Fault diagnosis of HVCB via the subtraction average based optimizer algorithm optimized multi channel CNN-SABO-SVM network
Qingjun Song, Jiuxin Wang, Qinghui Song, Kai Li, Wenchao Hao, Haiyan Jiang · 2024
Read Fault diagnosis of HVCB via the subtraction average based optimizer algorithm optimized multi channel CNN-SABO-SVM network by Qingjun Song, Jiuxin Wang, Qinghui Song, Kai Li, Wenchao Hao, Haiyan Jiang (2024) in the Tower of Babel, a free online library of public-domain works preserved in clean, searchable text. No sign-up. The full text is served as a plain-text file at a predictable URL, where text is present: https://antarctic-labs.com/tower-of-babel/pmc-11603140.txt.
Description
Qingjun Song and five co-authors spot faults in high-voltage circuit breakers by sound and vibration, fused in one network. Breaker faults can shake the whole grid, yet fault samples are small, which starves deep networks. Their 2024 model takes two-form data through a multi-path grid network and fuses the traits. A voting classifier head then makes the calls, in place of the stock soft head, for toughness on small sample sets.
A mean-shift optimizer tunes the dials of that head on its own. A test rig built for the work feeds training and test runs. Next to a fused network with a stock head, accuracy rose 2.66 points; next to one-form networks, it rose 10.66 points. Small sample sets need such craft, they hold.
Catalog record
| CREATOR | Qingjun Song, Jiuxin Wang, Qinghui Song, Kai Li, Wenchao Hao, Haiyan Jiang |
|---|---|
| YEAR | 2024 |
| COLLECTION | PAPERS |
| FORMAT | TXT |
| FILE SIZE | 95 KB |
| VERSION | 1.0 |
| LICENSE | CC BY 4.0 |
| RIGHTS | CC BY |
| SOURCE | Europe PMC |