Radio Frequency Field Programable Gate Array Implementation of Reflectometry Cable Monitoring
Glass, Samuel W., Tedeschi, Jonathan R., McDaid, Stephanie L. et al. · 2025
Read Radio Frequency Field Programable Gate Array Implementation of Reflectometry Cable Monitoring by Glass, Samuel W., Tedeschi, Jonathan R., McDaid, Stephanie L. et al. (2025) in the Tower of Babel, a free online library of public-domain works preserved in clean, searchable text. No sign-up. The full text is served as a plain-text file at a predictable URL, where text is present: https://antarctic-labs.com/tower-of-babel/doe-osti-3363881-radio-frequency-field-programable-gate-a.txt.
Introduction
Pacific Northwest National Laboratory report PNNL-38235, by S. W. Glass, J. Tedeschi, S. L. McDaid, M. S. Elen, and L. S. Fifield, appeared in September 2025 under the Light Water Reactor Sustainability Program. It describes a single-board device that tests power plant cables using reflectometry, which sends signals down a cable and reads the echoes to find damage. The board pairs a radio frequency system-on-chip with a field programmable gate array, a chip whose circuits can be rewired in software.
The device performs both frequency domain reflectometry and spread spectrum time domain reflectometry, for cables taken offline or still in service. The team adapted earlier laboratory methods onto the compact board and evaluated its performance. A clamp-on current coupler design also gets attention, including a printed centering fixture that steadied readings. The goal is portable cable checks for aging nuclear plants.
Catalog record
| CREATOR | Glass, Samuel W., Tedeschi, Jonathan R., McDaid, Stephanie L. et al. |
|---|---|
| YEAR | 2025 |
| COLLECTION | PAPERS |
| FORMAT | TXT |
| FILE SIZE | 51 KB |
| LICENSE | Public Domain |
| RIGHTS | PUBLIC DOMAIN |
| SOURCE | DOE OSTI |
Browse the full library · About the Tower of Babel
Full text
The opening of the work, from the library's hosted text:
PNNL-38235 M3LW-25OR0404023 Light Water Reactor Sustainability Program Radio Frequency Field Programable Gate Array Implementation of Reflectometry Cable Monitoring S.W. Glass, J. Tedeschi, S.L. McDaid, M.S. Elen, L.S. Fifield Pacific Northwest National Laboratory September 2025 U.S. Department of Energy Office of Nuclear Energy PNNL-38235 Milestone #: M3LW-25OR0404023 Radio Frequency Field Programable Gate Array Implementation of Reflectometry Cable Monitoring S.W. Glass, J. Tedeschi, S.L. McDaid, M. Elen, L.S. Fifield Pacific Northwest National Laboratory September 2025 Prepared by Pacific Northwest National Laboratory Richland, WA 99354 operated by Battelle for the U.S. Department of Energy Under Contract DE-AC05-76RL01830 SUMMARY This document describes the development of a field programable gate array (FPGA) radio frequency system on a chip (RF SoC) adaptation and evaluation of the single-board device to perform both Frequency Domain Reflectometry (FDR) and Spread Spectrum Time Domain Reflectometry (SSTDR) for offline and online cable testing. The work builds on and leverages the work of Pacific Northwest CONTENTS SUMMARY .................................................................................................................................................. ii ACKNOWLEDGEMENTS ......................................................................................................................... iii CONTENTS ................................................................................................................................................. iv FIGURES ...................................................................................................................................................... v ACRONYMS ............................................................................................................................................... vi 1. INTRODUCTION .............................................................................................................................. 1 1.1 FREQUENCY DOMAIN REFLECTOMETRY ..................................................................... 2 1.2 SPREAD SPECTRUM TIME DOMAIN REFLECTOMETRY ............................................. 3 1.3 INDUCTIVE CURRENT COUPLER ..................................................................................... 4 2. FIELD PROGRAMABLE GATE ARRAYS ..................................................................................... 6 3. DEVELOPMENT OF AN FPGA MULTI-CHANNEL FDR AND SSTDR DEVICE ..................... 7 3.1 HARDWARE ARCHITECTURE ........................................................................................... 7 3.2 SOFTWARE ARCHITECTURE ............................................................................................. 9 4. TEST AND EVALUATION ............................................................................................................ 10 5. TEST RESULTS .............................................................................................................................. 13 6. LOW VOLTAGE ENERGIZED CABLE TESTING ...................................................................... 15 7. CONCLUSIONS .............................................................................................................................. 17 REFERENCES ........................................................................................................................................... 18 APPENDIX 1: FPGA software ................................................................................................................... 19 iv FIGURES Figure 1. The FDR cable test introduces a swept frequency chirp onto a conductor and then monitors reflections from impedance changes along the cable length. ........................................ 3 Figure 2. SSTDR cable test applies a PN code to the conductor for cross-correlation analysis. .................. 4 Figure 3. Architecture of a typical current probe. ......................................................................................... 5 Figure 4. Example of a commercial clamp-on current probe........................................................................ 6 Figure 5. This product provides good response from 1 to 500 MHz with low frequency isolation including operational line frequencies. ......................................................................................... 6 Figure 5. This product provides good response from 1 to 500 MHz with low frequency isolation including operational line frequencies. ......................................................................................... 6 Figure 6. RF SoC high level architecture shown with RF Front End and Cable(s) Under Test ................... 7 Figure 7. PNNL RF SoC Hardware Configuration ....................................................................................... 8 Figure 8. High-level schematic of a single RF front end channel ................................................................. 9 Figure 9. Copper Mountain VNA with std 1-port connect (left), and 2-port test configuration (right) with RF Open/Short/Load calibration standards in lower left of images ........................ 11 Figure 10. RF test cable measured on standard 1-port VNA configuration and 2-port VNA configuration to validate the calibration method that would be utilized with the RF SoC. ............................................................................................................................................ 11 Figure 11. Shorted RF test cable comparison plots between std 1-port calibration and manual 2- port calibration. ........................................................................................................................... 12 Figure 12. FDR performance comparison between RF SoC (left), and Copper Mountain VNA (right) .......................................................................................................................................... 12 Figure 13. Shorted RF test cable SSTDR correlation results for different reference waveforms. Ideal SSTDR waveform (left), Short standard waveform (middle), and Short–Open standard (left) .............................................................................................................................. 13 Figure 14. CUT connection to the RF SoC system channel 1 (left), CUT test configuration (right) ......... 14 Figure 15. FDR measurement results between channel 1 and 2 for an approximately 170 ft cable ........... 14 Figure 16. Test configuration for simultaneous multi-conductor monitoring ............................................. 15 Figure 17. Simultaneous dual channel multi-conductor monitoring FDR responses ................................. 15 Figure 18. Energized test configuration for RF SoC and VNA FDR. ........................................................ 16 Figure 19. Cable Fault................................................................................................................................. 16 Figure 20. 480 VAC energized 200 ft low voltage cable FDR results for a Copper Mountain VNA vs. the RF SoC system ................................................................................................................ 17 v ACRONYMS AC alternating current (60 Hz in the US) ADC analog-to-digital converter AMD Advanced Micro Devices CUT cable or cable segment under test DAC digital-to-analog converter DC direct current DMA Direct Memory Access DOE U.S. Department of Energy EMI electromagnetic Interference EQ environmentally qualified FDR frequency domain reflectometry FFT fast Fourier transform FPGA field programmable gate array Hz Hertz (per second, unit of frequency) IF intermediate-frequency I/O input/output LWRS Light Water Reactor Sustainability LOCA Loss of Coolant Accident NPP nuclear power plant PCB printed circuit board PN pseudo-random noise PNNL Pacific Northwest National Laboratory RAM random access memory RF radio frequency (typically 3 kilohertz (kHz) to 300 gigahertz (GHz)) RF SoC radio frequency system on a chip SSTDR spread spectrum time domain reflectometry SMA Sub-Miniature Version A connector SNR signal-to-noise ratio V volt VNA vector network analyzer vi 1. INTRODUCTION Safety critical nuclear power plant (NPP) cables were initially type-tested and qualified in typical worst- case environments equivalent to a service life of 40 years. As part of subsequent licence renewals to either 60 or 80 years, the cable’s continued use is justified by an aging management program which includes cable testing. Cable degradation can occur due to several factors including heat, moisture, chemical exposure, radiation, flexure, abrasion, and pinching; plus connector and splice crimp workmanship issues. All these factors can lead to cable insulation materials crumbling, separating, eroding, degrading dielectric insulation properties, or breaking and exposing conductors that may lead to low-resistance, short or open circuits and corresponding circuit failures with associated safety risks and/or operational outages. The environment and stress duration of a cable in service varies based on the cable function but environmentally qualified (EQ) cables are required to survive and continue to function following a LOCA (Loss of Coolant Accident) and consequent accident radiation dose exposure after thermal accelerated aging and radiation aging equivalent to 40 years of exposure to the NPP environment (IEEE 2015). During the first 40 years of life, plant operators are not required to test these cables beyond normal system function verification tests. With plant life extension, however, cables are called on to continue to function beyond their initial qualified life. Testing has shown that most cables can continue to serve their function well beyond their 40-year initial qualification and so their continued use is justified by a cable test program. This typically involves: • Scheduling the cable test during an outage or period where the safety critical system can be taken out of service. • Disconnecting the cable. • Performing one or more tests of the cable from one or both ends of the cable. (Note that cables are commonly buried in conduit or otherwise inaccessible for most of their length). • Typically, tests conclude that the cable is good, bad, or needs further evaluation. Practical management of a “bad” or “needs further evaluation” cable may include full replacement or identification of damage location and splicing in a new piece of cable then re-testing. • Once the cable segment tests “good”, the cable must be re-connected and the system returned to service. Reconnections are performed by trained staff but experience shows that workmanship errors are among the most common causes of cable failure (Pyy 2001). An alternative paradigm to this periodic testing could be online condition monitoring. Condition monitoring may be used in place of a qualified life to determine if qualified equipment is suitable for further service (NRC 2010). Condition monitoring for the purpose of equipment qualification