Unstable Poles Arising in AC Power Grid Subsystem Representations

Liam Hallinan, Ioannis Lestas · 2026

Read Unstable Poles Arising in AC Power Grid Subsystem Representations by Liam Hallinan, Ioannis Lestas (2026) in the Tower of Babel, a free online library of public-domain works preserved in clean, searchable text. No sign-up. The full text is served as a plain-text file at a predictable URL, where text is present: https://antarctic-labs.com/tower-of-babel/arxiv-2606-03514.txt.

Description

Hallinan and Lestas warn that split views of an AC power grid can hide unstable poles. Grid studies now treat the grid as linked subsystems. Input-output traits of each part then support scalable stability checks. Two views appear often in that work. The PQ model links powers to angle and voltage size. The IV model links currents to voltages.

Both models are derived here without trimming bus or line dynamics. A loop transformation turns out to relate the two views. Each view can show unstable poles on its own. For the IV model, the risk hangs on the operating point. For the PQ model, high-frequency passive dynamics drive it. These poles can appear even when the whole grid is stable. Numeric tests confirm the effect, down to a full generator case. Engineers must choose a view with care, or the checks will miss what the network must stabilize.

Catalog record

CREATORLiam Hallinan, Ioannis Lestas
YEAR2026
COLLECTIONPAPERS
FORMATTXT
FILE SIZE43 KB
LICENSEhttp://creativecommons.org/licenses/by/4.0/
RIGHTSCC BY
SOURCEarXiv

Source: https://arxiv.org/abs/2606.03514

Browse the full library · About the Tower of Babel