Development of Reduced Feeder and Load Models Using Practical Topological and Loading Data This work has been funded by Salt River Project.

Sameer Nekkalapu 1 , Sushrut Thakar 2 , Antos Cheeramban Varghese 3 , Vijay Vittal 3 , Bo Gong 4 , Ken Brown 4 1 Pacific Northwest National Laboratory, WA, USA ; 2 Electric Power Research Institute, TN, USA ; 3 Arizona State University, AZ, USA ; 4 Salt River Project, AZ, USA · 2025

Read Development of Reduced Feeder and Load Models Using Practical Topological and Loading Data This work has been funded by Salt River Project. by Sameer Nekkalapu 1 , Sushrut Thakar 2 , Antos Cheeramban Varghese 3 , Vijay Vittal 3 , Bo Gong 4 , Ken Brown 4 1 Pacific Northwest National Laboratory, WA, USA ; 2 Electric Power Research Institute, TN, USA ; 3 Arizona State University, AZ, USA ; 4 Salt River Project, AZ, USA (2025) in the Tower of Babel, a free online library of public-domain works preserved in clean, searchable text. No sign-up. The full text is served as a plain-text file at a predictable URL, where text is present: https://antarctic-labs.com/tower-of-babel/arxiv-2505-06439.txt.

Introduction

Sameer Nekkalapu and co-authors shrink a real power utility's feeder models until they run fast, without losing the behaviors that matter, in a 2025 paper. Distribution studies need models that are faithful yet light; full detail is too slow. Their algorithm builds reduced feeder and load models straight from the utility's own topology and loading data, rather than from textbook guesses.

In simulation, the reduced model of a real feeder reproduced the critical events engineers fear: contactors dropping out and motors stalling during fault-induced delayed voltage recovery. That fidelity, at a fraction of the compute, is the point of reduction done right. The work was funded by the Salt River Project, whose network supplied the data. The authors offer the method to utilities planning studies of rooftop solar, electric vehicles, and storm recovery.

Catalog record

CREATORSameer Nekkalapu 1 , Sushrut Thakar 2 , Antos Cheeramban Varghese 3 , Vijay Vittal 3 , Bo Gong 4 , Ken Brown 4 1 Pacific Northwest National Laboratory, WA, USA ; 2 Electric Power Research Institute, TN, USA ; 3 Arizona State University, AZ, USA ; 4 Salt River Project, AZ, USA
YEAR2025
COLLECTIONPAPERS
FORMATTXT
FILE SIZE23 KB
VERSION1.0
LICENSEhttp://creativecommons.org/licenses/by/4.0/
RIGHTSCC BY
SOURCEarXiv

Source: https://arxiv.org/abs/2505-06439

Browse the full library · About the Tower of Babel

Full text

The opening of the work, from the library's hosted text:

Development of Reduced Feeder and Load Models Using Practical Topological and Loading Data This work has been funded by Salt River Project. Sameer Nekkalapu 1 , Sushrut Thakar 2 , Antos Cheeramban Varghese 3 , Vijay Vittal 3 , Bo Gong 4 , Ken Brown 4 1 Pacific Northwest National Laboratory, WA, USA ; 2 Electric Power Research Institute, TN, USA ; 3 Arizona State University, AZ, USA ; 4 Salt River Project, AZ, USA Abstract Distribution feeder and load model reduction methods are essential for maintaining a good tradeoff between accurate representation of grid behavior and reduced computational complexity in power system studies. An effective algorithm to obtain a reduced order representation of the practical feeders using utility topological and loading data has been presented in this paper. Simulations conducted in this work show that the reduced feeder and load model of a utility feeder, obtained using the proposed method, can accurately capture contactor and motor stalling behaviors for critical events such as fault induced delayed voltage recovery. I Introduction Representation of the distribution system behavior in power system studies requires accurate feeder and load models [ 1 ] . The composite load model (CMPLDWG) is the state-of-the-art model for incorporating loads adequately into system planning and operation studies [ 2 ] . However, the composite load model represents the distribution feeders as an aggregated load at a single bus behind a feeder impedance [ 3 ] . Currently, efforts are being undertaken by the industry vendors to modularize the composite load model to improve the model flexibility in terms of better representation of the load behavior such as the motor stalling phenomenon which leads to fault induced delayed voltage recovery (FIDVR) type critical events in the system [ 4 ] . This is because the current version of the composite load model do not capture partial motor stalling behavior in which typically only motors in some sections of the feeder stalls depending on the voltage magnitude and the angle seen at their terminals at the moment of fault initiation [ 4 ] , [ 5 ] . It is especially important to capture this partial motor stalling phenomenon in the presence of their protection models, contactors [ 3 ] , to not overestimate or underestimate the resiliency of the distribution system under critical events such as the FIDVR type phenomenon. Therefore, in recent literature, a state-of-the-art three-segment feeder and load model has been developed for modeling the distribution systems behavior, in the grid [ 6 , 5 , 3 ] . This feeder and load model has the capability to accurately capture both the necessary phenomenon – partial motor stalling and accurate contactor behavior, to accurately estimate the feeder behavior for FIDVR type critical events. However, this is dependent on having an accurate estimate of the feeder and load parameters for this model. In [ 6 ] , an optimization algorithm has been proposed to estimate the load parameters provided in this paper and in [ 5 ] , a data-driven deep neural network technique has been developed to estimate the contactor and motor stalling parameters. However, all these parameters were obtained by making simplistic assumptions about the voltage drops across the three-segment feeder model without validating it using field topological or measurement data across the feeders. Therefore, the main objective of this paper is to develop a systematic approach, while utilizing practical field data, to obtain a realistic reduced three-segment feeder model that can accurately capture the dynamic characteristics of a feeder comprising of contactors and the motor load behavior. The authors of [ 7 ] model a real network including 15 feeders in detail and study the FIDVR response and motor stalling. However, they do not conduct dynamic simulations but rather rely on time series power flow to estimate the FIDVR response. The increased network size by modeling all the distribution feeders in detail (including the entire network) may not be suitable for dynamical simulations of larger networks owing to computational complexity. This computational complexity issue can be mitigated by reducing the distribution system model to an equivalent lower order model. [ 8 ] proposed a load area-based approach for the simplification of the distribution system. Generalized analytical methods were proposed in [ 9 ] to create a reduced order feeder model. However, [ 8 , 10 , 9 ] do not capture the dynamic behaviors of the distribution systems. A ruin and reconstruct-based feeder reduction method is proposed in [ 11 ] for modeling feeders in real-time simulators. Although, these methods are good ways to reduce distribution system model order, they have not been tested using field data. None of these approaches [ 12 , 7 , 8 , 10 , 9 ] considered using utility topological data to obtain an accurate feeder structure which would be crucial in the process of the load modeling studies. This paper proposes an effective method to model a three-segment feeder model for distribution load modeling studies using practical topological feeder data obtained from a local utility in the South Western U.S. The proposed reduced feeder model is extremely useful for applications such as load composition and load parameter estimation [ 13 ] and contactor modeling [ 5 ] . The key contributions of this paper are as follows: (1) An algorithm based on utilizing the feeder topological and loading data to reduce the distribution system into three segments is proposed. This reduced-order feeder model can be leveraged by the utilities to conduct accurate distribution system studies without any computational complexity issues that come with representing detailed distribution feeder models. (2) The impact of utilizing the proposed modified three-segment feeder model to estimate the contactor behavior and motor stalling phenomenon accurately on the feeder behavior under critical FIDVR type phenomena has been demonstrated. In this paper, Section II provides the critical parameter details of the contactors and motor models used in this work. In Section III , the proposed methodology to create the reduced feeder model and its validation using the topological and loading data obtained from the local utility has been presented. Section IV investigates the performance comparison between the proposed modified three-segment feeder model with the existing state of the art three-segment feeder model [ 5 ] in the literature. The conclusions of this work are present in Section V . All the simulations in this work have been conducted in an electromagnetic transient (EMT) simulator (PSCAD) [ 14 ] . II Case Setup: Contactor & SPHIMS Stalling Modeling The three-segment three-phase feeder and load model considered in this work has been presented in Fig. 1 . The considered feeder model comprises of three-phase motor load, single-phase motor load (SPHIMs), resistive load and distribution transformers that step down the voltage from feeder head level (12.47 kV) to their respective rated low voltage load levels. More description about the contactor and the SPHIMs models modeling has been presented below - II-A Contactor Modeling A Contactor is an electromechanical device which trips the load (SPHIMs in this paper) under low voltage conditions. Typically, when there is a fault in the system, the voltage at the terminals of the contactor (and load) is depressed which leads to the contactor tripping

Read the complete text