Transferring the driveshaft inertia to the grid via the DC-link in MV drive systems

Catalin Arghir, Pieder Jörg, Silvia Mastellone · 2025

Read Transferring the driveshaft inertia to the grid via the DC-link in MV drive systems by Catalin Arghir, Pieder Jörg, Silvia Mastellone (2025) in the Tower of Babel, a free online library of public-domain works preserved in clean, searchable text. No sign-up. The full text is served as a plain-text file at a predictable URL, where text is present: https://antarctic-labs.com/tower-of-babel/arxiv-2508-21760.txt.

Introduction

Catalin Arghir, Pieder Jörg, and Silvia Mastellone show how a spinning shaft can steady the power grid in a 2025 engineering paper. Medium-voltage motor drives store energy in their rotating driveline. The authors modify the speed control signal and the DC-link control so that this inertia appears, in effect, on the grid side. Two control designs are compared, one classic cascade and one that mimics a synchronous machine.

Both grid-connection schemes, they show, can be read as feedback optimization with different steady behaviors. That lens reveals a hidden phase-locked loop inside the matching design, plus current-limiting and tracking strengths. Simulations back the claims. Drives that lend their inertia could help grids ride through faults.

Catalog record

CREATORCatalin Arghir, Pieder Jörg, Silvia Mastellone
YEAR2025
COLLECTIONPAPERS
FORMATTXT
FILE SIZE34 KB
VERSION1.0
LICENSEhttp://creativecommons.org/licenses/by/4.0/
RIGHTSCC BY
SOURCEarXiv

Source: https://arxiv.org/abs/2508-21760

Browse the full library · About the Tower of Babel

Full text

The opening of the work, from the library's hosted text:

Transferring the driveshaft inertia to the grid via the DC-link in MV drive systems Catalin Arghir, Pieder Jörg, Silvia Mastellone Abstract This paper investigates a control approach that renders the driveshaft inertia completely available on the grid side and enhances the fault ride-through behavior of medium-voltage (MV) drive systems. Two main contributions are presented. First, we show how the rotational inertia of the driveline shaft can be synchronously coupled to the grid through a modification of the speed control reference signal and through an adapted DC-link control strategy. For the latter, we pursue two alternatives: one based on conventional cascaded control and another based on synchronous machine (SM) model matching. Second, we demonstrate that both the standard phase-locked loop (PLL) and the matching control approach can be interpreted, via the ray–circle complementarity, as feedback optimization schemes with distinct steady-state maps. This perspective allows us to revisit matching control, reveal its embedded PLL, highlight its current-limiting and tracking capabilities, and provide an extensive simulation study. I INTRODUCTION Medium-voltage (MV) drive systems play a central role in high-power industrial processes, electric propulsion, renewable and conventional energy generation [ 1 , 2 ] . Such processes are grid-connected through converters supplying a complex driveline through one or more electric machines. When equipped with an active front end—particularly in the high-power MV range—such drives are increasingly expected to contribute beyond basic specifications, by providing ancillary services such as inertia, phase jump support, and reactive power compensation [ 3 ] . Ubiquitous in wind applications, emerging standards such as IEEE 1547.3 and IEC 61400 are becoming relevant to large industrial drives [ 4 ] , prompting them to support the natural behavior of the synchronous machine [ 5 , 6 ] . While substantial attention has been paid to motor-side control [ 7 ] and grid-side compliance [ 8 , 9 , 10 ] , less is understood about how mechanical energy stored in the drivetrain can interact dynamically with the grid [ 11 , 12 ] , for example, in cases where torsional resonances overlap with sub-synchronous harmonics. In this work, we adopt an interconnected viewpoint and show how, whether acting as generators or loads, MV drive systems can play a significant role in grid stabilization. In the context of inertia emulation, grid-forming converters have been extensively investigated as virtual synchronous machines [ 13 , 14 ] , but these techniques typically require explicit virtual models or control augmentation. Our work is thus distinct in combining: ( i ) a first-principles treatment of synchronization mechanisms (PLL and matching control) as gradient-based algorithms; ( ii ) a demonstration of natural inertia transfer by physical energy coupling while satisfying current limits, tracking performance, and providing voltage support; ( iii ) a comparative study under realistic grid events using a high-fidelity simulation of an industrial drive system. We build on the control-theoretic foundations of [ 15 ] , which provides stability guarantees for both single- and multi-inverter settings. A key feature of this framework is the inherent passivity induced by matching control, ensuring a robust grid interaction [ 16 ] . Furthermore, we highlight its connection to the Online Feedback Optimization (OFO) paradigm [ 17 ] , which points to potential future research. To enable a fair comparison, we propose a modification to the reference signals in the classical cascaded-control structure. By using the same pumped-hydro drive setup as in [ 18 ] , we further expand in the direction of drive availability, and provide a benchmark scenario for the matching approach. The remainder of this paper is structured as follows. Section II presents the modeling framework and coupling control formulation. Section III revisits the standard PLL and matching control. Section IV presents the experimental results, and Section V concludes the paper with a discussion of implications for future drive system control design. II Drive system control We consider a back-to-back drive system consisting of a grid-side converter, a DC-link capacitor, a motor-side converter, an electrical machine, and a flexible driveshaft attached to a prime mover or a load. The main role of the grid-side converter, is to deliver active power by regulating the DC-link voltage, and thus allow the motor-side converter to supply the load under a wide range of external conditions. II-A Drive system model We adopt an energy-preserving, average-switch model of a back-to-back drive system with a 2-mass driveshaft \displaystyle L_{g}\dot{i}_{g} \displaystyle=-R_{g}i_{g}+v_{g}-m_{g}v_{dc} (1a) \displaystyle C_{dc}\dot{v}_{dc} \displaystyle=-G_{dc}v_{dc}+m_{g}^{\top}i_{g}-\tfrac{{\tau}_{m}}{v_{dc}}{w}_{1} (1b) \displaystyle\dot{x}_{1} \displaystyle=w_{1} (1c) \displaystyle M_{1}\dot{w}_{1} \displaystyle=-C_{12}(w_{1}-w_{2})-K_{12}(x_{1}-x_{2})+\tfrac{{\tau}_{m}}{v_{dc}}v_{dc} (1d) \displaystyle\dot{x}_{2} \displaystyle=w_{2} (1e) \displaystyle M_{2}\dot{w}_{2} \displaystyle=-C_{12}(w_{2}-w_{1})-K_{12}(x_{2}-x_{1})-\tau_{l}\,, (1f) where M=M_{1}\!+\!M_{2} is the total moment of inertia of the driveshaft, C_{12} is the damping coefficient and K_{12} is the spring coefficient of the coupling between the two masses, w_{1},w_{2} are the angular velocities of the two shaft sections, x_{1},x_{2} their absolute angles, {\tau}_{m} the motor torque reference (control input), and \tau_{l} is the driveshaft load torque (unmeasured disturbance). Note that this model exhibits a torsional natural frequency (TNF), and requires active damping or filtering out of the feedback loop. The DC-link voltage v_{dc} is modeled across a capacitance C_{dc} in parallel with a conductance G_{dc} . Furthermore, m_{g}\in\mathbb{R}^{2} is the grid-side converter \alpha\beta -modulation vector (control input), L_{g},{R}_{g}>0 phase inductance and resistance, respectively, i_{g}\in\mathbb{R}^{2} is the grid-side converter current and v_{g}\in\mathbb{R}^{2} is the PCC voltage in \alpha\beta -coordinates (measured disturbance). We use the well established notions of instantaneous power [ 19 ] and the power-invariant \alpha\beta -frame transformation as \displaystyle x_{abc}\mapsto x_{dq0} \displaystyle={T}_{\theta}T_{\alpha\beta\gamma}x_{abc}={T}_{\theta}x_{\alpha\beta\gamma}\,, (2) with T_{\alpha\beta\gamma}^{-1}=T_{\alpha\beta\gamma}^{\top} , and where {T}_{\theta}=\mathrm{blkdiag}({R}_{\theta},1) , with {R}_{\theta}=\begin{bmatrix}\begin{smallmatrix}\cos\theta&-\sin\theta\\ \sin\theta&\cos\theta\end{smallmatrix}\end{bmatrix} being the rotation matrix. Moreover, by virtue of the third-harmonic injection, the maximum modulation amplitude in \alpha\beta -coordinates becomes \tfrac{1}{\sqrt{2}} . In the rest of this paper we only consider the first two components, namely the two-dimensional vector x_{dq} or x_{\alpha\beta} . We are therefore able to define the (instantaneous) active and reactive power for quantities in either dq or \alpha\beta as \displaystyle P \displaystyle=v_{\alpha\beta}^{\top}i_{\alpha\beta}=v_{dq}^{\top}i_{dq} (3) \displaystyle Q \displaystyle=v_{\alpha\beta}^{\top}Ji_{\alpha\beta}=v_{dq}^{\top}Ji_{dq}\,, (4) where J={R}_{\pi/2} . As we shall see, we only need the dq transformation for the integral term of the PI current control to ensure tracking of a harmonic reference, and henceforth all equations can be equivalently expressed in either coordinates. Remark 1 In this model, we omit the motor and its torque control dynamics, an abstraction which enables us to focus on the grid-side behavior and its interaction with the shaft dynamics. II-B Drive system objectives On a high level, the driveshaft is required to rotate at a given speed while the grid-side converter supplies the motor-side converter with a stable voltage. The tracking objectives \displaystyle{w}_{1},w_{2} \displaystyle\rightarrow{w}^{\mathrm{ref}} (5) \displaystyle v_{dc} \displaystyle\rightarrow v_{dc}^{\mathrm{ref}} (6) are meant to reject the external disturbance (\tau_{l},v_{g}) . Moreover, |{w}^{\mathrm{ref}}|\leq w_{\mathrm{nom}} is an external set-point, while |\tau_{l}|\leq\tau_{\mathrm{nom}} , \|v_{g}\|\leq v_{g,\mathrm{nom}}=\alpha_{v}v_{g,\mathrm{nom}} with e.g. \alpha_{v}=1.1 representing a grid code overvoltage limit. We also consider some margin for producing reactive power necessary for the loose regulation of the PCC voltage magnitude v_{g} . \displaystyle\tau_{\mathrm{nom}}w_{\mathrm{nom}}=P_{g,\mathrm{nom}}=\tfrac{1}{\alpha_{q}}\sqrt{P_{g,\mathrm{nom}}^{2}+Q_{g,\mathrm{nom}}^{2}}\,, (7) where e.g. \alpha_{q}=1.2 is a de-rating factor, such that the maximum current amplitude becomes i_{g,\mathrm{nom}}=\tfrac{\alpha_{q}P_{g,\mathrm{nom}}}{v_{g,\mathrm{nom}}} . In a classical back-to-back drive system, the control strategy is a two-fold tracking cascade, one on the load side (a speed regulator provides reference to the inner torque regulator), and one on the grid-side (a DC-link

Read the complete text