Voltage and Frequency Stability Analysis of Transmission Power Grids with EV Charging Stations
Akib Mostabe Refat 1 , Mohammed F. Al-Mashdali 1 , Alan Cordic 1 , Abdulaziz Qwbaiban 1 , Emad Abukhousa 4 , Kazi N. Hasan 5 , M. A. Abido 1,2,3 , Mohammed Al-Muhaini 1 1 Electrical Engineering Department, King Fahd University of Petroleum & Minerals (KFUPM), Dhahran 31261, Saudi Arabia 2 Interdisciplinary Research Center for Sustainable Energy Systems (IRC-SES), KFUPM, Dhahran 31261, Saudi Arabia 3 SDAIA-KFUPM Joint Research Center for Artificial Intelligence, KFUPM, Dhahran 31261, Saudi Arabia 4 School of Electrical and Computer Engineering, Georgia Institute of Technology, Atlanta, GA, USA 5 School of Engineering, RMIT University, Melbourne 3001, Australia { g202315250, g201864560, g202525710, qwbaiban, mabido, muhaini } @kfupm.edu.sa ; [email protected] ; [email protected] · 2026
Read Voltage and Frequency Stability Analysis of Transmission Power Grids with EV Charging Stations by Akib Mostabe Refat 1 , Mohammed F. Al-Mashdali 1 , Alan Cordic 1 , Abdulaziz Qwbaiban 1 , Emad Abukhousa 4 , Kazi N. Hasan 5 , M. A. Abido 1,2,3 , Mohammed Al-Muhaini 1 1 Electrical Engineering Department, King Fahd University of Petroleum & Minerals (KFUPM), Dhahran 31261, Saudi Arabia 2 Interdisciplinary Research Center for Sustainable Energy Systems (IRC-SES), KFUPM, Dhahran 31261, Saudi Arabia 3 SDAIA-KFUPM Joint Research Center for Artificial Intelligence, KFUPM, Dhahran 31261, Saudi Arabia 4 School of Electrical and Computer Engineering, Georgia Institute of Technology, Atlanta, GA, USA 5 School of Engineering, RMIT University, Melbourne 3001, Australia { g202315250, g201864560, g202525710, qwbaiban, mabido, muhaini } @kfupm.edu.sa ; [email protected] ; [email protected] (2026) in the Tower of Babel, a free online library of public-domain works preserved in clean, searchable text. No sign-up. The full text is served as a plain-text file at a predictable URL, where text is present: https://antarctic-labs.com/tower-of-babel/arxiv-2605-26602.txt.
Introduction
Akib Mostabe Refat and seven colleagues study voltage and frequency stability in transmission grids with EV charging stations. Large EV grid entry challenges stability through dynamic loadability events. While distribution-system EV impacts are well studied, transmission-level work remains limited. The team models charging-station loads for voltage and frequency stability analysis on the transmission grid. EV stations cause more stability complexity than other loads through high loadability. Simulations run on the IEEE-9 and IEEE-39 bus test systems.
Catalog record
| CREATOR | Akib Mostabe Refat 1 , Mohammed F. Al-Mashdali 1 , Alan Cordic 1 , Abdulaziz Qwbaiban 1 , Emad Abukhousa 4 , Kazi N. Hasan 5 , M. A. Abido 1,2,3 , Mohammed Al-Muhaini 1 1 Electrical Engineering Department, King Fahd University of Petroleum & Minerals (KFUPM), Dhahran 31261, Saudi Arabia 2 Interdisciplinary Research Center for Sustainable Energy Systems (IRC-SES), KFUPM, Dhahran 31261, Saudi Arabia 3 SDAIA-KFUPM Joint Research Center for Artificial Intelligence, KFUPM, Dhahran 31261, Saudi Arabia 4 School of Electrical and Computer Engineering, Georgia Institute of Technology, Atlanta, GA, USA 5 School of Engineering, RMIT University, Melbourne 3001, Australia { g202315250, g201864560, g202525710, qwbaiban, mabido, muhaini } @kfupm.edu.sa ; [email protected] ; [email protected] |
|---|---|
| YEAR | 2026 |
| COLLECTION | PAPERS |
| FORMAT | TXT |
| FILE SIZE | 20545 |
| LICENSE | http://creativecommons.org/licenses/by/4.0/ |
| RIGHTS | CC BY |
| SOURCE | arXiv |
Source: https://arxiv.org/abs/2605.26602
Browse the full library · About the Tower of Babel
Full text
The opening of the work, from the library's hosted text:
Voltage and Frequency Stability Analysis of Transmission Power Grids with EV Charging Stations Akib Mostabe Refat 1 , Mohammed F. Al-Mashdali 1 , Alan Cordic 1 , Abdulaziz Qwbaiban 1 , Emad Abukhousa 4 , Kazi N. Hasan 5 , M. A. Abido 1,2,3 , Mohammed Al-Muhaini 1 1 Electrical Engineering Department, King Fahd University of Petroleum & Minerals (KFUPM), Dhahran 31261, Saudi Arabia 2 Interdisciplinary Research Center for Sustainable Energy Systems (IRC-SES), KFUPM, Dhahran 31261, Saudi Arabia 3 SDAIA-KFUPM Joint Research Center for Artificial Intelligence, KFUPM, Dhahran 31261, Saudi Arabia 4 School of Electrical and Computer Engineering, Georgia Institute of Technology, Atlanta, GA, USA 5 School of Engineering, RMIT University, Melbourne 3001, Australia { g202315250, g201864560, g202525710, qwbaiban, mabido, muhaini } @kfupm.edu.sa ; [email protected] ; [email protected] Abstract The large-scale Electric Vehicle (EV) integration into the electricity grid has initiated significant challenges to grid stability issues due to dynamic loadability events. Although electric vehicle impacts on distribution systems are well studied, transmission-level investigations remain limited. In this research paper, case scenarios of EV load models as charging stations have been considered for stability analysis (Voltage and Frequency Stability) to address EV operation on the transmission grid. It is also noted that the operation of EV stations due to their high loadability causes more stability complexities to the grid compared to other loads in a power network. Simulations have been conducted on two different power networks of the IEEE-9 and IEEE-39 bus test systems, respectively. I Introduction Electric Vehicle (EV) integration into transmission networks significantly affects grid stability, especially at vulnerable buses. To evaluate variation in power and system voltage, EVs alter grid stability and should be modeled as three-phase dynamic loads. Stability analysis is necessary to evaluate real and reactive power loading, weak lines and grid oscillations. Recent research has explored the combined impact of EVs and renewable sources such as Photovoltaic (PV) systems, on power quality and stability [1]. Maintaining voltage within \textpm 5\% – 6\% of nominal value after disturbances [2][3] and a power factor of at least 0.95 are vital for secure grid operation [4]. Tavakoli et al. [1] analyzed the joint PV–EV impact and emphasized coordinated control to sustain grid stability. However, most studies focus on distribution-level power quality or steady-state voltage. Recent probabilistic and deep-learning methods improve voltage-stability prediction in renewable networks but are seldom applied to EV integrated transmission systems [5][6]. Momoh et al. [7] have articulated the future directions on Single Stage Converter (SSC) technique to address the State of Charge (SoC) problems of EV charging stations in maintaining grid stability. This research focuses on the voltage and frequency stability of EV integrated transmission networks using IEEE-9-bus and IEEE-39-bus test systems. Three EV load models are developed to analyze their grid impact. Voltage stability is assessed using P–V curves to address voltage collapse under heavy loading, the Fast Voltage Stability Index (FVSI), and the Novel Line Stability Index (NLSI) to identify weak transmission lines and determine loadability limits. Frequency stability, primarily governed by generator inertia, is defined as maintaining synchronism by sustaining core frequency parameters following grid disturbances and power imbalances [2]. The North American Electric Reliability Corporation (NERC) report highlights key frequency-response concerns and stresses the need for simulation case studies for interconnection stability [8]. It is analyzed for the IEEE-9-bus system under grid disturbances and EV load placements using two main metrics—Frequency Nadir and Rate of Change of Frequency (ROCOF). Multi-Band PSS (MB-PSS) and Automatic Generation Control (AGC) are also examined to show improved damping and frequency regulation, guiding EV load placement in weak grids by explaining post-disturbance restoration. To address rising EV demand, this study focuses on the stability limitations since very few research works have been conducted to consider EV charging stations in transmission grids [9]. This research contributes to the assessment of grid impacts on voltage and frequency stability to facilitate large-scale EV charging station integration, through the development of appropriate EV load models and the identification of optimal modeling parameters. The remainder of this paper is organized as follows: Section II presents the modeling framework and methodology for EVs and transmission networks, respectively; Section III discusses simulation results and solutions for voltage and frequency stability; and Section IV concludes the paper with major findings and recommendations for future work. II Methodology and modeling This paper concentrates on EV station modelling approaches for stability analysis of grid integration using the IEEE-9 and IEEE-39 power networks as test cases. MATLAB/Simulink software models the transmission network and dynamic EV loads have been developed. II-A Systematic modeling of EV load for grid integration To realize the stability analysis problem, a simple 2-bus system scenario incorporating an EV and a load is considered. The load includes a constant-power type and EV, with power transfer between buses. Previously, EV load was regarded as a Constant Impedance, Current, and Power (ZIP) model. Tavakoli et al. [1] defined the EV station as a dynamic load by including the constant power components a and b and a voltage negative exponential term \alpha , as shown in equation (1). The parameters described in (1) have been utilized in different EV models under dynamic three phase load block. The actual dynamic load equation in (2) is predefined in the SIMULINK workspace, where exponent, n_{p} controls the load type and T_{p} , T_{s} are the time constants representing active power in (2) [10]. \frac{P}{P_{0}}=a(\frac{V}{V_{0}})^{\alpha}+b (1) \frac{P}{P_{0}}=(\frac{V}{V_{0}})^{n_{p}}(\frac{1+T_{p}}{1+T_{s}}) (2) where P , V , P_{0} , and V_{0} indicate real power consumption and voltages with existing and initial measurements on the EV load bus, respectively. Therefore, the following EV load model constraints (3) - (6) are described in detail to ensure the system stability of the power network model. It is to be noted that the value of power components and lead resistance, R_{L} varies based on the power network type. \displaystyle\alpha \displaystyle\leq-1 (3) \displaystyle 0.05 \displaystyle\leq a\leq 0.07 (4) \displaystyle 0.93 \displaystyle\leq b\leq 0.95 (5) \displaystyle 0.01\,\Omega \displaystyle\leq R_{L}\leq 0.09\,\Omega (6) By considering the number and system constraints of dynamic EV model for grid integration in such a way to ensure the following power system constraints (7) - (9). \displaystyle\text{{FVSI,NLSI}}<1 (7) \displaystyle 59.5\,\text{Hz}\leq f_{\text{nom}}\leq 60.1\,\text{Hz} (8) \displaystyle\text{{ROCOF}}<1\,\text{Hz/s} (9) II-B Description of the power transmission network model This section presents a summary of test bus systems on large-scale EV load model integration affecting grid stability. Stability studies are performed on the IEEE-9 and IEEE-39 bus networks described in [5][11], with Table - 1 listing key system parameters for load-flow analysis. The P–V curve algorithm from [6] is implemented in this research. TABLE I : Transmission Network System Parameters Parameter Value Frequency fsys 60 Hz Base Voltage Vb (IEEE-9) 230 KV Base Voltage Vb (IEEE-39) 345 KV Solar Irradiance G_{rated} 1000\ \text{W}/\text{m}^{2} To identify weak transmission lines prone to congestion under EV load integration, suitable stability indices are applied. Following Salama and Vokony [12], the FVSI and NLSI in (10) and (11) are adopted, and their values must remain below unity to avoid system instability. The equations with subscripts i and j represent the sending and receiving end busses, respectively. FVSI=\frac{4Z_{ij}^{2}Q_{j}}{V_{j}^{2}X_{ij}} (10) NLSI=\frac{R_{ij}P_{j}+X_{ij}Q_{j}}{0.25V_{j}^{2}} (11) II-C EV load modeling approaches in transmission network planning EV load integration into the power grid significantly affects