Differentially Private Obfuscation of Power Grid Dynamics
Shengyang Wu, Vladimir Dvorkin · 2026
Read Differentially Private Obfuscation of Power Grid Dynamics by Shengyang Wu, Vladimir Dvorkin (2026) in the Tower of Babel, a free online library of public-domain works preserved in clean, searchable text. No sign-up. The full text is served as a plain-text file at a predictable URL, where text is present: https://antarctic-labs.com/tower-of-babel/arxiv-2605-24725.txt.
Introduction
Shengyang Wu and Vladimir Dvorkin synthesize dynamic power-grid models that protect source-grid privacy without losing quality. Real grid models aid blackout and shock analysis, yet their release risks exposing sensitive transmission, generation, and load settings. Their algorithm adds privacy noise to hide original settings, then tunes the perturbed settings so model dynamics stay statistically matching with the source grid. The privacy guarantee uses differential privacy as its yardstick. On frequency dynamics of the IEEE 30-bus system, stricter privacy degrades quality, yet tuning greatly improves the built models.
Catalog record
| CREATOR | Shengyang Wu, Vladimir Dvorkin |
|---|---|
| YEAR | 2026 |
| COLLECTION | PAPERS |
| FORMAT | TXT |
| FILE SIZE | 49580 |
| LICENSE | http://creativecommons.org/licenses/by-sa/4.0/ |
| RIGHTS | CC BY SA |
| SOURCE | arXiv |
Source: https://arxiv.org/abs/2605.24725
Browse the full library · About the Tower of Babel
Full text
The opening of the work, from the library's hosted text:
Differentially Private Obfuscation of Power Grid Dynamics Shengyang Wu, Vladimir Dvorkin Abstract Dynamic models of power systems are critical for analyzing grid response to disturbances and blackouts, but the release of real-world dynamic models is hindered by privacy and cybersecurity concerns, as such models carry sensitive information about transmission, generation, and load parameters. We develop an algorithm for synthesizing dynamic grid models from real-world power grids balancing two objectives: the privacy of the source grid, quantitatively measured using the notion of differential privacy, and the fidelity of the synthesized model. The algorithm applies privacy-preserving noise to obfuscate the original grid parameters, but then optimizes the perturbed parameters to ensure that the resulting model dynamics are statistically consistent with those observed in the source grid. Application to the frequency dynamics of the IEEE 30-bus system reveals the inherent privacy-fidelity trade-off: stricter privacy requirements degrade modeling fidelity, yet optimization significantly improves the quality of the synthesized models. I Introduction Power system dynamics governs how the grid responds to disturbances and rapidly changing conditions. With growing complexity from the integration of renewable energy resources [ 17 , 34 ] and AI electricity demand [ 26 ] , accurate dynamic models are imperative for resilient control [ 25 , 31 ] and post-event analysis of blackouts [ 15 ] . Yet, releasing real-world dynamic models is hindered by privacy and cybersecurity concerns. For example, disclosing generator models enables targeted AGC cyberattacks [ 37 ] , while releasing frequency dynamics models exposes network topology and line parameters, thereby facilitating integrity attacks on power markets [ 40 ] . Kron reduction techniques [ 9 , 21 , 7 , 32 ] eliminate selected buses while preserving input-output dynamics, inherently obfuscating network topology and admittance data. However, the eliminated data remain vulnerable to reverse engineering under voltage and current measurements [ 30 , 29 ] , while the reduced models can also seed data-driven topology estimation methods capable of recovering the original topology [ 8 ] . Differential privacy (DP) [ 14 ] provides algorithmic foundations for privacy-preserving data publication. By perturbing the source data with carefully calibrated noise, DP renders any two adjacent datasets statistically indistinguishable in the random outcome of the perturbation, up to prescribed privacy parameters. DP has been leveraged for privacy-preserving releases of voltage and smart meter data streams from distribution systems, as well as records from PV and wind power plants [ 3 , 18 , 35 , 10 ] . To protect grid data used in power system computations, DP has been applied to randomize power flow optimization solvers [ 12 , 13 ] , dynamical simulations [ 4 ] , training of machine learning models [ 11 ] , and aggregated market-clearing statistics [ 41 ] , i.e., applications where sensitive data may be inferred from computational outcomes. The key challenge of DP randomization is that the perturbed data may lose modeling fidelity, become infeasible for the underlying analysis, or introduce new system risks. Post-processing optimization addresses this by restoring modeling fidelity while preserving the privacy guarantee, and has been applied to DP release of demand and transmission data to ensure cost-consistent power flow outcomes [ 16 , 10 ] and to prevent the synthesized data from being used to calibrate cyberattacks [ 39 ] . However, the application of post-processing optimization beyond steady-state power flow to power systems dynamics remains largely unexplored. The control community has focused on the privacy-preserving release of measurements [ 23 ] and inputs [ 24 ] for general dynamical systems, but no prior work has addressed DP release of the model itself. This gap is critical for power system dynamics, where model owners must simultaneously reproduce the electrical behavior of the source system and protect sensitive parameters (admittances, generation inertia and damping) that define it. Contributions: This work translates the success of DP in steady-state grid optimization [ 16 , 39 , 10 ] to power system dynamics. We develop algorithms for the public release of dynamic models with DP guarantees on sensitive parameters, such as inertia, damping, and admittance, while preserving modeling fidelity. Our technical contributions include: 1. We develop a principled algorithm for the public release of power system dynamic models. In the context of grid frequency dynamics, we release the model \dot{\omega}(t)=\tilde{f}(\omega(t),u(t)) such that the original f cannot be reverse-engineered from \tilde{f} , while the two models produce statistically similar frequency trajectories. 2. To obfuscate grid topology, we introduce a DP version of Kron reduction that injects calibrated noise into the source admittance, making reverse engineering in style of [ 30 , 8 ] infeasible up to prescribed DP parameters. 3. We formulate an ODE-constrained optimization to post-process DP grid parameters and recover modeling fidelity lost to DP noise. We propose a solution technique based on the adjoint method [ 5 ] , fitting the DP grid parameters to observable frequency trajectories, thus extending DP post-processing from steady-state grid optimization [ 16 , 39 , 10 ] to dynamical systems. Our algorithm contributes to the ongoing effort of synthesizing dynamic grid models, including the ENTSO-E model of the Pan-European grid [ 36 ] , where bus-level dynamics are initialized from standard models and tuned to match mean transients and dominant inter-area oscillation modes under a plant outage event. To support such efforts, we provide rigorous guarantees for source grids. Although focused on frequency dynamics as a case study, the approach generalizes to synchronous generator [ 22 ] , PSS [ 20 ] , AVR [ 38 ] , inverter models [ 17 ] , and to linear systems more broadly. Notation: Lower- (upper-) case boldface letters denote column vectors (matrices); \top stands for transposition; \mathbf{0}/\mathbf{1} are all-zero/one vectors. Scalar a_{i} is the i^{\text{th}} element of vector \mathbf{a} . The total and partial derivatives are denoted by \mathrm{d}_{x} and \partial_{x} , respectively. Projection of \mathbf{a} onto [\underline{a},\overline{a}] is denoted \mathcal{P}[\mathbf{a}]_{\underline{a}}^{\overline{a}} . II Preliminaries In this section, we introduce the reference model, discuss the privacy risks of releasing its parameters, and overview the classic Kron-reduction technique for model reduction. II-A Transmission Frequency Dynamics Consider a power transmission network with a connected directed graph (\mathcal{N},\mathcal{E}) , with a set \mathcal{N} of nodes (buses) and a set of \mathcal{E} edges (transmission lines). We define (i,j) as the transmission line between node i and j . We make the following common assumptions [ 6 ] : 1. All lines (i,j)\in\mathcal{E} are lossless and only characterized by their reactance x_{ij} . 2. Reactive power injections and flows are ignored. 3. Voltage magnitude of all buses are fixed. Based on these assumptions, this paper describes the linearized dynamics of the transmission network as \displaystyle\mathbf{M}\dot{\bm{\omega}} \displaystyle=\mathbf{K}\bm{\delta}+\mathbf{p}-\bm{\ell}-\mathbf{D}\bm{\omega} (1a) \displaystyle\dot{\bm{\delta}} \displaystyle=\bm{\omega} (1b) \displaystyle\dot{\mathbf{p}} \displaystyle=-\mathbf{T}(\mathbf{p}+\mathbf{R}\bm{\omega}) (1c) where the state variables include the vector \bm{\omega} of nodal frequencies, the vector \bm{\delta} of nodal voltage phase angles and the vector \mathbf{p} of mechanical power output of every node, with entries corresponding to non-generator nodes set to 0 . The disturbance is confined to load deviations, denoted by vector \bm{\ell} . All variables are deviations from their nominal values. The system design parameters include the diagonal matrices \mathbf{M} of generator inertia, \mathbf{D} of nodal damping, \mathbf{T} with diagonal elements being the inverse of governor/turbine time