Investigation of fiber Bragg grating sensor measurability in concrete beams under static load conditions Authors: Mohammad Hany Yassin, Mohamad Hussein Farhat, Michel Nahas, Ahmad Said Saad Published: 2024 ABSTRACT Recent advances in construction materials and architecture have enhanced the safety of modern structures, which now feature higher, lighter, and more unique designs. Bridges, as critical infrastructure, face increasing load demands due to rising traffic volumes, leading to accelerated structural deterioration. This necessitates more frequent inspections and maintenance, resulting in increased costs and potential operational disruptions. Real-time built-in monitoring systems are thus essential for both new and aging structures. Fiber Optic Sensor (FOS) technology, particularly Fiber Bragg Grating (FBG) sensors, offers a reliable and stable solution for long-term Structural Health Monitoring (SHM). This study evaluates the performance and applicability of FBG sensors (FBGs) in comparison to traditional strain gauges (SGs) for capturing strains, loads, deflections, and temperature in full-scale beams under static loads. Four large-scale reinforced concrete (RC) and CFRP-strengthened beams were tested. Nonlinear finite element analysis (NLFEA) using VecTor2 was employed to simulate the behavior of these beams under static loading. Data from FBGs were compared to those from collocated electrical SGs. The results demonstrated the reliability and flexibility of FBGs in monitoring structural performance. Notably, FBGs continued to provide accurate readings even after the specimens reached their maximum load, showcasing their endurance and resilience compared to conventional SGs. Introduction and background Over the past 20 years, significant advancements in SHM have emerged, driven by new sensor technologies, monitoring systems, and non-destructive tests (NDT) methods capable of assessing structural performance [[1], [2], [3], [4], [5]]. Preserving the integrity of critical infrastructure, particularly bridges, is essential for economic stability, as neglecting inspection and maintenance can lead to severe financial repercussions. FBGs have gained increasing attention in SHM for their lightweight design, high sensitivity, and immunity to electromagnetic interference, making them ideal for monitoring structural performance in challenging environments such as aerospace, civil engineering, and underground structures [[6], [7], [8]]. FBGs provide real-time data on strain, temperature, and other parameters, facilitating proactive maintenance and safety assessments that extend the service life of infrastructure [6,9,10]. In civil engineering, FBGs have been effectively used for monitoring bridges and other structures. For example, Shen and Jiang [11] demonstrated the use of FBGs for deformation monitoring in bridge components, while Liu et al. [7] highlighted their effectiveness in underground structures. Their integration into structural components enables continuous assessment of stresses and strains, allowing timely interventions to prevent failures [8,12]. FBGs are also widely used in the aerospace sector to monitor composite materials and structures due to their high strength-to-weight ratios [13,14]. These sensors provide critical real-time data to inform maintenance decisions, enhancing the safety and reliability of aircraft [15,16]. Additionally, integrating FBGs into the manufacturing processes of composite materials improves monitoring capabilities [17]. FBGs also offer valuable applications in monitoring geological stability and landslides, providing high-precision measurements over long distances [10,18]. This capability is particularly beneficial for civil engineering projects where ground stability is critical, as presented in Ref. [18], which demonstrated their use in monitoring deformations during landslide events. Recent developments in hybrid monitoring systems combine FBGs with other technologies to enhance damage detection. For example, Jinachandran and Rajan [15] explored integrating FBGs with acoustic emission techniques, providing a more comprehensive understanding of structural behavior under various conditions. In RC bridges, asphalt concrete is used for its waterproofing properties, protecting structures from water-induced corrosion and extending service life [19]. Integrating FBGs into such infrastructure, especially asphalt concrete, offers significant potential for real-time monitoring [20,21]. These sensors help in proactive maintenance strategies, enhancing the longevity of pavement structures [21]. Furthermore, advancements in materials like polymer-modified asphalt, which improve durability, highlight the relevance of FBGs in monitoring enhanced materials [22]. Significance of structural integrity, economic impact, and advanced monitoring for bridges Maintaining the structural integrity of bridges is crucial for ensuring public safety and economic stability. Neglecting routine inspections and preventive maintenance can lead to deterioration, increased risk of failures, and severe social and economic consequences [[23], [24], [25], [26], [27], [28], [29]]. Advanced SHM systems, such as those utilizing FBGs, are essential for continuous monitoring, early defect detection, and extending the lifespan of critical infrastructure. Bridges are key components of national infrastructure, playing a vital role in the economy by facilitating the movement of goods and people. Poor maintenance can result in costly repairs, service disruptions, and reduced economic productivity [[30], [31], [32], [33], [34]]. Implementing SHM systems with FBGs helps optimize maintenance strategies, reduce costs, and ensure the long-term preservation of structural integrity. Bridge failures can occur due to various factors, including design errors, aging, environmental impacts, and inadequate maintenance [[35], [36], [37], [38], [39]]. Recent incidents have underscored the need for reliable monitoring technologies, such as FBGs, to detect early signs of structural distress and enhance the resilience of bridges against unforeseen failures. To address these challenges, the use of FRP materials, particularly Carbon Fiber Reinforced Polymers (CFRPs), has gained prominence in retrofitting and strengthening concrete structures. FRPs offer high strength-to-weight ratios, durability, and resistance to corrosion, making them ideal for reinforcing existing bridge components [[40], [41], [42], [43]] as well as other structural and nonstructural components [44,45]. When used in newly constructed structures, FBGs enhance monitoring and maintenance capabilities by providing clearer evaluations of the condition of the structure and its loading history. This approach helps optimize rehabilitation scenarios and assists with the selection and design of FRP strengthening techniques. Additionally, FBGs can detect interfacial strains between FRP laminates and concrete, providing an early warning for potential debonding or other defects in FRP-strengthened structures [46,47]. Modern SHM systems, incorporating FBGs, provide real-time monitoring and early warnings of structural issues [3]. These sensors are particularly effective in environments with temperature fluctuations, offering accurate and reliable data for better management of infrastructure health [9,[48], [49], [50], [51], [52], [53], [54]]. The integration of FBGs with advanced materials like FRPs represents a forward-looking approach to enhancing bridge performance and longevity. Advantages and application of FBGs in SHM FBGs based FOS operate differently from traditional electrical SGs. FBG is a microstructure that is a few millimeters in length, created by modifying a standard single-mode telecom fiber which is doped with germanium using a UV laser. The microstructure present in the optical fiber causes a repetitive change in the refractive index [54,55]. As light travels through the fiber, the Bragg grating reflects only a specific range of wavelengths, while allowing all other wavelengths to pass through. The center of this narrow band of reflected wavelengths is known as the Bragg wavelength [56]. When an optical fiber is stretched or compressed under stress, the period of an FBG increases, leading to a shift in the Bragg wavelength, which is detected and recorded by the interrogator (i.e., data acquisition system) [56,57]. FBGs have several advantages over electrical SGs. These devices ensure long-term signal stability and system durability, even when exposed to high levels of vibratory loads, such as those encountered on heavily used highways and bridges [56,57]. Prior research has demonstrated the excellent ability of FBGs to measure strain and temperature concurrently [[58], [59], [60], [61], [62]] or to thermally compensate strain measurements [63,64]. Parameters such as tilt, acceleration, pressure, etc., can also be measured and monitored using FBG-based sensors applied to transducers. The FOS, particularly those based on Bragg grating, to electromagnetic and radio frequency interference (EMI/RFI) is highly advantageous in railway structures, such as bridges and tunnels designed for electrically powered trains. These trains generate intense electromagnetic fields, and the immunity of embedded FOS to EMI/RFI makes them an ideal choice for addressing stress redistribution issues in such environments. Notable study by Bock [65] consistently highlight the benefits of FOS in civil engineering structures, emphasizing their EMI resistance and compatibility with fiber-optic data transmission networks. However, embedding FBG-based FOS in layered composite materials may lead to stress concentrations around the sensor due to material property discontinuities [[66], [67], [68]]. Encapsulating the FBG within a capillary tube can mitigate the effects of transverse strains on FOS measurements. Research has shown that encapsulating the FBG in this manner preserves a single peak in the reflected optical spectrum after the composite material fabrication process [69]. Other studies utilized capillary encapsulation to increase FBG temperature sensitivity for sensing applications [68]. Additional studies have explored numerous other applications of FBGs in SHM. For example, Braunfelds et al. [52] developed a strain measurement calibration technique for monitoring road pavement, while Qin et al. [70] designed a new variable sensitivity FBG strain sensor for SHM with an accuracy of ±5 %. The fabrication and validation of FBGs using Internet of Things (IoT) and big data, attached to a bridge base plate, were discussed by Mohapatra et al. [71]. Furthermore, Velázquez-Carreón et al. [72] proposed a method to increase the sensitivity of FBG-embedded devices by enhancing the reinforcement in the area where the FBG is embedded. In another study, Luís Pereira et al. [73] reported on the development, characterization, and installation of a simple and low visual impact FBG-based sensing system for long-term crack monitoring in the historical Monastery of Batalha. Given these applications, the use of FBGs in SHM is both timely and critical for advancing sustainable transport infrastructure. This research presents a novel approach to evaluating the performance of FBGs in real-world conditions by integrating them into full-scale RC and CFRP strengthened beams. Unlike previous studies that have predominantly focused on laboratory-controlled environments, this study uniquely situates the full-scale frame outside the Civil Engineering Laboratory, exposing it to actual weather conditions in Kuwait during the summer months (May to August). This outdoor testing environment introduces variables such as high temperatures and fluctuating humidity, which are often excluded in controlled laboratory tests. The study further distinguishes itself by comparing FBGs with traditional SGs, providing a comprehensive evaluation of FBG sensor performance in terms of their accuracy, reliability, and practical applicability under extreme environmental conditions. Additionally, the use of both destructive and non-destructive testing methods on small cylindrical samples to verify the quality of the concrete material adds another layer of rigor and authenticity to the findings. This research bridges the gap between theoretical knowledge and practical application, offering insights into the real-world effectiveness of FBGs in SHM systems for critical infrastructure. The main objectives of this study are outlined as follows.1Evaluate FBG sensor performance in harsh conditions: assess the performance of FBGs in monitoring strains, loads, deflections, and temperatures in full-scale RC and CFRP-strengthened beams under static loads, specifically in the extreme summer weather conditions of Kuwait.2Compare FBGs with traditional SGs: compare the performance of FBGs against traditional foil SGs to identify their strengths, limitations, and potential advantages in SHM applications.3Investigate temperature sensitivity and compensation capabilities: examine the temperature sensitivity of FBGs and their ability to compensate for temperature variations to ensure accurate strain measurements under fluctuating environmental conditions.4Analyze structural behavior under load: study the behavior of simply supported concrete beams, focusing on the transition from linear to nonlinear behavior under load and the implications for CFRP debonding, crack formation and propagation.5Demonstrate multi-point monitoring capabilities: showcase the ability of FBGs to simultaneously monitor multiple points within a structure, highlighting their potential for comprehensive monitoring of large-scale infrastructure.6Early detection of structural failures: highlight the potential of FBGs for early failure detection, such as identifying debonding in CFRP-reinforced structures, which is critical for proactive maintenance and safety assurance.7Integrate FBGs with CFRP: explore the integration of FBGs with CFRP materials to enhance SHM, including assessing the impact of CFRP reinforcement on the transition from linear to nonlinear behavior in concrete beams and on crack initiation and propagation.8Assess Concrete Material Quality: Use both destructive (compressive strength tests) and non-destructive (ultrasonic pulse velocity tests) testing on small cylindrical samples to evaluate the quality and consistency of the concrete material used in the full-scale testing. 1Evaluate FBG sensor performance in harsh conditions: assess the performance of FBGs in monitoring strains, loads, deflections, and temperatures in full-scale RC and CFRP-strengthened beams under static loads, specifically in the extreme summer weather conditions of Kuwait. Evaluate FBG sensor performance in harsh conditions: assess the performance of FBGs in monitoring strains, loads, deflections, and temperatures in full-scale RC and CFRP-strengthened beams under static loads, specifically in the extreme summer weather conditions of Kuwait. 2Compare FBGs with traditional SGs: compare the performance of FBGs against traditional foil SGs to identify their strengths, limitations, and potential advantages in SHM applications. Compare FBGs with traditional SGs: compare the performance of FBGs against traditional foil SGs to identify their strengths, limitations, and potential advantages in SHM applications. 3Investigate temperature sensitivity and compensation capabilities: examine the temperature sensitivity of FBGs and their ability to compensate for temperature variations to ensure accurate strain measurements under fluctuating environmental conditions. Investigate temperature sensitivity and compensation capabilities: examine the temperature sensitivity of FBGs and their ability to compensate for temperature variations to ensure accurate strain measurements under fluctuating environmental conditions. 4Analyze structural behavior under load: study the behavior of simply supported concrete beams, focusing on the transition from linear to nonlinear behavior under load and the implications for CFRP debonding, crack formation and propagation. Analyze structural behavior under load: study the behavior of simply supported concrete beams, focusing on the transition from linear to nonlinear behavior under load and the implications for CFRP debonding, crack formation and propagation. 5Demonstrate multi-point monitoring capabilities: showcase the ability of FBGs to simultaneously monitor multiple points within a structure, highlighting their potential for comprehensive monitoring of large-scale infrastructure. Demonstrate multi-point monitoring capabilities: showcase the ability of FBGs to simultaneously monitor multiple points within a structure, highlighting their potential for comprehensive monitoring of large-scale infrastructure. 6Early detection of structural failures: highlight the potential of FBGs for early failure detection, such as identifying debonding in CFRP-reinforced structures, which is critical for proactive maintenance and safety assurance. Early detection of structural failures: highlight the potential of FBGs for early failure detection, such as identifying debonding in CFRP-reinforced structures, which is critical for proactive maintenance and safety assurance. 7Integrate FBGs with CFRP: explore the integration of FBGs with CFRP materials to enhance SHM, including assessing the impact of CFRP reinforcement on the transition from linear to nonlinear behavior in concrete beams and on crack initiation and propagation. Integrate FBGs with CFRP: explore the integration of FBGs with CFRP materials to enhance SHM, including assessing the impact of CFRP reinforcement on the transition from linear to nonlinear behavior in concrete beams and on crack initiation and propagation. 8Assess Concrete Material Quality: Use both destructive (compressive strength tests) and non-destructive (ultrasonic pulse velocity tests) testing on small cylindrical samples to evaluate the quality and consistency of the concrete material used in the full-scale testing. Assess Concrete Material Quality: Use both destructive (compressive strength tests) and non-destructive (ultrasonic pulse velocity tests) testing on small cylindrical samples to evaluate the quality and consistency of the concrete material used in the full-scale testing. Methodology The research evaluated the performance of FBGs in monitoring full-scale RC and CFRP strengthened beams (RC-CFRP) under static loading conditions. The full-scale frame was placed outside the Civil Engineering Laboratory at the Australian University in Kuwait, and the testing was conducted between May and August, reflecting the real weather conditions in Kuwait during the summer, characterized by high temperatures and challenging environmental factors. The concrete beams were prepared using a mix designed according to ASTM standards, with materials locally sourced. Beams were cast in custom-made wooden molds and cured under conditions replicating the actual environment. A three-point bending test was performed on the beams using a full-scale loading frame to assess their behavior under static loads. Both destructive and non-destructive tests were conducted on small cylindrical samples to check the quality of the concrete material. Ultrasonic pulse velocity tests and compressive strength tests were performed to evaluate the material properties and ensure consistency. The data obtained from the FBGs were compared to that from traditional SGs to determine the accuracy of the sensors and reliability under harsh environmental conditions. Material preparation Grade 40 MPa concrete mix was prepared and cast according to the ASTM C31/C31M standard [74]. Mix design is shown in Table 1 for 1 m3 of concrete. Mixing and casting were conducted at the Civil Lab of the Australian University in Kuwait.Table 1Ingredients proportions for 1 m3 of concrete.Table 1Cement (kg)w/caSand (kg)Aggregates ¾″ (kg)Aggregates ½″ (kg)Aggregates ⅜″ (kg)Admixture (ℓ)3200.56695.006102303254.5aw/c: water to cement ratio. Table 1Ingredients proportions for 1 m3 of concrete.Table 1Cement (kg)w/caSand (kg)Aggregates ¾″ (kg)Aggregates ½″ (kg)Aggregates ⅜″ (kg)Admixture (ℓ)3200.56695.006102303254.5aw/c: water to cement ratio. Ingredients proportions for 1 m3 of concrete. w/c: water to cement ratio. Fresh concrete testing and curing procedure The fresh concrete was tested for workability using a slump test in accordance with C143/C143M − 20 standard [75] to ensure it met the necessary requirements for construction applications as shown in Fig. 1(a) and (b). Following the slump test, the concrete was poured into oiled cylindrical molds, prepared as per ASTM C0470/C0470M standard [76]. The samples were kept under consistent curing conditions for 24 h before being unmolded and submerged in water –see Fig. 1 (c), where they continued to cure until testing at 7 and 28 days.Fig. 1from left to right (a) concrete slump test (b) measuring the slump (c) samples curing.Fig. 1 from left to right (a) concrete slump test (b) measuring the slump (c) samples curing. Beam samples were cast simultaneously in custom-made wooden molds – see Fig. 2 (a) and kept wet throughout the curing period using special cloths that maintained humidity –see Fig. 2 (b), ensuring optimal curing conditions and sufficient hydration. The beams were moistened twice daily with water.Fig. 2from left to right (a) beam molds with steel cages (b) curing the concrete beams with wet cloths.Fig. 2 from left to right (a) beam molds with steel cages (b) curing the concrete beams with wet cloths. Destructive and non-destructive testing of concrete To monitor strength development, both destructive and non-destructive tests were conducted on cylindrical concrete samples at two maturity ages of 7 and 28 days as per the related standards. Ultrasonic pulse velocity (UPV) test The ultrasonic pulse velocity of waves transmitted through cylindrical concrete specimens was measured in accordance with ASTM C597 [77]. The UPV test was conducted using an ultrasonic pulse velocity tester fitted with cylindrical transducer heads. Testing was carried out on four cylindrical concrete samples, each with dimensions of 200 mm in height and 100 mm in diameter, at 7 and 28 days of curing, as shown in Fig. 3 (a). The velocity of the ultrasonic pulses was calculated using Eq. (1):Eq. 1v=Ltwhere v (m/sec) is the pulse travel velocity, L (m) is the length of the specimen, and t (sec) is the time duration.Fig. 3from left to right (a) UPV test (b) compression test (c) Static elasticity test.Fig. 3 from left to right (a) UPV test (b) compression test (c) Static elasticity test. Compressive strength test Compressive strength tests were performed on four samples at curing intervals of 7 and 28 days, following the ASTM C39/C39M standard [78]. The cylindrical samples, each measuring 200 mm in height and 100 mm in diameter, were tested using a compressive strength testing machine with a loading rate of 2.4 kN/s. The load was applied continuously until a clear fracture pattern appeared, as shown in Fig. 3 (b). The peak load value was recorded directly from the digital gauge of the test apparatus. The average compressive strength was determined using Eq. (2):Eq. 2σc=PAwhere σc represents the compressive strength in MPa, P is the maximum load in newtons, and A is the cross-sectional area in mm2. Static Modulus of Elasticity test The static modulus of elasticity (secant modulus ) was evaluated according to the ASTM C469/C469M standard [79] on the same cylindrical samples used in the non-destructive testing protocol. Four samples, with dimensions of 200 mm in height and 100 mm in diameter, were tested using the same compression testing machine at the previouse test. For this test, the machine is equipped with a compressometer featuring longitudinal and lateral dial gauges. The procedure involved positioning the sample within the testing machine and aligning it with the upper bearing plate, as illustrated in Fig. 3 (c). Stress-strain data in the longitudinal direction were recorded to calculate the modulus of elasticity, based on Eq. (3):Eq. 3E=S2−S1ε2−0.00005where E is chord modulus of elasticity in MPa [or psi], S2 is the stress corresponding to 40 % of the ultimate load, S1 is the stress corresponding to a longitudinal strain, ε1, of 50 millionths in MPa [or psi], and ε2 = longitudinal strain associated with S2. Table 2 presents the summary of the test results conducted on the cylindrical samples.Table 2Summary of average test results for the concrete cylindrical samples.Table 2Maturity Age (days)S (mm)UPV (km/sec)f′c (MPa)E (GPa)030–––7–4.8333.63028–4.6643.842.9S: Slump, f′c: compressive strength, E: Static Modulus of Elasticity. Table 2Summary of average test results for the concrete cylindrical samples.Table 2Maturity Age (days)S (mm)UPV (km/sec)f′c (MPa)E (GPa)030–––7–4.8333.63028–4.6643.842.9S: Slump, f′c: compressive strength, E: Static Modulus of Elasticity. Summary of average test results for the concrete cylindrical samples. S: Slump, f′c: compressive strength, E: Static Modulus of Elasticity. Beam specimens Four concrete beams were prepared and cast using high-strength concrete with a target compressive strength of 40 MPa, as described previously. Each beam measured 200 mm in width, 300 mm in height, and 1900 mm in length. Two plain RC beams served as control specimens, labeled RC_C, while the other two beams, designated as RC_CFRP, were strengthened with two different CFRP patterns. The CFRP was applied at the end of the curing period (i.e. 28 days). The internal reinforcement consisted of ASTM A572 Grade 50 (350 MPa) steel bars, including two No. 10 steel bars. Shear reinforcement was provided by No. 10 stirrups, spaced at 100 mm near the supports and 200 mm at midspan. The mechanical properties of the steel material are presented in Table 3.Table 3Steel reinforcement mechanical properties.Table 3Steel Gradefy(MPa)fu(MPa)εmin%, (200 mm)εmin%, (50 mm)ASTM A572 - Grade 503454501821fy yielding strength, fu ultimate strength, εmin percentage elongation. Table 3Steel reinforcement mechanical properties.Table 3Steel Gradefy(MPa)fu(MPa)εmin%, (200 mm)εmin%, (50 mm)ASTM A572 - Grade 503454501821fy yielding strength, fu ultimate strength, εmin percentage elongation. Steel reinforcement mechanical properties. fy yielding strength, fu ultimate strength, εmin percentage elongation. The two RC-CFRP beams have distinct CFRP configurations, each selected to induce specific failure modes. The first beam was reinforced with a single CFRP laminate applied on the top tensile side, designated as CFRP_T, intended to experience debonding followed by flexural stress. The second beam featured a U-shaped CFRP wrap, covering the top tensile side and both lateral sides, designated as CFRP_U, designed to fail solely due to flexural stress before debonding. The CFRP laminate used in this study has the properties shown in Table 4.Table 4CFRP laminate properties.Table 4E (GPa)σy (MPa)εy %σu (MPa)εu %Ut (MJ/m3)Ur (MJ/m3)45.7107.530.24051.349511.080.12E: Elastic Modulus, σy: Yield Strength, εy: Yield Strain, σu: Ultimate Strength, εu: Ultimate Strain, Ut: Toughness, Ur: Modulus of Resilience. Table 4CFRP laminate properties.Table 4E (GPa)σy (MPa)εy %σu (MPa)εu %Ut (MJ/m3)Ur (MJ/m3)45.7107.530.24051.349511.080.12E: Elastic Modulus, σy: Yield Strength, εy: Yield Strain, σu: Ultimate Strength, εu: Ultimate Strain, Ut: Toughness, Ur: Modulus of Resilience. CFRP laminate properties. E: Elastic Modulus, σy: Yield Strength, εy: Yield Strain, σu: Ultimate Strength, εu: Ultimate Strain, Ut: Toughness, Ur: Modulus of Resilience. The installation of CFRP has followed the ACI 440.2R-17 guidelines [80]. At day 28 of curing, the concrete surface was prepared prior to CFRP application by grinding to remove contaminants and create a slightly rough texture, improving bonding effectiveness. Once cleaned, epoxy resin was applied evenly across the prepared surface, and the CFRP laminate was carefully positioned onto the epoxy-coated area, ensuring full contact with minimal air pockets. To avoid excessive daytime heat, the application was conducted at night when the temperature ranged between 35 and 40 °C. After application, the beams were left outdoors to cure for seven days, allowing the epoxy to set under stable conditions and form a robust bond with the concrete for effective reinforcement. The effectiveness of FBGs in two key aspects was the primary focus of these configurations. Firstly, the capability of FBGs to detect debonding between CFRP and concrete was examined. Secondly, the study aimed to evaluate the capacity of these sensors in measuring large strain values. This investigation was essential for understanding the performance and reliability of FBGs in SHM of concrete beams reinforced with CFRP. Beams were designed with a flexural failure mechanism to assess the capacity and reliability of FBGs in capturing tensile strains accurately. The test parameters were designed to ensure a controlled and predictable failure mode, primarily due to bending stress rather than shear. This approach simulated conditions that maximally engaged flexural reinforcement, allowing for a comprehensive understanding of the maximum strain limits detected by the sensors. Reinforcement distribution was planned to effectively distribute loads, especially at critical support points, in alignment with the structural requirements outlined in the ACI-318 standard [81]. The required flexural and shear capacities for the beams shall satisfy equations Eq. 4, Eq. 5).Eq. 4ΦMn≥MuEq. 5ΦVn≥Vuwhere ΦMn and ΦVn represent the reduced flexural and shear capacities of the beam respectively and Mn and Vu are the ultimate moment and shear demands respectively. This specific design and casting process was crucial in evaluating the performance of the FBGs in capturing strains, loads, deflections, and temperature within these beams, thereby confirming their suitability for use in SHM. Experiment setup Three-point bending tests were conducted on beams using a full-scale loading frame available at the Australian University - Kuwait, as depicted in Fig. 4, Fig. 5. The beams were anchored from the top side at both ends and subjected to an uplift monotonic load at midspan, inducing a negative moment. This method employed self-strained configuration with the beams inverted to utilize the maximal tensile capacity of the loading frame. As shown in Fig. 6, stiffened steel support beams with drilled webs were utilized to provide the required end supports, allowing high strength threaded rods to secure the beams to the bottom beam of the frame. Temporary scaffolding supported the concrete beams before testing, with the tension side reinforced with CFRP laminates and/or internal steel facing upward. Lateral restraints were provided through the frictional interaction between the supporting steel beams and the concrete. The load was captured by a load cell located beneath the hydraulic jack.Fig. 4Schematic of the experimental setup.Fig. 4Fig. 5Loading frame with the testing setup.Fig. 5Fig. 6Beam supported by temporary scaffold prior to testing.Fig. 6 Schematic of the experimental setup. Loading frame with the testing setup. Beam supported by temporary scaffold prior to testing. Instruments The instrumentation plan was designed to capture a comprehensive range of mechanical responses from the tested beam, enabling a detailed analysis of the structural behavior up to the point of failure. It consisted of mechanical instruments for load application, reaction forces, and displacement measurements, in additionto the FBGs and foil SGs, connected to an interrogator and Data Acquisition System (DAQ) system for strain measurements. Mechanical instruments The mechanical setup for the experiment consisted of an Enerpac hydraulic jack with a capacity of 550 kN (62 tons), selected for its ability to apply a quasi-static load until failure. Positioned directly below the hydraulic jack was a RAL1-100 KS load cell, capable of measuring up to 445kN, which was used to capture the applied load. The load cell readings were monitored using a DI-1000UHS-10K DAQ with a specified sampling rate, ensuring real-time data capture. Additionally, deflection at midspan was measured using a Linear Variable Displacement Transducer (LVDT) with a 100 mm range, and the LVDT data were recorded using a D1I-1000HS-1K DAQ system. FBGs and SGs An extensive array of FBGs was carefully installed along the beam. The FBG sensor array, depicted in Fig. 7, included five sensors for strain measurement and one for temperature compensation, affixed directly to the steel reinforcement which had been smoothed at the sensor installation zones, as depicted in Fig. 8. These sensors were characterized by evenly spaced FBG wavelengths at 10 nm intervals.Fig. 7FBG sensor array.Fig. 7Fig. 8Surface preparation for direct gluing of the FBG to the steel bar.Fig. 8 FBG sensor array. Surface preparation for direct gluing of the FBG to the steel bar. The Mountable Strain Sensor (MS-03) from Sylex, shown in Fig. 9, with a measuring base of 90–110 mm, was installed on the exterior side of the beam for concrete strain monitoring.Fig. 9MS-03 Fiber strain sensor from Sylex.Fig. 9 MS-03 Fiber strain sensor from Sylex. The Strain Cable Sensor (SC-01), also from Sylex and illustrated in Fig. 10, with a 300 mm base, was utilized primarily for external strain measurement. It featured an integrated temperature sensor for additional temperature compensation and was designed to be immune to local defects or surface inhomogeneities. FBG Temperature sensor (TP-03) was used to measure and compensate for temperature changes. Two sizes of resistance SGs were used to measure strain BX120-3AA and BX120-80AA. BX120-3AA was used inside the beam and attached directly to the steel bars, while BX120-80AA was used externally on the concrete surface.Fig. 10SC-01 Fiber strain sensor from Sylex.Fig. 10 SC-01 Fiber strain sensor from Sylex. FBG interrogator and data acquisition and monitoring system The data acquisition from the FBGs was managed by an FBG X100 Interrogator from FiSens, which featured an embedded light source and onboard processing. It was capable of sampling at rates ranging from 1 to 100 Hz, with a wavelength bandwidth of 808–880 nm, ensuring measurement precision of 0.1 °C and 1 με. The strain gauge data were collected using a Microlink 770 unit, which supported 16 channels, 16-bit data acquisition, and a sampling rate of up to 100 KHz. Applied load data was captured by the DI-1000UHS-10K High-Speed USB Load Cell Interface, operating at sampling rates of up to 50 KHz. Additionally, the DI-1000U-5V was used to interface the displacement sensor, providing 24-bit resolution with a sampling rate of 80 Hz. For comparative accuracy, traditional SGs were installed alongside the FBGs on the steel reinforcement bars and the beam's tension surface, allowing for cross-verification of strain measurements and a comprehensive analysis of strain distribution across the structure. This instrumentation plan was designed to capture a full spectrum of mechanical responses from the tested beam, facilitating a detailed analysis of the structural behavior until failure. Strain calculation FBGs calculations: The measured strain Δε for all strain sensors that were used in this project is derived as the following:Eq. 6Δε=Δλ−B.ΔTA.Δl+ΔT.CTESS304.Δl2where Δλ, ΔT, Δl, and Δl₂ represent the shifted wavelength, shifted temperature, and shifted gauge lengths, respectively, which can be determined from Eqs. Eq. 7, Eq. 8, Eq. 9, Eq. 10), CTESS304 is the coefficient of thermal expansion (16 με/°C), while A (7.77588 × 10⁻⁷ με⁻1) and B (5.89292 × 10⁻⁶ °C⁻1) are the strain coefficients, as provided.Eq. 7Δλ=λact−λ0λ0Eq. 8ΔT=Tact−T0Eq. 9Δl=lFALlFFLEq. 10Δl2=(lFAL−lFFL)lFALwhere λac, λ0,Tact and T0 are the actual strain wavelength, initial strain wavelength, the actual temperature and initial temperature, respectively. The free fiber length (lFAL) is approximately 0.113 m for the MS-03 sensor, 0.237 m for the SC-01 sensor, and 0.1 m for the FBG sensor array. Similarly, the anchoring length (lFAL) is approximately 0.098 m for the MS-03 sensor, 0.22 m for the SC-01 sensor, and 0.1 m for the FBG sensor array. For SGs calculations; Two sizes of resistance SGs were used to measure strain BX120-3AA and BX120-80AA. All SGs were configured in a quarter bridge, and a dummy strain gauge was used for temperature compensation. The strain is calculated from the output voltage using Eq. (11):Eq. 11ε=4VokVswhere ε,k,VoandVs are the strain, gauge factor, output voltage and source voltage, respectively. Micro link 770 high speed data acquisition with 16 bits and 100 kHz was used to collect data. Sensors distribution The test matrix incorporated sensor type and placement variations to enable comparative evaluation. Each beam contained an array of FBG, including externally mounted FBGs as well as some traditional electrical resistance SGs embedded inside the concrete. Fig. 11, Fig. 12 depict the precise location of twelve sensors and gauges within the RC beams, a critical aspect of the setup. These sensors were carefully placed, both internally on the left and right steel fibers in the tension zone and externally at the furthest tension fiber of the concrete.Fig. 11Top view of steel reinforcement showing the location and designation of internal sensors with respect to the reinforcement bars. Sensor designations: (1) FBG strain sensor, (2) Unstrained FBG temperature sensor, (3) SG, (4) Unstrained SG for temperature compensation. Sensor positions: (A) exterior ends, (B) quarter span, (C) midspan zone.Fig. 11Fig. 123D view of the steel reinforcement and the locations of the internal FBGs and SGs on the reinforcement bars.Fig. 12 Top view of steel reinforcement showing the location and designation of internal sensors with respect to the reinforcement bars. Sensor designations: (1) FBG strain sensor, (2) Unstrained FBG temperature sensor, (3) SG, (4) Unstrained SG for temperature compensation. Sensor positions: (A) exterior ends, (B) quarter span, (C) midspan zone. 3D view of the steel reinforcement and the locations of the internal FBGs and SGs on the reinforcement bars. The internal sensors and gauges were distributed along the outermost surface of the reinforcement bars, ensuring their placement coincided with the zones that are most susceptible to experiencing maximum strain in the steel in tension. This deliberate placement allowed for the precise capture of strain data critical for assessing the structural behavior of the beams. To ensure comprehensive data collection, the internal sensors and gauges were spaced at regular intervals of precisely 300 mm. This careful spacing strategy was pivotal in guaranteeing that data collection spanned the entire length of the beams. This arrangement was instrumental in acquiring precise and comprehensive data throughout the entire structural span of the beams. On one tension reinforcement bar, six FOSs were placed strategically and played a pivotal role in data collection. Among these FOSs, one was designated as an Unstrained Fiber Optic Temperature sensor. This specialized sensor served the critical function of compensating for temperature variations during the monitoring process. The remaining five FOSs were specifically designed as strain FOS, tasked with recording and analyzing strain-related data. These sensors were instrumental in assessing the structural integrity of the RC beams during the test. The strain FOS utilized an FBG interrogation system with an accuracy of 1με. To facilitate a comprehensive comparative analysis of the data obtained from the distributed fiber sensors, a deliberate choice was made to incorporate two distinct types of gauges on the opposite side–in the tension zone of the beam. This approach enabled a detailed assessment of structural performance. Therefore, six traditional 120 Ω foil SGs were employed to provide a baseline for comparison. The SGs were installed on the second tension reinforcement bar. Additionally, an unstrained 120 Ω foil strain gauge, accurately calibrated for temperature compensation, was included to ensure that temperature variations do not introduce distortions into the collected data. Furthermore, it is imperative to highlight the precautions taken to safeguard and preserve the integrity of these sensors and gauges during the concrete casting process. This included protective coatings and careful placement and installation to mitigate any potential damage during concrete pouring. Moving to the top exterior side –the tension side of the beam, three distinct gauges of varying sizes were positioned to capture specific data points that are critical for this study. At the midpoint of the 1900 mm beam span, a substantial 300 mm FOS was securely affixed. This sensor was carefully placed to capture the maximum flexural strain in the beam. In addition to the 300 mm gauge, a smaller 100 mm strain gauge was installed at a distance of 500 mm from the midspan to provide more data points along the beam. Furthermore, two additional 100 mm SGs and one 100 mm strain FOS were carefully placed at 250 mm from each end to ensure a comprehensive understanding of strain distribution. These gauges provided valuable insights into the structural behavior at key points along the span. Fig. 13 illustrates the placement of sensors and gauges on the tension side of the concrete beam.Fig. 13Top view of the RC beam showing externally applied sensors. Sensor designations: (1) 30 cm long FBG, (2) 10 cm long FBG, (3) 10 cm long Strain Gauge. Sensor positions: (A) exterior side, (B) midspan.Fig. 13 Top view of the RC beam showing externally applied sensors. Sensor designations: (1) 30 cm long FBG, (2) 10 cm long FBG, (3) 10 cm long Strain Gauge. Sensor positions: (A) exterior side, (B) midspan. Collectively, this detailed placement of sensors and gauges, both on the interior (steel) and exterior (concrete/CFRP) tension zones of the beam, facilitated a thorough and robust data collection process. The instrumentation plan allowed for a comprehensive analysis of the structural performance of the RC beams under various loading conditions. Finite element analysis A two-dimensional finite element model (FEM) was developed to simulate the behavior of an RC_C beam. The NLFEA program VecTor2 [82] was utilized for this study primarily due to its proficiency in simulating the behaviors of RC. This was achieved through a smeared, rotating-crack approach based on the Modified Compression Field Theory (MCF) [83] and the Disturbed Stress Field Model (DCFM) [84]. The model utilized two continuum materials: steel and concrete. The steel and concrete materials were defined as per the properties in Table 2, Table 3 The beam was modeled using 2D quadratic elements to represent concrete, and 1D truss elements were used for steel reinforcement. These truss elements were constrained to the concrete elements at the common nodes, ensuring accurate load transfer under the assumption of a perfect bond between steel and concrete. Initial element size was set to 100 mm and was subsequently refined to 80 mm, 50 mm, 20 mm, and finally 10 mm. For each trial, the total reaction at the supports was captured and compared to the experimental values. The mesh size was optimized to match the dimensions of the steel and concrete elements, ensuring proper constraints for complete bonding and accurately capturing the resistance of the beam as measured in the experiment. The impact of the mesh size of the results of the FE analysis is presented in Fig. 15. A mesh size of 20 mm was selected, as it provided acceptable results with minimal error and relatively short calculation time. Additionally, mesh refinement was employed to ensure convergence and enhance the accuracy of the FEM results. The top surface of the beam was restrained at two locations corresponding to the ends of beam to replicate the actual support conditions. Five separate load cases were defined in the analysis: the initial load case represented the dead load of the beam, while the remaining four cases represented the application of upward displacement at the center of the bottom face of the beam, in a monotonic fashion, applied in four stages, to replicate the slow application of the load of the experiment. A secant stiffness formulation coupled with a total-load iterative procedure was employed for enhanced numerical robustness and convergence. Fig. 14 provides a schematic view of the beam and the corresponding FEM.Fig. 14Schematic of the test arrangement (up) and the FE model (down).Fig. 14Fig. 15Impact of mesh size on FE analysis results.Fig. 15 Schematic of the test arrangement (up) and the FE model (down). Impact of mesh size on FE analysis results. Results and observations The analysis encompassed an examination of all results derived from testing the four specimens. This examination carefully compared strain measurements obtained from the FBGs with those concurrently acquired from the traditional SGs. The performance of both external and internal gauges was recorded throughout the testing process. These observations, along with a detailed force-displacement relationships, are presented in this section, followed by a comprehensive discussion of results, supported by illustrative graphs for each specimen, providing valuable insights into the experimental outcomes. The RC_C beam results The RC_C serves as the baseline for this study; therefore, it was decided to run an NLFEA for this beam so the test results can be validated. The load-displacement relationship of the control beam, as shown in Fig. 16, has been examined. During the test, the nonlinear behavior of the beam was effectively captured. Notably, the illustrated relationship indicates a reduction in the stiffness of the RC beam, at approximately 4 mm midspan displacement and an ultimate load of 55 kN. This reduction in stiffness is attributed to the failure of concrete under tension with the propogation of cracks.Fig. 16Load-displacement charts for the RC_C beams.Fig. 16 Load-displacement charts for the RC_C beams. Furthermore, these observations were confirmed by the Vector2D FE model. A detailed comparison of the horizontal tensile strain at the top fiber of the beam reveals a good match between the NLFEA results and the experimental test data. However, it is important to note that the FBG sensor demonstrated enhanced sensitivity comparing to the SGs. It detected the sudden change in strain, which is indicative of severe crack formation and relative section rotation, at an earlier stage of deformation, specifically at around 2.5 mm displacements, or 3500 με, as depicted in Fig. 17.Fig. 17Longitudinal reinforcement strain versus vertical displacement at midspan for the RC_C beams.Fig. 17 Longitudinal reinforcement strain versus vertical displacement at midspan for the RC_C beams. This finding underscores the capability of the FBG sensor of early and precise detection of structural changes, providing crucial insights into the behavior of the beam under load. Early detection is vital for proactive SHM, particularly in critical infrastructure. In the experimental investigation of the simply supported concrete beam, the primary failure mode observed was flexural in nature. Initially, as a gradually increasing load was applied, the load-displacement relationship displayed a linear elastic behavior, indicating that the beam responded proportionally to the applied load. However, as the load reached 25 kN, a brief load plateau was observed, signaling a stabilization in the beam's response. Subsequently, as the load continued to increase, a flexural crack initiated and progressively propagated at the midspan of the beam. This phenomenon marked the transition from the linear elastic phase to a nonlinear region in the force-displacement curve. The nonlinear behavior in the curve was attributed to the development of the flexural crack and a reduction in the stiffness of the concrete beam. Ultimately, the applied load reached the ultimate load capacity, at which point the flexural crack had propagated significantly, and the beam could no longer support additional load. Post-failure behavior was characterized by further deformation and the presence of well-defined flexural crack, as illustrated in Fig. 18 (a). This analysis of the force-displacement curve provides valuable insights into the structural response and failure mechanisms of the simply supported concrete beam under experimental loading conditions and assures the reliability of the used sensors.Fig. 18Midspan cracks in the RC_C beam and CFRP rupture in the CFRP_T beam, as observed at failure through (a) the SGs and (b) the FBGs.Fig. 18 Midspan cracks in the RC_C beam and CFRP rupture in the CFRP_T beam, as observed at failure through (a) the SGs and (b) the FBGs. Strain versus sampling time plots for internal and external SGs are illustrated in Fig. 19 For internal SGs, it has been shown that the closer the gauge is to the center of the beam, the higher the strain. (Int_A) experienced a relatively low and steady strain of almost 50 με over the loading time however (Int_C) has increased significantly to about 1300 με with time. This happened due to the increase in the flexural demand at the center of the beam. On the other hand, (Ext_A) maintained almost the same behavior of the internal gauges and reached a maximum strain of almost 700 με, whereas (Ext_B) witnessed an increase in strain in a very short time afterward. It maintained a constant value of strain; this is due to the failure of strain gauge. Fig. 20 represents the strain-time relationship of FBGs that are embedded internally inside the beam. The graph shows that the path is almost like that obtained from the SGs, except those results from SGs encountered higher electrical noise than those from FBG.Fig. 19Strain versus sampling time for the internal and SGs on the RC_C beams.Fig. 19Fig. 20Strain versus sampling time for the internal FBGs on the RC_C beams.Fig. 20 Strain versus sampling time for the internal and SGs on the RC_C beams. Strain versus sampling time for the internal FBGs on the RC_C beams. CFRP_T beam results In the experimental analysis, the reinforced beam with CFRP on one side was subjected to load testing in a similar manner. The Load vs Displacement chart, denoted as Fig. 21, reveals that the behavior of the RC-CFRP- beam under loading was comparable to that of the control beam, up to a certain point. The reinforcement, however, allowed the beam to reach and sustain a higher maximum load of approximately 77 kN before failure, indicating a 40 % improvement in load-bearing capacity due to the CFRP.Fig. 21Load-displacement chart for the CFRP_T beam.Fig. 21 Load-displacement chart for the CFRP_T beam. The strain vs sampling time graph shown in Fig. 22 for the External FBGs displays a clear distinction between the readings from two gauges, External_A and External_B. The disparity in the results can be attributed to the location and size of the gauges. External_A registered a much lower strain compared to External_B, which can be interpreted as a variation due to the position of the gauge or potentially the influence of CFRP reinforcement on the strain distribution along the beam.Fig. 22Longitudinal strain in the FRP versus sampling time for external FBGs on the CFRP_T beam.Fig. 22 Longitudinal strain in the FRP versus sampling time for external FBGs on the CFRP_T beam. Collectively, these figures provide insights into the structural performance of CFRP_T beam and the efficacy of FBGs in capturing strain data, which are essential for assessing the health and integrity of such structures. During the testing phase, a critical observation was made when the CFRP-T beam reached its maximum load capacity. Approximately 120 s into the test, a distinctive snap sound was heard, indicating the onset of debonding between the CFRP layer and the concrete substrate. Likely, this was confirmed via visual inspection during the test. Despite the continuous monotonic increase in the applied load, the resistance of the beam experienced a precipitous drop at this juncture, signaling the transition to a dominant flexural failure mechanism as shown in Fig. 18(b). This phenomenon is clearly illustrated in Fig. 21, Fig. 22, where a sharp decline in the load—from 77 kN down to 55 kN— is evident at t =130 seconds. This abrupt reduction in load-bearing capacity aligns with the resistance of the control beam, underscoring a return to expected performance post-debonding. The chart serves as a graphical representation of this pivotal moment, capturing both the quantitative and qualitative aspects of the failure process. The audible cue of the snap, paired with the visual confirmation from the chart, provides a compelling narrative of the structural behavior under duress and the critical point of debonding that precedes flexural failure. CFRP_U beam results In the analysis of the CFRP_U beam, a distinctive confinement effect was achieved, as intended by the full wrapping. The force-displacement relationship exhibited by this specimen diverged notably from previous examples, as captured in Fig. 23. The graph depicted an almost nonlinear trajectory, reflective of the changing load behavior over time, signaling a possible alteration in the structural response due to the confinement. Embedded within the beam, internal FBGs and SGs were installed, providing closely correlated strain readings at points A and B, as shown in Fig. 24, Fig. 25. A notable observation was that the SGs recorded data over a more extended period than the FBGs, which may be indicative of their differing operational characteristics or limits. Additionally, the data revealed that the strain escalated with proximity to the center of the beam, which corresponds to the expected increase in bending.Fig. 23Load-displacement chart for CFRP_U beam.Fig. 23Fig. 24Longitudinal reinforcement strain versus sampling time for internal SGs on the CFRP_U beam.Fig. 24Fig. 25Longitudinal reinforcement strain versus time for internal FBGs on the CFRP_U beam.Fig. 25 Load-displacement chart for CFRP_U beam. Longitudinal reinforcement strain versus sampling time for internal SGs on the CFRP_U beam. Longitudinal reinforcement strain versus time for internal FBGs on the CFRP_U beam. Particularly striking was the performance of the internal FBGs in Fig. 25, which registered a sharp rise in strain, from approximately 3000 μm/m to an excess of 15000 μm/m, before stabilizing up to the point of failure. This suggests a critical threshold in the response of material under stress. Furthermore, Fig. 26 presented the strain-time relationship for external FBG gauges, highlighting contrasting behaviors. External_A demonstrated a consistently increasing strain pattern, whereas External_B exhibited fluctuations, reflecting the complexities of load behavior and its impact on the strain experienced by the structure. This divergence underscores the influence of CFRP wrapping on strain distribution and the importance of gauge placement in capturing accurate structural responses.Fig. 26Longitudinal strain in the FRP versus sampling time for external FBGs on the CFRP_U beam.Fig. 26 Longitudinal strain in the FRP versus sampling time for external FBGs on the CFRP_U beam. In conjunction with the previous findings, it was observed that the U-wrapped CFRP beam experienced debonding in two distinct stages, like the beam reinforced with CFRP on one side. The initial debonding occurred between the side CFRP laminates and the concrete, followed by a subsequent separation at the top side of the beam. Notably, these instances of debonding were registered at substantially higher strain levels compared to the previously examined beam. This indicates that the U-wrap configuration may contribute to a more robust bond, thereby delaying the onset of debonding and enhancing the overall strain capacity of the beam before failure. Discussion and conclusion FBGs demonstrated outstanding reliability, accuracy, and robustness under extreme environmental conditions, such as the intense summer temperatures in Kuwait. Unlike traditional SGs, FBGs maintained accurate strain measurements even under high-load conditions, successfully recording strains up to 16,000 με. Their superior sensitivity enabled the early detection of minor deformations, such as crack initiation and propagation, underscoring high precision of FBGs for SHM applications. The robustness of FBGs to electrical noise interference, which often affects SG readings, enhanced their reliability in environments with fluctuating temperatures and electromagnetic noise. The lightweight design, chemical compatibility, and multiplexing capabilities of FBGs make them ideal for long-term SHM in harsh conditions, establishing them as the preferred choice for SHM in infrastructure subjected to extreme environments. In monitoring RC and RC-CFRP beams, FBGs proved highly effective in detecting critical behaviors, including debonding and strain escalation. In CFRP_U beams, sensors captured substantial strain increases, exceeding 15,000 με before stabilization, marking their sensitivity to early failure signs and post crack performance. The U-wrap configuration enhanced confinement and bonding strength, facilitating more effective load transfer than single-sided reinforcement. Notably, staged debonding was observed between side laminates and concrete, indicating improved load transfer capabilities. The precise placement of FBGs allowed for detailed monitoring of these behaviors, reinforcing their essential role in SHM applications, with capabilities for detecting the transition from linear to nonlinear behavior and registering debonding events via sudden load drops and experimental observation (audible snaps). Integrating FBGs with traditional SGs offered complementary SHM data, providing a more reliable and comprehensive understanding of the structural performance of the tested beams. This combined approach aligns with findings by Zhang et al. [85] and Karatas et al. [86], which suggest that more accurate SHM data enables proactive maintenance and repair, ultimately extending the lifespan of critical infrastructure. The following points can be concluded from this study.•Superior sensitivity and robustness of FBGs: FBGs excelled in measuring strain under high-load conditions, maintaining accuracy up to 16,000 με, and exhibiting resistance to electromagnetic interference, making them suitable for SHM in harsh environments.•Early detection of debonding: FBGs effectively detected debonding between CFRP layers and the concrete substrate, providing early warning indicators critical for proactive maintenance strategies.•Multiplexing and monitoring efficiency: the multiplexing capability of FBGs enabled simultaneous monitoring across multiple beam locations, enhancing SHM efficiency without extensive wiring, a distinct advantage for large-scale infrastructure applications.•Enhanced structural performance with CFRP: CFRP reinforcement significantly increased the load-bearing capacity of RC beams by 40 %, achieving a peak load of 77 kN. FBGs successfully captured detailed strain distributions and critical load-bearing behaviors, underscoring their value for real-time monitoring and early failure detection in CFRP-strengthened RC structures.•FBG integration in SHM systems: integrating FBGs into SHM systems provides a promising approach to enhancing the monitoring, maintenance, and rehabilitation of critical infrastructure. The combination of FBG technology with advanced materials such as CFRP offers a robust solution for extending the service life of concrete structures. •Superior sensitivity and robustness of FBGs: FBGs excelled in measuring strain under high-load conditions, maintaining accuracy up to 16,000 με, and exhibiting resistance to electromagnetic interference, making them suitable for SHM in harsh environments. Superior sensitivity and robustness of FBGs: FBGs excelled in measuring strain under high-load conditions, maintaining accuracy up to 16,000 με, and exhibiting resistance to electromagnetic interference, making them suitable for SHM in harsh environments. •Early detection of debonding: FBGs effectively detected debonding between CFRP layers and the concrete substrate, providing early warning indicators critical for proactive maintenance strategies. Early detection of debonding: FBGs effectively detected debonding between CFRP layers and the concrete substrate, providing early warning indicators critical for proactive maintenance strategies. •Multiplexing and monitoring efficiency: the multiplexing capability of FBGs enabled simultaneous monitoring across multiple beam locations, enhancing SHM efficiency without extensive wiring, a distinct advantage for large-scale infrastructure applications. Multiplexing and monitoring efficiency: the multiplexing capability of FBGs enabled simultaneous monitoring across multiple beam locations, enhancing SHM efficiency without extensive wiring, a distinct advantage for large-scale infrastructure applications. •Enhanced structural performance with CFRP: CFRP reinforcement significantly increased the load-bearing capacity of RC beams by 40 %, achieving a peak load of 77 kN. FBGs successfully captured detailed strain distributions and critical load-bearing behaviors, underscoring their value for real-time monitoring and early failure detection in CFRP-strengthened RC structures. Enhanced structural performance with CFRP: CFRP reinforcement significantly increased the load-bearing capacity of RC beams by 40 %, achieving a peak load of 77 kN. FBGs successfully captured detailed strain distributions and critical load-bearing behaviors, underscoring their value for real-time monitoring and early failure detection in CFRP-strengthened RC structures. •FBG integration in SHM systems: integrating FBGs into SHM systems provides a promising approach to enhancing the monitoring, maintenance, and rehabilitation of critical infrastructure. The combination of FBG technology with advanced materials such as CFRP offers a robust solution for extending the service life of concrete structures. FBG integration in SHM systems: integrating FBGs into SHM systems provides a promising approach to enhancing the monitoring, maintenance, and rehabilitation of critical infrastructure. The combination of FBG technology with advanced materials such as CFRP offers a robust solution for extending the service life of concrete structures. Future research directions: future work should focus on dynamic load testing, exploring diverse reinforcement materials, and conducting long-term durability assessments of FBGs in various environmental conditions. Integrating FBG technology with emerging monitoring techniques could provide more comprehensive SHM data collection, advancing infrastructure reliability. CRediT authorship contribution statement Mohammad Hany Yassin: Conceptualization, Methodology, Supervision, Modeling, Software, Visualization, Writing – original draft, Writing – review & editing. Mohamad Hussein Farhat: Supervision of the project, Budget management, Funding acquisition, Data analysis, Data curation, Writing – review & editing. Michel Nahas: Project administration, Resources, Investigation, Supervision of tests, Data management. Ahmad Said Saad: Investigation, Software, Validation, Writing – review & editing. Data availability statement Some or all data, models, or code that support the findings of this study are available from the corresponding author upon reasonable request. Declaration of competing interest The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper.