Switching-Reference Voltage Control for Distribution Systems with AI-Training Data Centers
Mingyuan Yan, Trager Joswig-Jones, Baosen Zhang, Yize Chen, Wenqi Cui · 2026
Read Switching-Reference Voltage Control for Distribution Systems with AI-Training Data Centers by Mingyuan Yan, Trager Joswig-Jones, Baosen Zhang, Yize Chen, Wenqi Cui (2026) in the Tower of Babel, a free online library of public-domain works preserved in clean, searchable text. No sign-up. The full text is served as a plain-text file at a predictable URL, where text is present: https://antarctic-labs.com/tower-of-babel/arxiv-2603-15588.txt.
Introduction
Yan and co-authors design a voltage controller for power grids that feed AI training data centers. Such loads swing fast between two phases, which standard controllers treat as random noise. Their switching-reference design moves each bus reference in step with the workload phase. That cancels the phase-driven voltage shift at low control effort. Local voltage readings let each bus infer the phase with no live communication. Tests on real traces cut violations sharply, sometimes to zero, with about ten times less effort than droop control.
Catalog record
| CREATOR | Mingyuan Yan, Trager Joswig-Jones, Baosen Zhang, Yize Chen, Wenqi Cui |
|---|---|
| YEAR | 2026 |
| COLLECTION | PAPERS |
| FORMAT | TXT |
| FILE SIZE | 38785 |
| LICENSE | http://creativecommons.org/licenses/by/4.0/ |
| RIGHTS | CC BY |
| SOURCE | arXiv |
Source: https://arxiv.org/abs/2603.15588
Browse the full library · About the Tower of Babel
Full text
The opening of the work, from the library's hosted text:
Switching-Reference Voltage Control for Distribution Systems with AI-Training Data Centers Mingyuan Yan, Trager Joswig-Jones, Baosen Zhang, Yize Chen, Wenqi Cui Abstract Large-scale AI training workloads in modern data centers exhibit rapid and periodic power fluctuations, which may induce significant voltage deviations in power distribution systems. Existing voltage regulation methods, such as droop control, are primarily designed for slowly varying loads and may therefore be ineffective in mitigating these fast fluctuations. In addition, repeated control actions can incur substantial costs. To address this challenge, this paper proposes a decentralized switching-reference voltage control framework that exploits the structured behavior of AI training workloads. We establish conditions under which the reference-tracking error contracts and characterize a reference design aligned with the two dominant operating levels of the workload. The switching rule for voltage references is implemented solely using local voltage measurements, enabling simple decentralized implementation while significantly reducing control effort. Simulation studies show that the proposed method substantially reduces both voltage deviations and reactive power control effort, while remaining compatible with internal data center control strategies and requiring no extensive coordination. I Introduction The rapid growth of artificial intelligence (AI) has led to the deployment of increasingly large training workloads in hyperscale data centers. Empirical scaling laws show that model performance improves predictably with increasing model size, data, and computational budget [ 15 , 12 ] . As a consequence, electricity demand from AI training has also grown rapidly [ 1 ] . At the same time, the scale and geographic concentration of modern data centers make their power consumption an increasingly important factor in power system operation. At the distribution level, large data centers introduce a new class of highly dynamic loads. For example, recent industrial studies report that synchronized AI training workloads can produce large, periodic active-power ramps [ 7 ] . Unlike conventional electricity demand, which typically evolves gradually over time, AI training workloads can produce large and rapid power swings in the aggregate demand of a data center. When such loads are connected to a distribution feeder, these power swings propagate through the network and cause large voltage deviations. Without effective regulation, voltages may exceed their allowable limits. One common approach to voltage regulation in distribution systems is network-wide reactive power control. Traditionally, this has been achieved using mechanical devices such as tap-changing transformers, which are not suitable for frequent adjustments due to equipment lifespan limitations. Inverter-based resources, such as energy storage systems, can update their reactive power setpoints much more rapidly and have therefore emerged as valuable resources for voltage regulation. Accordingly, voltage droop control and its variants have been widely proposed to exploit this capability [ 14 , 23 , 4 , 9 ] . However, these methods are primarily designed for slowly varying loads and are not well suited to AI training workloads with rapid power fluctuations. Beyond grid-side voltage regulation, recent studies have also treated data centers as active participants by leveraging internal infrastructure for voltage support, including workload-aware power capping [ 18 ] , server-level power modulation [ 13 , 6 ] , coordinated control of UPS and cooling systems [ 21 ] , and GPU utilization control via batch size modulation [ 16 ] . Some works have further considered coordination with external grid assets by introducing new interface infrastructure, such as grid-forming battery energy storage systems providing line-interactive UPS functionality and dynamic active power support [ 3 , 17 ] , as well as coordination with external flexible resources like EV charging stations [ 11 ] . However, these approaches overlook the underlying power dynamics of modern AI training workloads, leading to unnecessarily large control effort with limited improvement in worst-case voltage deviations. Fig. 1: Per unit power readings from an at-scale training job on DGX H100 racks [ 7 ] . A representative AI training power trace is shown in Fig. 1 , characterized by rapid ramps and periodic fluctuations. This distinctive pattern arises from the distributed training of large AI models across multiple GPU racks: power demand increases substantially during computation in each training iteration and then drops sharply during communication. These abrupt load transitions constitute the dominant source of voltage deviations along the feeder. Since the most severe voltage violations arise during these abrupt transitions, existing regulation methods designed for smoothly varying loads may not respond sufficiently fast or deliver effective control actions to mitigate the worst violations. In addition, responding to repeated large power fluctuations may incur substantial control costs. In this work, we aim to answer the following question: How should we design a voltage control law to mitigate voltage deviations induced by AI training workloads, while avoiding excessive control effort? In this paper, we propose a decentralized switching-reference voltage control for distribution systems with AI-training data centers. The key idea is to exploit the structured switching dynamics of such loads to reduce worst-case voltage deviations with minimal control effort. We first characterize the two-mode structure of large-scale AI training workloads, and then design a switching-reference droop controller that aligns the voltage reference with the dominant operating level of the data center load. On this basis, we establish conditions for voltage convergence and characterize when voltage reference placement can effectively reduce voltage deviations. We further develop a rule for switching voltage references based solely on local voltage measurements, enabling simple local implementation while significantly reducing control effort. Case studies demonstrate that the proposed approach substantially reduces voltage deviations and reactive power control effort compared with conventional fixed-reference droop control. It remains effective under multiple data centers and data-center-level load smoothing, without the need for extensive coordination. II Network Model and Problem Formulation II-A Network Model and Data Center Power Characteristics We consider a radial distribution network with n buses, where a large data center is connected at the j -th bus. Let \bm{v}_{t},\bm{p}_{t},\bm{q}_{t}\in\mathbb{R}^{n} denote the vectors of bus voltage magnitudes, active power injections, and reactive power injections at time t . Following common practice, voltages are normalized so that the nominal value at all buses is 1 per unit (p.u.). We adopt the LinDistFlow model in [ 5 , 23 ] to characterize the bus voltages \bm{v}_{t}=\mathbf{R}\bm{p}_{t}+\mathbf{X}\bm{q}_{t}+\mathbf{1}, (1) where \mathbf{1} is the all-ones vector and \mathbf{R},\mathbf{X}\in\mathbb{R}^{n\times n} are positive definite matrices determined by the network topology and line impedances. Modern synchronized training workloads exhibit temporal structure in active power consumption that differs fundamentally from conventional slowly varying demand. As shown in Fig. 1 , the aggregate data center power exhibits repeated switching between two dominant operating levels with abrupt transitions. We refer to the high-power phase (forward and backward propagation) as the compute phase , and to the lower-power phase (synchronization and checkpointing) as the communication phase . Because accelerators (i.e., GPUs or TPUs) operate synchronously, the aggregate demand switches collectively between these two phases. Motivated by this temporal structure, we model active power injection at the data center bus j as p_{j,t}=\bar{p}_{j}(m_{t})+w_{t},\qquad|w_{t}|\leq\bar{w}(m_{t}), (2) where m_{t}\in\{0,1\} denotes the mode, with 0 for communication and 1 for computation. The injections \bar{p}_{j}(0) and \bar{p}_{j}(1) are the corresponding average demand, while w_{t} captures intra-phase fluctuations, and \bar{w}(m_{t}) specifies a mode-dependent bound on these fluctuations. During large-scale AI training, short-term active power variation is dominated by training workload within the data