine Introduction Amid rising global energy demand and the urgent necessity to address climate change, the pursuit of sustainable and renewable energy solutions has become increasingly vital. Bangladesh, as a developing nation with a rapidly growing population, faces a severe energy crisis that poses risks to both socioeconomic progress and environmental sustainability [1]. With more than 160 million inhabitants and a steadily expanding economy, the country's energy requirements have grown more complex and demanding [2, 3]. Recent global assessments indicate that nearly 675 million people worldwide remain without electricity, including about 41 million in Bangladesh, which continues to hinder productivity and sustainable development [4]. The nation's energy insecurity is made worse by its reliance on nonrenewable energy sources, which also contribute to environmental damage by emitting large amounts of CO2 [5]. Currently, a significant share of global energy demand is met through fossil fuels, which are major contributors to global warming [6]. Hydrogen, owing to its high specific energy, has emerged as a promising energy carrier and an efficient medium for energy storage [7]. While hydrogen can be derived from resources such as coal, natural gas, and biomass, its production through water electrolysis powered by renewable energy sources has demonstrated considerable potential in minimizing environmental impacts. Renewable energy systems can address the limitations of fossil fuels by fulfilling energy demand, enabling long‐term sustainable generation, and reducing adverse environmental consequences [8]. However, fluctuations in renewable energy output, driven by the variable nature of weather conditions such as solar radiation and wind speed, create reliability challenges. To overcome these issues, storage systems become indispensable, though often associated with high costs. In off‐grid renewable applications, the limited capacity of conventional storage frequently leads to excess energy, which in some cases may surpass 60% of total generation [9]. Integrating a hydrogen production subsystem offers a practical solution by converting surplus energy into green hydrogen via an electrolyzer, with storage in hydrogen tanks for later utilization [10]. This stored hydrogen can subsequently be converted back into electricity using FCs, which act as backup units to meet demand during periods of low renewable generation. Consequently, hydrogen applications in renewable‐based systems hold significant promise for electrification in remote and underserved regions [11]. Renewable energy technologies are increasingly recognized as sustainable alternatives to fossil fuels. As of 2026, Bangladesh's total installed renewable capacity reaches 1,694.46 MW, with grid‐connected systems contributing 77.7% and off‐grid systems 22.3%. Solar energy dominates the mix (82.7%), followed by hydropower (13.6%) and wind (3.7%), while biomass and biogas play minor roles [12]. Around six million Solar Home Systems deployed under the IDCOL program highlight the success of off‐grid electrification [13, 14]. However, large‐scale grid integration remains constrained by financial, infrastructural, and technical challenges. To address these issues, this study proposes a hybrid renewable microgrid for Char Ishwar, Noakhali, integrating solar PV, WTs, battery storage, hydrogen production and storage, and FCs. Optimized using HOMER Pro, the system ensures reliable, low‐carbon electricity for remote coastal communities. Hybrid renewable–hydrogen microgrids have gained significant scholarly attention as viable solutions for low‐carbon, resilient, and decentralized energy systems, particularly in regions with high fuel costs, unreliable grids, or strong decarbonization goals. A consistent finding across the literature is the trade‐off between environmental benefits and the high capital and storage costs of hydrogen technologies, which continue to limit large‐scale deployment despite technological progress. Many studies emphasize optimal sizing and techno‐economic performance under diverse climatic and load conditions. Alturki (2022) [15] optimized a PV–wind–generator–storage–FC system in Yanbu, Saudi Arabia, achieving an LCOE of $0.155/kWh and an LCOH of $25.6/kg, while identifying hydrogen components as the dominant contributor to NPC. Similarly, Alharthi (2024) [16], showed that insufficient battery integration reduces FC lifetime and increases costs, highlighting the need for hybrid storage architectures. Regional comparisons further demonstrate context‐dependent feasibility. Ram et al. (2023) [17] reported lower costs in Fiji due to complementary renewable resources, whereas Kumar et al. (2024) [18] emphasized the role of financial incentives in rural India. DSM has been shown to improve system economics, as demonstrated by Youssef et al. (2024) [19], though excess electricity and storage inefficiencies remain challenges. Overall, the literature underscores that integrated storage design, optimized dispatch, and supportive policies are essential for advancing hydrogen‐based microgrids. Tiong et al. (2022) [20] demonstrated that grid‐connected microgrids integrating solar, wind, battery, and hydrogen storage achieve lower NPC and LCOE than stand‐alone systems, though reliance on grid electricity reduces overall emission mitigation, highlighting a trade‐off between cost efficiency and decarbonization depth. In an urban European context, Basnet et al. (2024) [21] showed that at electricity prices above €140/MWh, renewable sources could supply up to 70% of grid demand and 80% of electrolyzer demand, substantially lowering CO2 emissions, yet hydrogen production costs remained high, emphasizing the need for policy support and electrolysis cost reductions. Comparative storage studies consistently identify hybrid solutions as cost‐optimal. El Bakkali et al. (2022) [22] found that combined battery–hydrogen systems minimized energy costs, whereas hydrogen‐only storage resulted in prohibitive NPC. Similarly, Kapen et al. (2022) [23] reported very low LCOH under optimized hybrid configurations despite high upfront investments. Sector‐specific analyses further highlight hydrogen's flexibility benefits. Vichos et al. (2022) [24] reported LCOE reductions exceeding 40% in port applications, while Cruz‐Soto et al. (2022) [25] emphasized the need for major FC cost reductions. Advanced optimization studies by Akarsu et al. (2022) [26] and Le et al. (2023) [27] underscore the role of sophisticated algorithms in balancing cost, reliability, and emissions. Large‐scale analysis by Timalsina and Ghahremanlou (2024) [28] optimized a wind‐to‐hydrogen system in Newfoundland and achieved a short‐term LCOH of $3.43/kg, illustrating the significant cost advantages achievable at scale. Song et al. (2024) [29] investigated 100% renewable energy systems for data centers in South Korea and projected that on‐site hydrogen production becomes economically viable after 2030, with NPC reductions exceeding 75% as green hydrogen prices decline, highlighting the strong time dependence of hydrogen competitiveness. Review studies provide broader system‐level insights. Modu et al. (2023) [30] reported efficiency improvements of up to 85% and cost reductions of 20% in hybrid renewable–hydrogen systems, while identifying high capital investment and storage losses as persistent barriers. Li et al. (2023) [31] showed that coordinated electric and hydrogen storage across multiple microgrids can reduce costs by 15% and enhance reliability by 25%, although hydrogen storage remains the dominant cost component. Yousri et al. (2023) [32] demonstrated that advanced energy management systems can deliver customer savings exceeding 80%, albeit with increased system complexity. Application‐specific studies confirm hydrogen's versatility but reiterate economic challenges. Urs et al. (2023) [33] achieved a 78% RF with an LCOH of $3.117/kg in a UAE commercial microgrid. Optimization studies by Kumar et al. (2022) [34], Alturki (2022) [15], Mandić et al. (2023) [35], and Caliskan and Percin (2024) [36] consistently show that hydrogen enhances long‐duration storage and reliability under optimized hybrid configurations. Alhawsawi et al. (2024) [37] performed a comparative assessment of geothermal, wind, and photovoltaic resources, concluding that PV‐grid‐connected hybrid systems deliver the highest energy production with minimal system complexity. Bin et al. (2022) [38] demonstrated that optimal battery energy storage sizing in campus microgrids reduced grid electricity costs by 36.6%, yielding savings of $668.8/day, though grid dependency persisted as a limitation. Environmental performance remains a key driver of recent microgrid research. Almohaimeed et al. (2023) [39] quantified CO2 emission reductions at Qassim University from 615.8 Mt to 147.4 Mt following microgrid deployment, while Abdelsattar et al. (2024) [40] reported concurrent reductions in emissions and operational costs in Hurghada, Egypt, using PV–wind–diesel hybrids. Islanded and rural electrification studies further highlight the role of HRES in energy access. Molu et al. (2023) [41] demonstrated that a solar–wind–biogas hybrid system for Manoka Island, Cameroon, achieved an energy cost of $0.1981/kWh and an NPV of $2 209 741, though high battery costs remained a challenge. Pérez Uc et al. (2024) [42], in a comprehensive review of HOMER‐based HRES applications, confirmed that integrating solar, wind, and biomass reduces fossil‐fuel dependence across sectors, but high capital costs and technological constraints persist. Barakat et al. (2024) [43] showed that advanced multi‐objective optimization using NSGA‐II significantly improves the economic and sustainability performance of PV–wind–battery systems with EV charging integration, emphasizing the importance of algorithmic advances alongside hardware cost reductions. Mohamed G. Moh Almihat and Kahn (2023) [44] emphasized that integrated control strategies are essential to minimize COE and NPC in solar–wind–diesel–battery microgrids. Demand‐side efficiency measures increasingly complement supply‐side optimization. Nassar et al. (2024) [45] showed that replacing conventional lighting with LEDs reduced required batteries from 56 to 22 and PV panels from 20 to 8, achieving an LCOE of $0.12/kWh and reducing NPC by 30%. Nassar et al. (2024) [46] demonstrated that optimized hybrid systems could supply 82% of Palestine's energy demand from renewables, significantly reducing costs and emissions. El‐Khozondar et al. (2022) [47] showed that PV–wind–diesel systems for COVID‐19 quarantine centers in Gaza reduced COE by 54.89% with a payback period of 1.8 years. Hakizimana et al. (2024) [48] demonstrated that grid‐connected PV systems in industrial facilities achieved a 10‐year payback and reduced CO2 emissions by 6,555.1 tons annually. Overall, the literature shows that hybrid renewable–hydrogen energy systems, optimized using HOMER Pro and advanced algorithms, can substantially reduce energy costs, emissions, and grid dependence. Grid‐connected systems generally offer better economic performance, while off‐grid systems achieve higher renewable fractions at higher costs. Hydrogen is most effective when combined with battery storage and advanced energy management. However, high capital costs, storage inefficiencies, and system complexity persist, highlighting the need for cost reductions, improved optimization, and supportive policy frameworks. Despite the growing interest in hybrid renewable energy systems (HRES) in Bangladesh, existing studies are predominantly limited to single‐source or dual‐source configurations, such as standalone solar PV or wind‐based microgrids. The integrated deployment of advanced multi‐source systems combining solar PV, WTs, BESS, and hydrogen‐based technologies—including electrolyzers, hydrogen storage tanks, and FCs—remains insufficiently explored under realistic operating conditions. Moreover, prior research rarely incorporates long‐term techno‐economic optimization using high‐resolution time‐series data that reflect local climatic variability, seasonal demand fluctuations, and component‐level interactions. Comprehensive sensitivity analyses addressing uncertainties in renewable resource availability, load demand, and economic parameters are also scarce, leaving critical questions unresolved regarding the feasibility, optimal configuration, cost‐effectiveness, reliability, and emission reduction potential of hydrogen‐assisted hybrid microgrids for rural electrification in Bangladesh. To address these gaps, this study aims to design and evaluate an optimized off‐grid hybrid renewable microgrid tailored to rural coastal communities by integrating solar PV, WTs, BESS, electrolyzers, hydrogen tanks, and FCs. Using HOMER Pro, multiple system configurations are assessed to identify the optimal solution based on COE, NPC, system reliability, and environmental performance. The study further examines the role of hydrogen‐based long‐term storage in mitigating renewable intermittency and enhancing energy security, supported by extensive sensitivity analyses to evaluate system robustness under varying climatic, load, and economic conditions. Collectively, this work contributes a comprehensive techno‐economic framework, quantitative insights into hydrogen–battery hybrid storage integration, and policy‐relevant guidance for deploying scalable, low‐carbon microgrids in remote and vulnerable regions of Bangladesh. Materials and Methods Site Location Char Ishwar, situated in the eastern region of Hatiya Upazila under Noakhali District, Bangladesh (22°17.2′N, 91°10.0′E), covers an area of around 55 square kilometers. The proposed microgrid is designed to meet a daily community demand of 1956.87 kWh with a peak load of 268.19 kW. Being a coastal and riverine area, Char Ishwar faces high exposure to tidal surges, flooding, and erosion, while also offering prospects for agriculture, fisheries, and renewable energy deployment. Figure 1 highlights its geographical boundaries, underscoring the critical need for resilient energy systems and sustainable development measures in this vulnerable region. Geographic location of the study area. Load Profile Table 1 presents the estimated load calculation for a single household, based on common electrical appliances such as fans, lighting, TV, iron, desktop, refrigerator, random load, and water pump. The total daily consumption is 10.8715 kWh/day, where the refrigerator and water pump are the major contributors. This load represents a community‐type demand profile, typical of rural households. When scaled to 180 households, the community demand reaches 1956.87 kWh/day with a peak load of 268.19 kW. TABLE 1Daily Energy Consumption of Electrical Components.ComponentsRatingsQuantityOperating hours per dayTotal demand (kWh/d)Fan60481.92Lighting Bulbs155100.75TV50150.25Iron130010.1750.2275Desktop250141Refrigerator3501134.55Random Load56160.224Water pump130011.51.95Total10.8715John Wiley & Sons, Ltd. Daily Energy Consumption of Electrical Components. Figure 2 shows the temporal variation of electrical load demand at both hourly and monthly scales. Figure 2a illustrates the 3D hourly–monthly electrical load profile derived from the given dataset. The x‐axis represents the hour of the day, the y‐axis denotes the months from January to December, and the z‐axis shows the load demand in kW. A consistent diurnal pattern is observed for all months, with minimum demand during late‐night and early‐morning hours and a sharp rise after 06:00. Peak demand occurs between 12:00 and 18:00. Seasonal variation is clearly visible, with summer months (June–August) exhibiting significantly higher peak loads, exceeding 160 kW, compared to winter months (December–February), where peak values remain below approximately 120 kW. This indicates increased energy usage during warmer periods. Figure 2b presents the monthly average load demand, with error bars indicating the minimum and maximum hourly loads for each month. The average demand increases gradually from January to July, reaching a maximum in mid‐summer, and then decreases toward December. Larger error bars during summer months reflect greater intra‐day variability, while smaller ranges in winter indicate more stable demand. Together, the figures highlight the combined effects of daily and seasonal variations on load behavior. Electrical load profile: (a) Hourly–monthly (kW). (b) Monthly average load with minimum–maximum hourly variation. Resources Site‐specific renewable resource variables, such as solar radiation, clearness index, temperature, and wind speed, are critical for realistic modeling in HOMER. NASA's Surface Meteorology and Solar Energy (SSE) database provided solar irradiation data for the research site [49]. HOMER Pro leverages long‐term averaged climate information from NASA, generally lasting 22 years (1983–2005), to offer trustworthy averages of temperature, wind speed, and solar radiation for the specified site [50]. Solar Irradiance and Clearness Index The average global horizontal irradiance (GHI) and clearness index at the research site are shown to vary monthly in Figure 3. The highest daily radiation is recorded in April (5.51 kWh/m2/day) and March (5.44 kWh/m2/day), while the lowest is recorded in July (4.04 kWh/m2/day). The clearness index has an inverse trend, with a minimum of 0.367 in July and a maximum of 0.630 in December. Although seasonal monsoon cloud cover considerably lowers sunlight from June to September, the yearly mean radiation of 4.56 kWh/m2/day indicates moderate solar potential. Increased solar radiation increases PV systems' capacity to produce electricity, while the clearness index, which measures air transparency, influences their efficiency by figuring out how much sunlight really reaches the panels [49]. Solar GHI and clearness index for the site. Wind Speed Figure 4 presents the monthly average wind speed distribution at 10 m above sea level. Wind speeds peak during July and June, reflecting strong monsoonal influence, while the lowest occurs in December and February. Moderate values are observed during spring and autumn, with May and September showing transitional patterns. The annual mean wind speed is 5.41 m/s, indicating favorable wind energy potential, particularly during the summer monsoon period, making this location suitable for hybrid renewable energy integration. Higher wind speeds enhance heat dissipation from solar panels, thereby improving their operating efficiency [51]. Conversely, cloud cover reduces solar irradiance and diminishes PV generation, though wind can help disperse clouds and support solar output. In addition, the performance of WTs is directly dependent on wind velocity; greater wind speeds lead to higher electricity production, while lower speeds result in reduced output [52]. Monthly average wind speed for the site. Temperature Figure 5 Illustrates the Daily Temperature Profile of the Site, Showing an Average of 26.24°C. The Performance of Solar PV Systems Is Closely Influenced by Temperature Fluctuations, as Higher Temperatures Reduce Module Efficiency by Increasing the Internal Resistance of PV Panels [53]. Monthly average temperature for the site. Solar PV The real power (PPV ) of the PV panel under real operation and climatic conditions can be written in Equation (1) as [54]: (1) PPV=PSTC1+βpTcell−TSTCHtHSTC where β p is the power temperature coefficient, PSTC is the power output at Standard Test Conditions (STC), TSTC is the cell's surface temperature at STC and Tcell is the actual cell surface temperature, Ht is the real solar irradiance, and HSTC is the irradiance at STC. The cell surface temperature Tcell can be written in Equation (2) as [55]: (2) Tcell=T∞+7.8×10−2Ht where T ∞ is the ambient temperature. Wind Turbine Equation (3) enables the estimation of wind power at different heights as described in [56]. With the known turbine density, it is possible to determine wind acceleration variation, or conversely, calculate the density when wind acceleration is available. The fundamental power equation for WTs is expressed as: (3) P=12CpAρv3 wherein, P is the WT power output in watts; ρ is the wind power density in W/m2; v is the wind velocity in m/s; Cp is the rotor efficiency, and A is the rotor swept area in m2. Moreover, wind energy modeling can be expressed in Equation (4) as [57]: (4) EW=PratVZ,t−Vcut−inVrat−Vcut−inVcut−in