Analysis of the impact of non-real-time frequency sampling and damping coefficient on the dynamic frequency support response of grid-forming type renewable energy Authors: Xiang Tao, Shuai Zhang, Hao He, Junjie Xiong, Wei He, Wei Zeng Published: 2025 ABSTRACT Grid-forming type control has become an important control mode of renewable energy inverters in practice, since it makes renewable energy could provide the dynamic frequency support for power system like conventional synchronous generator. However, experiments shows that its dynamic frequency support response characteristics are contrary to the original design intention of grid-forming type control. For example, the inertia output doesn’t increase to the maximum value as expected at the moment of disturbance. Instead, it follows a trend of initially increasing and then decreasing. This paper conducts the relative analyse research. It reveals the reason causing the above problem is the grid-forming type renewable energy does not sample the grid voltage frequency in real time for closed-loop control, but instead by constructing an intrinsic equivalent frequency. Furthermore, it constructs one frequency support response model taking into account the impact of non-real-time frequency sampling, and systematically explains the impact mechanism of non-real-time frequency sampling on the dynamic frequency support response of grid-forming type renewable energy, and the impact mechanism of damping coefficient on the primary frequency regulation response of grid-forming type renewable energy. Finally, the correctness of the analysis conclusions is verified through simulation. Introduction In recent years, countries around the world have made major breakthroughs in green and low-carbon energy development. The installed capacity of wind power and photovoltaic (PV) has continuously risen. In some regions, over 50% of their power capacity comes from the renewable energy sources. The traditional power grid, which has mainly relied on synchronous generators, is gradually transitioning to a new power system dominated by renewable energy sources1,2. On the other hand, the safe and stable operation of the system is facing serious challenges. Major incidents such as the 2017 Australian blackout, the 2019 UK blackout, and the 2021 European power grid blackout are all closely related to the frequency instability, with significant economic and social impacts3. The underlying cause is the large-scale integration of renewable energy sources, which is replacing synchronous generators in equal measure. However, most renewable energy sources have zero inertia and weak frequency support capabilities, which directly leads to a sharp decline in the power grid’s ability to resist frequency disturbances. As a result, the power grid faces major risk of frequency instability. Developing the active frequency support technology of renewable energy, and increasing the types of power sources that can participate in frequency regulation, has become an inevitable choice to ensure the safe operation of the new power system. Against this backdrop, grid-forming type renewable energy have emerged4,5. These systems use Virtual Synchronous Generator (VSG) control as their core technology to simulate the characteristics of synchronous generators, thereby providing grid-support capabilities to renewable energy sources (Fig. 1). To achieve this function, a systematic design approach is typically required, focusing on both energy supply and regulation quality. Existing research has gradually explored this area, as summarized below: Firstly, in terms of energy supply for inertia output, literature6 utilizes “renewable energy + electrochemical energy storage system” combined control. This approach offers large inertia support and a long duration of frequency regulation power output, making it the mainstream VSG energy supply model, but with high investment costs. Literature7–9 proposes an active power backup style VSG control strategy, where renewable energy operates at a derated capacity, where the reserve active power is used to ensure inertia output and primary frequency regulation. But this leads to low utilization of photovoltaic/wind energy. Literatures10–12 introduce a new method by adding supercapacitors to the DC side of renewable energy power generation units. This is another way of adding storage on the renewable energy side, but it also increases the cost of supercapacitors and bidirectional DC/DC converters. In terms of regulation quality, traditional VSG control uses fixed values for virtual inertia and damping parameters, which makes it difficult to adapt to the changing grid environment, leading to issues such as overshooting in active power regulation and excessive frequency deviation13. So, many scholars improves the VSG control strategy. Literature14 divides the entire regulation process into four stages based on the system’s angular velocity and its rate of change after a disturbance, and provides tuning principles for virtual inertia and damping coefficients, effectively reducing frequency overshoot and regulation time. Literature15 proposes a combined adaptive virtual inertia and adaptive damping control of VSG in order to improve the dynamic frequency response. Literature16 uses an improved model predictive control, combining adaptive inertia damping control and adaptive weight coefficient control for joint control to enhance frequency support response capability. In literature17, an improved Reinforcement Learning (RL) based approach for adaptive VSG control is given to improve frequency transients metrics such as frequency nadir and rate of change of frequency. For reducing the transient energy loss without sacrificing grid frequency support effect, literature18 proposed an adaptive-droop-coefficient VSG control. Further to improve the frequency regulation performance considering the nonlinear dynamics, an optimal frequency control approach is proposed in19. Although great progress has been made in the construction of renewable energy and energy storage grid-connected control, there are still some phenomena that have not been effectively explained. For example, a large number of experiments have shown that the inertia response of grid-forming type renewable energy gradually increases to the maximum value after responding for a period of time. However, according to the design of VSG, the inertia response is a function of the derivative of system frequency. Theoretically, the inertia output of the grid-forming type renewable energy should increase to the maximum value as expected at the moment of disturbance. This is contrary to the original design intention of VSG. Although existing literatures have modeled and analyzed the small-signal stability and front-end/back-end coordination stability of VSGs from multiple perspectives, including single-machine and multi-machine configurations20–23, the reason why these points have not been effectively explained is that existing research has not thoroughly analyzed the interaction influence between the power grid and the grid-forming type renewable energy during the frequency regulation process. Particularly, it overlooks the fact that the grid-forming type renewable energy do not sample the grid’s voltage and frequency in real-time, but instead use the constructed equivalent frequency for control loops. This factor significantly impacts their inertia response and the primary frequency regulation response. Therefore, the conclusions drawn from existing modelling and dynamic frequency regulation behaviour analysis are not rigorous. To address this, this paper conducts the related research. The main work is as follows. Section Basic principles of grid-forming type renewable energy control and limitations of the frequency support capabilities discovered during experiments introduces the basic principles of grid-forming type renewable energy control and points out the limitations of the frequency support capabilities discovered during experiments. Section Analysis of the impact of non-real-time frequency sampling and damping coefficient on the dynamic frequency support response of grid-forming type renewable energy, analyses the impact of non-real-time frequency sampling and damping coefficient on the dynamic frequency support response of grid-forming type renewable energy through building new analytical model. Section Simulation and experimental analysis presents simulation experiments to verify the correctness of the analysis conclusions. Basic principles of grid-forming type renewable energy control and limitations of the frequency support capabilities discovered during experiments Frequency regulation principles of grid-forming type renewable energy To address the frequency support issues mentioned above, both the scientific community and industry, both domestically and internationally, have engaged in extensive discussions on grid-forming type renewable energy and have made significant deployments in various regions. The core of grid-forming type renewable energy lies in VSG control, which simulates the power output characteristics of traditional synchronous generators, thereby providing grid-support capabilities akin to those of synchronous generators. The control structure of grid-forming type renewable energy is shown in Fig.2, with the topology parameters detailed in table.1.Fig. 1Grid-connected renewable energy/storage control effect.Fig. 2Main circuit and control structure of grid-forming type renewable energy.Table 1Grid-forming inverter parameters.ParameterDescription\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V_{dc}$$\end{document}DC-Side Voltage\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V_{o\alpha }, V_{o\beta }, V_{oc}$$\end{document}Inverter Three-Phase Output Voltage\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V_{a}, V_{b}, V_{c}$$\end{document}PCC Three-Phase Voltage\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$I_{La}, I_{Lb}, I_{Lc}$$\end{document}Inverter Three-Phase Output Current\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$I_{ga}, I_{gb}, I_{gc}$$\end{document}Three-Phase Grid-Connected Current\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$C_f$$\end{document}Filter Capacitor\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$R_{eq}, L_{eq}$$\end{document}Equivalent Resistance and Inductance of the Transmission Line Grid-connected renewable energy/storage control effect. Main circuit and control structure of grid-forming type renewable energy. Table 1Grid-forming inverter parameters.ParameterDescription\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V_{dc}$$\end{document}DC-Side Voltage\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V_{o\alpha }, V_{o\beta }, V_{oc}$$\end{document}Inverter Three-Phase Output Voltage\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V_{a}, V_{b}, V_{c}$$\end{document}PCC Three-Phase Voltage\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$I_{La}, I_{Lb}, I_{Lc}$$\end{document}Inverter Three-Phase Output Current\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$I_{ga}, I_{gb}, I_{gc}$$\end{document}Three-Phase Grid-Connected Current\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$C_f$$\end{document}Filter Capacitor\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$R_{eq}, L_{eq}$$\end{document}Equivalent Resistance and Inductance of the Transmission Line Grid-forming inverter parameters. In this structure, the power outer loop is the key module for effectively simulating the power output characteristics of traditional synchronous generators. The active power control includes the VSG control and the frequency droop control. The VSG active power control rate is expressed as1\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned} \left\{ \begin{aligned} \frac{1}{\omega _0} \left( P_e^{ref} - P_e^S \right)&= J\frac{\textrm{d}\left( \omega - \omega _0 \right) }{\textrm{d}t} + D_p\left( \omega - \omega _0 \right) \\ \delta&= \int (\omega - \omega _0) \textrm{d}t \end{aligned} \right. , \end{aligned}$$\end{document}where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$D_p$$\end{document} is the damping coefficient of the grid-forming type renewable energy controller, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega$$\end{document} and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega _0$$\end{document} are the angular velocity and its rated value, respectively; \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\delta$$\end{document} is the phase angle of internal potential inside the controller; \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$P_e^{ref }$$\end{document} and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$P_e^{S }$$\end{document} are the active power reference and the sampled value, respectively. The droop control rate between the active-power and frequency is given by2\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned} \frac{1}{{{\omega _0}}}\left( {P_e^{ref} - P_e^{ref0}} \right) = {K_f}\left( {\omega - {\omega _0}} \right) , \end{aligned}$$\end{document}where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$P_e^{ref0}$$\end{document} is the active power reference corresponding to the rated angular velocity. Based on formula (2), the controller’s real-time power reference \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$P_e^{ref}$$\end{document} can adjust autonomously in response to changes in \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega$$\end{document}, increasing or decreasing the actual power output. Based on formulas (1) and (2), the active power control loop structure of the grid-forming type renewable energy controller can be derived, as shown in Fig. 3. The mathematical model of the grid-forming type renewable energy control is similar to that of traditional synchronous generator control. Grid-forming type renewable energy, therefore, possess the frequency support characteristics of synchronous generators. These systems include three functional units ➀ The \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$J\frac{\mathrm{{d}}\left( \omega - \omega _0 \right) }{\mathrm{{d}}t}$$\end{document} term in formula (1) is responsible for the inertia response, aiming to provide an immediate response to system frequency disturbances and prevent the frequency from dropping too rapidly. ➁ The \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$D_p\left( \omega - \omega _0 \right)$$\end{document} term in formula (1) is responsible for the damping response, reducing the rate of frequency change. ➂ The primary frequency regulation responsibility is handled by the frequency droop loop (2) at the front end of the VSG.Fig. 3Power control principle diagram of grid-forming type renewable energy/storage. Power control principle diagram of grid-forming type renewable energy/storage. Limitations of the frequency support capabilities of grid-forming type renewable energy control discovered during experiments Through extensive experimentation, it has been found that when the grid-forming type renewable energy participate in the system’s frequency regulation process, it exhibits the active power output, the inertia output, the damping output, and the controller angular velocity characteristics as shown in Fig. 4.Fig. 4Grid support process of grid-forming type renewable energy/storage. Grid support process of grid-forming type renewable energy/storage. However, based on formulas (1) and (2), it is difficult to explain the following three phenomena. Firstly, in the traditional design of grid-forming type renewable energy/storage VSG, to ensure the fast response, the controller does not sample the voltage angular velocity at the grid connection point in real time. Instead, the angular velocity \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega _0$$\end{document} is directly used to approximate the grid’s angular velocity. At the moment of system frequency disturbance, since the controller’s angular velocity \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega$$\end{document} does not change abruptly, and both \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega _0$$\end{document} and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$P_e^{ref}$$\end{document} are constant values, the first equation in formula (1) remains balanced. And in formula (1), \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\delta$$\end{document} does not change because at the fault moment, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega =\omega _0$$\end{document}. This raises the following question. What is driving the frequency regulation of the system? Secondly, according to the design of VSG, the inertia response is a function of the derivative of system frequency. Theoretically, the inertia output of the grid-forming type renewable energy should increase to the maximum value as expected at the moment of disturbance. Instead, it follows a trend of initially increasing and then decreasing. This is contrary to the original design intention of VSG. What is the mechanism behind this? Thirdly, the steady-state value of frequency regulation does not equal \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega _0$$\end{document}, but equal \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega _G$$\end{document}. What is the reason for this discrepancy? Analysis of the impact of non-real-time frequency sampling and damping coefficient on the dynamic frequency support response of grid-forming type renewable energy A novel analyse model for analysing frequency support characteristics of grid-forming type renewable energy control To address the aforementioned issues, this section attempts to construct a new frequency response model for the grid-forming type renewable energy, which includes the coupling relationship between the grid frequency and the constructed equivalent frequency. This would lay the foundation for analysing the system’s frequency dynamic response mechanism and dynamic behaviour in Section Analysis of the impact of non-real-time frequency sampling and damping coefficient on the dynamic frequency support response of grid-forming type renewable energy. Synchronization with power grid voltage is a critical aspect of renewable energy inverter control. Grid-forming type renewable energy employ a different synchronization method than conventional grid-following renewable energy control. The former achieves grid voltage matching through power synchronization, while the latter employs phase-locked loops (a method for capturing the phase and frequency of power grid voltage) to match grid voltage. In detail, the power synchronization of grid-forming type renewable energy is shown in Fig. 2. In principle, it samples power grid voltage and current, then calculates instantaneous power using angle information from the power loop estimation and rotary coordinate transformation. Through closed-loop control between reference power and calculated instantaneous power, it achieves synchronization with power grid voltage. Under this architecture, stable system control is only possible when the calculated instantaneous power accurately tracks the reference power. Since the calculation of instantaneous power is directly linked to the power angle (frequency information), this implies that when the system achieves stability, grid-forming renewable energy sources also achieve synchronous tracking of grid voltage. Otherwise, continuous oscillations will persist. This is a method for indirectly sensing power grid frequency information. In the process of the grid-forming type renewable energy participating in the system’s frequency regulation, the power grid’s angular velocity \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega _G$$\end{document} deviates from the rated angular velocity \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\omega _0}$$\end{document}, that is , \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\omega _G \ne \omega _0}$$\end{document}. Here, the symbols \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega ^{G}$$\end{document}, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega ^{C}$$\end{document} and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega _0$$\end{document} are used to clearly differentiate between the actual angular velocity of the power grid’s equivalent potential \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\dot{V}_g$$\end{document}, the angular velocity of the internal potential constructed by the controller, and the reference angular velocity of controller. They have different physical meanings. \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\delta ^{C}$$\end{document} represents the phase angle of the controller’s internal potential. Then, the VSG active power control rate (1) can be rewritten as:3\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned} \left\{ \begin{aligned}&\frac{1}{{\omega _0}} \left( P_e^{ref} - P_e^S \right) = J\frac{\textrm{d}\left( \omega ^C - \omega _0 \right) }{\textrm{d}t} + D_p\left( \omega ^C - \omega _0 \right) \\ \\&\delta ^C = \int \left( \omega ^C - \omega _0 \right) \textrm{d}t \end{aligned} \right. . \end{aligned}$$\end{document}The active power-frequency droop control rate (2) can be rewritten as:4\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned} \frac{1}{{{\omega _0}}}\left( {P_e^{ref} - P_e^{ref0}} \right) = {K_f}\left( {{\omega ^C} - {\omega _0}} \right) . \end{aligned}$$\end{document}When considering the line power transfer capability, the active power transferred from the grid-forming type renewable energy/storage system to the power grid is equal to:5\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned} \left\{ \begin{aligned} P_e^S&= \frac{{3{V_{pcc}}{V_g}}}{{{X_{eq}}}} \sin {\delta ^R} \\ {\delta ^R}&= \int {({\omega ^C} - {\omega ^G}) \mathrm{{d}}t} \end{aligned} \right. , \end{aligned}$$\end{document}where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V_{pcc}$$\end{document} represents the amplitude of the voltage \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\dot{V}}_{pcc}$$\end{document} at PCC of the grid-forming type renewable energy/storage system; \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V_g$$\end{document} presents the amplitude of the equivalent voltage \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\dot{V}}_{g}$$\end{document} of the power grid; \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$X_{eq}$$\end{document} is the equivalent impedance of the transmission line; \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\delta ^{R}$$\end{document} is the real power angle difference between the voltage \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\dot{V}}_{pcc}$$\end{document} at PCC and the equivalent voltage \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\dot{V}_{g}$$\end{document} of the power grid. Let \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\dot{V}_{g} = \dot{V}_{pcc} \angle 0^\circ$$\end{document}, under the steady-state condition, the following equation holds.6\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned} {\left\{ \begin{array}{ll} P_e^S = P_e^{ref} \\ \delta ^C = \delta ^R \end{array}\right. } , \end{aligned}$$\end{document}Under the condition of power grid voltage angular velocity fluctuations, since \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega _G \ne \omega _0$$\end{document}, according to formula (3) and (5),7\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned} {\delta _R} \ne {\delta _C} . \end{aligned}$$\end{document}From formula (5), the real active power \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$P_e^{S}$$\end{document} transmitted from the grid-forming type renewable energy/storage system to the power grid is a function of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\delta _R$$\end{document}. Therefore, although the 1st equation in formula (3) is balanced at the moment of frequency disturbance, and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\delta _R$$\end{document} does not change due to \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega ^{C}= \omega _0$$\end{document} during the disturbance. However, as time passes, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\delta _R$$\end{document} will change due to \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega _C \ne \omega _G$$\end{document}, causing \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$P_e^{S}$$\end{document} to change. This breaks the balance in the 1st equation of formula (3), thus triggering further frequency adjustments. Therefore, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\delta _R \ne \delta _C$$\end{document} is the fundamental cause of the frequency modulation dynamic behaviour in grid-forming type renewable energy. To more accurately analyze how \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\delta _R \ne \delta _C$$\end{document} affects the dynamic frequency regulation behavior of the grid-forming type renewable energy, further modelling and analysis are needed. By combining formula (3) and (5), the following equation can be written8\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned}&\frac{1}{{\omega _0}} \Bigg [ P_{ref} - \frac{3V_{pcc}V_g}{X_{eq}} \sin \left( \int \left( \omega _C - \omega _G \right) \textrm{d}t \right) \Bigg ] \nonumber \\&\quad = J\frac{\textrm{d}\left( \omega _C - \omega _0 \right) }{\textrm{d}t} + D_p\left( \omega _C - \omega _0 \right) . \end{aligned}$$\end{document}Considering that the rate of change of the grid voltage angular velocity \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega _G$$\end{document} is slow, its impact within short times is ignored here, i.e.,9\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned} J\frac{{\mathrm{{d}}\left( {{\omega _C} - {\omega _0}} \right) }}{{\mathrm{{d}}t}} \approx J\frac{{\mathrm{{d}}\left( {{\omega _C} - {\omega _G}} \right) }}{{\mathrm{{d}}t}} . \end{aligned}$$\end{document}And10\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned} {D_p}\left( {{\omega _C} - {\omega _0}} \right) = {D_p}\left( {{\omega _C} - {\omega _G}} \right) + {D_p}\left( {{\omega _G} - {\omega _0}} \right) . \end{aligned}$$\end{document}Combining formula (8), (9), and (10), the following equation can be written11\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned}&\frac{{P_{ref}}}{{\omega _0}} - D_p\left( \omega _G - \omega _0 \right) - \frac{{3V_{pcc}V_g}}{{X_{eq}\omega _0}} \sin \left( \int \left( \omega _C - \omega _G \right) \textrm{d}t \right) \nonumber \\&\quad = J\frac{\textrm{d}\left( \omega _C - \omega _G \right) }{\textrm{d}t} + D_p\left( \omega _C - \omega _G \right) . \end{aligned}$$\end{document}In the normal power grid operation scene or under the condition where the grid-forming type renewable energy/storage system actively changes the power reference \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$P^{ref}$$\end{document}, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega _G = \omega _0$$\end{document}. According to formula (11), the VSG active power control loop model for the grid-forming type renewable energy can be drawn as Fig. 5 shows. Clearly, when \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$P^{ref}$$\end{document} changes, the power control closed-loop breaks the balance instantaneously, and the system’s VSG control is activated. At the moment of activation, the inertia response reaches its maximum value. After reaching the new steady state, the controller constructs the equivalent angular velocity \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega _C =\omega _G = \omega _0$$\end{document}. Under these conditions, the system’s response characteristics are consistent with previous analyses.Fig. 5Steady-state active power-frequency control model of grid-forming type renewable energy/storage. Steady-state active power-frequency control model of grid-forming type renewable energy/storage. However, when the power grid frequency \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega _G$$\end{document} fluctuates, the disturbed power grid angular frequency \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\tilde{\omega }$$\end{document} is denoted as12\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned} {\tilde{\omega }_G} \buildrel \Delta \over = {\omega _G} + \Delta {\omega _G} , \end{aligned}$$\end{document}where \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta \omega _G$$\end{document} is the angular frequency disturbance value of the power grid. Substituting formula (12) into formula (11) gives:13\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned}&\frac{{P_{ref}}}{{\omega _0}} - D_p \Delta \omega _G - \frac{{3 V_{pcc} V_g}}{{X_g \omega _0}} \sin \left( \int \left( \omega _C - \left( \omega _G + \Delta \omega _G \right) \right) \textrm{d}t \right) \nonumber \\&\quad = J \frac{\textrm{d} \left( \omega _C - \left( \omega _G + \Delta \omega _G \right) \right) }{\textrm{d}t} + D_p \left( \omega _C - \left( \omega _G + \Delta \omega _G \right) \right) . \end{aligned}$$\end{document}Based on formula (13), the VSG active power control loop model for the grid-forming type renewable energy/storage system can be drawn as Fig. 6 shows.Fig. 6Active power-frequency control model of grid-forming type renewable energy/storage under frequency disturbance conditions. Active power-frequency control model of grid-forming type renewable energy/storage under frequency disturbance conditions. Analysis of the impact of non-real-time frequency sampling and damping coefficient on the dynamic frequency support response of grid-forming type renewable energy From Fig. 4, it is evident that the power grid angular frequency disturbance value \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta {\omega _G}$$\end{document} would have an important impact on the system’s frequency dynamic process in two aspects during the participation of grid-forming type renewable energy/storage in system frequency regulation. The specific impact mechanism and frequency regulation dynamic behaviour analysis are as follows. Impact Mechanism ➀. The power grid angular frequency disturbance value \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta {\omega _G}$$\end{document} will automatically generate a power feedforward branch (defined as influence loop ➀ in this paper, as marked in Fig. 6), with a gain coefficient of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$D_p$$\end{document}. In other words, the power reference of grid-forming type renewable energy can be equivalently expressed as \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$P'_{ref}$$\end{document}, i.e.,14\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned} \frac{{{{P'}_{ref}}}}{{{\omega _0}}} = \frac{{{P_{ref}}}}{{{\omega _0}}} - {D_p}\Delta {\omega _G} . \end{aligned}$$\end{document}When the grid-forming type renewable energy system reaches steady state, the power control closed loop on the far left of Fig. 6 would reach equilibrium, satisfying15\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned} \frac{{{P_{ref}}}}{{{\omega _0}}} - {D_p}\Delta {\omega _G} - \frac{{{P_e}}}{{{\omega _0}}} = 0 . \end{aligned}$$\end{document}Thus, after the grid-forming type renewable energy participates in system frequency regulation and reaches a new steady state, the actual active power output \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$P_e$$\end{document} would be equal to16\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned} \frac{{{P_e}}}{{{\omega _0}}} = \frac{{{P_{ref}}}}{{{\omega _0}}} - {D_p}\Delta {\omega _G} . \end{aligned}$$\end{document}Clearly, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$P_e$$\end{document} does not equal the active power reference value \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${P_{ref}}$$\end{document}. Comparing formula (16) with formula (2), it is easy to see that they have the same form. Therefore, the power feedforward branch automatically generated by the power grid angular frequency disturbance value \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta {\omega _G}$$\end{document} can be seen as a droop control on the frequency of the grid-forming type renewable energy/storage voltage at PCC, with a droop coefficient of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${D_p}$$\end{document}. Therefore, when designing the active power-frequency droop control according to formula (4), the impact of the power grid angular frequency disturbance value \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta {\omega _G}$$\end{document} on the droop control should be taken into account. Impact Mechanism ➁. The system frequency disturbance \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta {\omega _G}$$\end{document} itself forms a frequency disturbance branch (defined as influence loop ➁ in this paper, as marked in Fig. 6), which affects the angular velocity closed loop control. That is, through influence loop ➁, it first affects the system’s power angle \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\delta _R}$$\end{document}, and \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$P_e$$\end{document} then changes. \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$P_e$$\end{document} is no longer equal to \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$P_{ref}$$\end{document}, thus initiating the inertia and damping regulation process of VSG control of the grid-forming type renewable energy. It is worth noting that at the moment the power grid angular frequency suffers a disturbance, since17\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned} \left\{ \begin{aligned}&D_p \Delta \omega _G = D_p \left( \omega _C - \left( \omega _G + \Delta \omega _G \right) \right) , \\&P_{ref} = \frac{3 V_{pcc} V_g}{X} \sin \left( \int \left( \omega _C - \left( \omega _G + \Delta \omega _G \right) \right) \textrm{d}t \right) \end{aligned} \right. , \end{aligned}$$\end{document}the inertia section will not immediately take effect. In other words, during the system frequency dynamic process, the disturbance is initiated by influence loop ➀ and is independent of influence loop ➁. This explains the first phenomenon listed in Section Limitations of the frequency support capabilities of grid-forming type renewable energy control discovered during experiments. As the system’s power angle \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\delta _R$$\end{document} continues to increase, the inertia part would gradually increase from 0. When the offset of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\delta _R$$\end{document} reaches its maximum value, the inertia output would also reach its maximum value. Afterward, as the offset of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\delta _R$$\end{document} decreases, the inertia output decreases. This explains the second phenomenon listed in Section Limitations of the frequency support capabilities of grid-forming type renewable energy control discovered during experiments. Of course, this contradicts the design expectation of grid-forming type renewable energy, which aims to generate a large inertia output immediately after the disturbance (as shown in the third subplot of Fig. 4). When the system reaches the steady state, the angular velocity closed loop in Fig. 6 will reach equilibrium, i.e.,18\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\begin{aligned} {\omega _C} = {\omega _G} + \mathrm{{d}}{\omega _G} = {\tilde{\omega }_G} . \end{aligned}$$\end{document}According to formula (4), the grid-forming type renewable energy , through VSG control, would ultimately make the internal potential output angular frequency \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\omega _C}$$\end{document} automatically follow the actual power grid frequency \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\tilde{\omega }_G}$$\end{document}, rather than always maintaining \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega _0$$\end{document}. This explains the third phenomenon listed in Section Limitations of the frequency support capabilities of grid-forming type renewable energy control discovered during experiments. In summary, this section systematically answers the dynamic response mechanisms of grid-forming type renewable energy under system frequency disturbance conditions, explaining the three questions listed in Section Limitations of the frequency support capabilities of grid-forming type renewable energy control discovered during experiments, and compensating for the limitations in traditional grid-forming type renewable energy/storage active power regulation modelling that could not explain frequency regulation dynamics. Additionally, it should be noted that although the power grid angular frequency disturbance value \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta {\omega _G}$$\end{document} generates two control branches, influencing the dynamic behaviour of grid-forming type renewable energy, according to Fig. 6, the forward channel function of the system controller remains unchanged. This means that the rise time, overshoot, and other dynamic response characteristics of grid-forming type renewable energy/storage are still determined by the inertia and damping parameters, and have not changed. Simulation and experimental analysis i) Basic group experiment This section would validate the accuracy of the conclusions regarding the new frequency regulation modelling and dynamic behavior analysis of grid-forming type renewable energy system from section Basic principles of grid-forming type renewable energy control and limitations of the frequency support capabilities discovered during experiments. To achieve this, a simulation system as shown in Fig. 2 has been constructed using MATLAB/Simulink. The specific parameters are listed in table 2. The initial active power reference for the grid-forming type renewable energy controller is set to \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$10\text {kW}$$\end{document}, and the initial value of the power grid equivalent potential frequency is set to 50Hz. At \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$t = 5\mathrm{{s}}$$\end{document}, the power grid equivalent potential frequency is set to 49.9Hz, and the system’s active power output, the inertia output, the damping output, the angular velocity, the power angle, and other parameters are analyzed (shown in Fig. 7, 8, 9, 10, and 11) to validate the conclusions from section Basic principles of grid-forming type renewable energy control and limitations of the frequency support capabilities discovered during experiments.Table 2Grid-forming inverter parameters.ParametersValueParametersValue\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V_{dc}$$\end{document}700 V\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$L_c$$\end{document}3 mH\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V_{0}$$\end{document}313V\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$C_f$$\end{document}10 \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\mu$$\end{document}F\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V_{g}$$\end{document}313VJ2\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$Q_{ref}$$\end{document}0var\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$D_p$$\end{document}\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$10^4$$\end{document} Table 2Grid-forming inverter parameters.ParametersValueParametersValue\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V_{dc}$$\end{document}700 V\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$L_c$$\end{document}3 mH\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V_{0}$$\end{document}313V\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$C_f$$\end{document}10 \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\mu$$\end{document}F\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$V_{g}$$\end{document}313VJ2\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$Q_{ref}$$\end{document}0var\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$D_p$$\end{document}\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$10^4$$\end{document} Grid-forming inverter parameters. From Fig. 7, it is clear that the active power output of the grid-forming type renewable energy/storage system does not experience an instantaneous change at the moment of frequency disturbance (\documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$t = 5\mathrm{{s}}$$\end{document}), and remains equal to the initial active power reference of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$10\text {kW}$$\end{document}. In other words, at this moment, the system’s power balance is maintained, implying that the driving force for frequency regulation is not unbalanced power. This is consistent with the conclusion from Section Analysis of the impact of non-real-time frequency sampling and damping coefficient on the dynamic frequency support response of grid-forming type renewable energy. Furthermore, the final value of the active power output is approximately \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$12\text {kW}$$\end{document}, which is not equal to the system’s active power reference of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$10\text {kW}$$\end{document}. The active power deviation of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$0.2 \times 10\text {kW}$$\end{document} is exactly equal to \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${D_p}\Delta {\omega _G}{\omega _0}$$\end{document}. This confirms the conclusion from Section Analysis of the impact of non-real-time frequency sampling and damping coefficient on the dynamic frequency support response of grid-forming type renewable energy, which is the system frequency deviation introduces a power feedforward branch, causing the system’s active power output to exhibit a power-frequency droop characteristic. Figure 8 shows that the inertia output of the grid-forming type renewable energy system follows a trend of first increasing and then decreasing (the opposite occurs in a frequency rise scenario), and does not reach its maximum value at the moment of frequency disturbance. Additionally, the changes of the actual angular velocity \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\omega ^G}$$\end{document} of the power grid equivalent potential \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\dot{V}_g}$$\end{document}, the constructed angular velocity \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\omega ^C}$$\end{document}, and the controller’s angular velocity reference value \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega _0$$\end{document} in Fig. 10 show that, as the actual angular velocity \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\omega ^G}$$\end{document} of the power grid equivalent potential \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\dot{V}_g}$$\end{document} changes, the controller’s constructed angular velocity \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\omega ^C}$$\end{document} will adaptively follow \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\omega ^G}$$\end{document}. The final value is not equal to \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\omega _0$$\end{document}. These two points are consistent with the conclusions in Section Limitations of the frequency support capabilities of grid-forming type renewable energy control discovered during experiments. The reason for this is that at the moment of frequency disturbance, \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\omega ^C} \ne {\omega ^G}$$\end{document} (Fig. 11), and the system power angle \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\delta _R}$$\end{document} (shown in Fig. 11) changes. This breaks the balance between the grid-forming type renewable energy/storage system’s power output and the reference value, further triggering the system’s dynamics. This means that the factor triggering the system’s frequency regulation dynamic process is the frequency disturbance \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta {\omega _G}$$\end{document}, which generates and acts on the frequency disturbance branch of the angular velocity control loop (influence loop ➁). This confirms the conclusion from Section Analysis of the impact of non-real-time frequency sampling and damping coefficient on the dynamic frequency support response of grid-forming type renewable energy. In fact, during the change in the system’s power angle \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\delta _R}$$\end{document}, the imbalance between the grid-forming type renewable energy system’s power output and the reference value also triggers the inertia response, causing it to gradually increase from zero as \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\delta _R}$$\end{document} increases. When \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${\delta _R}$$\end{document} reaches its maximum, the inertia output will also reach its maximum value. This is consistent with the analysis conclusion from Section Analysis of the impact of non-real-time frequency sampling and damping coefficient on the dynamic frequency support response of grid-forming type renewable energy.Fig. 7Active power variation of basic group experiment.Fig. 8Inertia output variation of basic group experiment.Fig. 9Damping output variation of basic group experiment.Fig. 10Angular velocity variation of basic group experiment.Fig. 11Power angle variation of basic group experiment. Active power variation of basic group experiment. Inertia output variation of basic group experiment. Damping output variation of basic group experiment. Angular velocity variation of basic group experiment. Power angle variation of basic group experiment. ii) Control group experiment 1: different magnitudes of frequency disturbance In this part, the frequency offset becomes -0.2Hz. The simulation results are shown in Fig. 12, Fig. 13, Fig. 14, Fig. 15, Fig. 16 . It could be easily found that the changing trends of the variables under examination are exactly the same as in the first section, further proving the correctness of the analytical conclusions in this paper. The difference is the final value of the active power output is approximately \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$14\text {kW}$$\end{document}, which is not equal to the system’s active power reference of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$10\text {kW}$$\end{document}. The active power deviation of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$0.4\times 10\text {kW}$$\end{document} is exactly equal to \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{D}_{p}}\Delta {{\omega }_{G}}{{\omega }_{0}}$$\end{document}.Fig. 12Active power variation of control group experiment 1.Fig. 13Inertia output variation of control group experiment 1.Fig. 14Damping output variation of control group experiment 1.Fig. 15Angular velocity variation of control group experiment 1.Fig. 16Power angle variation of control group experiment 1. Active power variation of control group experiment 1. Inertia output variation of control group experiment 1. Damping output variation of control group experiment 1. Angular velocity variation of control group experiment 1. Power angle variation of control group experiment 1. iii) Control group experiment 2: frequency increases vs. decreases In this part, the frequency offset becomes 0.1Hz. The simulation results are shown in Fig. 17, Fig. 18, Fig. 19, Fig. 20, Fig. 21 . It could be easily found that the changing trends of the variables under examination are exactly the opposite as in the first section, further proving the correctness of the analytical conclusions in this paper. The difference is the final value of the active power output is approximately \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$0.8\text {kW}$$\end{document}, which is not equal to the system’s active power reference of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$10\text {kW}$$\end{document}. The active power deviation of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$-0.2\times 10\text {kW}$$\end{document} is exactly equal to \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{D}_{p}}\Delta {{\omega }_{G}}{{\omega }_{0}}$$\end{document}.Fig. 17Active power variation of control group experiment 2.Fig. 18Inertia output variation of control group experiment 2.Fig. 19Damping output variation of control group experiment 2.Fig. 20Angular velocity variation of control group experiment 2.Fig. 21Power angle variation of control group experiment 2. Active power variation of control group experiment 2. Inertia output variation of control group experiment 2. Damping output variation of control group experiment 2. Angular velocity variation of control group experiment 2. Power angle variation of control group experiment 2. iv) Control group experiment 3: varying damping coefficients \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$D_p$$\end{document} In this part, the \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$D_p$$\end{document} becomes 20. The simulation results are shown in Fig. 22, Fig. 23, Fig. 24, Fig. 25, Fig. 26 . It could be easily found that the changing trends of the variables under examination are exactly the same as in the first section, further proving the correctness of the analytical conclusions in this paper. The difference is the final value of the active power output is approximately \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$14\text {kW}$$\end{document}, which is not equal to the system’s active power reference of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$10\text {kW}$$\end{document}. The active power deviation of \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$0.4\times 10\text {kW}$$\end{document} is exactly equal to \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${{D}_{p}}\Delta {{\omega }_{G}}{{\omega }_{0}}$$\end{document}.Fig. 22Active power variation of control group experiment 3.Fig. 23Inertia output variation of control group experiment 3.Fig. 24Damping output variation of control group experiment 3.Fig. 25Angular velocity variation of control group experiment 3.Fig. 26Power angle variation of control group experiment 3. Active power variation of control group experiment 3. Inertia output variation of control group experiment 3. Damping output variation of control group experiment 3. Angular velocity variation of control group experiment 3. Power angle variation of control group experiment 3. Conclusion Grid-forming type control has become an important control mode of the inverters that interface renewable energy systems with the power grid. However, the significant impact of non-real-time frequency sampling and damping coefficient on their inertia response and primary frequency response has been overlooked. This has resulted in existing modelling and dynamic behaviour analysis conclusions being imprecise, leaving three major issues listed in Section Limitations of the frequency support capabilities of grid-forming type renewable energy control discovered during experiments: What drives the frequency regulation dynamics? Why does the inertia response first increase and then decrease? Why is the steady-state frequency not equal to the reference value? This paper conducts related analyse research work. It firstly considers the influence of non-real-time frequency sampling and constructs a new frequency response model. Based on this, it systematically explains the impact mechanism of non-real-time frequency sampling on the dynamic frequency support response of grid-forming type renewable energy, and the impact mechanism of damping coefficient on the primary frequency regulation response of grid-forming type renewable energy. It is found that during the frequency regulation process, the power grid’s angular frequency disturbance \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$$\Delta {\omega _G}$$\end{document} would automatically generate a power feedforward branch and a frequency disturbance branch within the controller, which affect the frequency dynamic process from two aspects. The power feedforward branch would produce a droop control characteristic with a coefficient \documentclass[12pt]{minimal} \usepackage{amsmath} \usepackage{wasysym} \usepackage{amsfonts} \usepackage{amssymb} \usepackage{amsbsy} \usepackage{mathrsfs} \usepackage{upgreek} \setlength{\oddsidemargin}{-69pt} \begin{document}$${D_p}$$\end{document}, which changes the active power output of the grid-forming type renewable energy system. The frequency disturbance branch, on the other hand, is the driving force behind the frequency response. It changes the system’s power angle, forcing the system to regulate the active power output. This causes the inertia response to first increase and then decrease, and the steady-state frequency to deviate from the reference value. Additionally, because the forward channel of the controller remains unchanged, the response speed and the overshoot during the frequency regulation process do not change. This paper systematically answers the three questions listed in Section Limitations of the frequency support capabilities of grid-forming type renewable energy control discovered during experiments and provides theoretical support for the development of future frequency regulation control strategies for the grid-forming type renewable energy system.