Analyzing the Impact of AC False Data Injection Attacks on Power System Operation

1 st Mohammadreza Iranpour, 2 nd Mohammad Rasoul Narimani · 2025

Read Analyzing the Impact of AC False Data Injection Attacks on Power System Operation by 1 st Mohammadreza Iranpour, 2 nd Mohammad Rasoul Narimani (2025) in the Tower of Babel, a free online library of public-domain works preserved in clean, searchable text. No sign-up. The full text is served as a plain-text file at a predictable URL, where text is present: https://antarctic-labs.com/tower-of-babel/arxiv-2502-20473.txt.

Introduction

Power grids run on sensor readings, and an attacker who quietly alters those readings can steer operators wrong. Mohammadreza Iranpour and Mohammad Rasoul Narimani study false data injection against the alternating-current model of the grid, the realistic one. Such attacks can slip past the bad-data detectors that guard control rooms.

Using the PowerWorld simulator on a standard thirty-nine-bus test grid, they compare attack designs head to head. Attacks tuned to be maximally stealthy changed the targeted readings less than crude attacks did. Counterintuitively, their physical impact on the grid was also often smaller. The authors frame attack design as a trade-off between hiding and harming. Their unified approach lets defenders test both kinds of attacks in one place.

Catalog record

CREATOR1 st Mohammadreza Iranpour, 2 nd Mohammad Rasoul Narimani
YEAR2025
COLLECTIONPAPERS
FORMATTXT
FILE SIZE26 KB
VERSION1.0
LICENSEhttp://creativecommons.org/licenses/by/4.0/
RIGHTSCC BY
SOURCEarXiv

Source: https://arxiv.org/abs/2502-20473

Browse the full library · About the Tower of Babel

Full text

The opening of the work, from the library's hosted text:

Analyzing the Impact of AC False Data Injection Attacks on Power System Operation Thanks: This work has been supported from NSF contract #2308498. 1 st Mohammadreza Iranpour, 2 nd Mohammad Rasoul Narimani Abstract False Data Injection (FDI) attacks are a significant threat to modern power systems. Although numerous research studies have focused on FDI attacks on power systems, these studies have primarily concentrated on designing or detecting DC FDI attacks, with less attention given to the impact analysis of AC FDI attacks. AC FDI attacks are potentially more harmful as they can easily bypass bad data detection (BDD) algorithms. In this paper, we present a unified approach to investigate the impact of AC FDI attacks on power transmission lines using the PowerWorld simulator. We also investigate the impact of different FDI attack designs, including those optimally designed to evade BDD algorithms and compare them accordingly. Our findings demonstrate that in designing optimal AC FDI attacks, a trade-off between the residuals of state variables and the corresponding impacts of the proposed attack should be considered. This is because optimal attacks result in fewer changes in the attacked variable states and their estimated residuals compared to arbitrary AC FDI attacks. Moreover, the impacts of optimal AC FDI attacks can be less severe than those of arbitrary attacks. We implement and analyze the proposed approach on the IEEE 39-bus test system using PowerWorld simulator. I Introduction In recent years, the use of communication and control devices in electric power grids has significantly improved power systems’ operation, enhancing both reliability, controllability, and efficiency. However, these systems have also become more vulnerable due to the presence of cyber elements with a high potential for anomaly intrusion. False Data Injection (FDI) attacks have been recognized as an important category of cyberattack that threatens the secure operation of power systems. An FDI attack is a type of cyberattack designed to deliver false information, intending to mislead or disrupt system operations [ 1 ] . In a general FDI attack scenario, an attacker injects an arbitrary amount of error into the system’s state estimator by hacking sensors and measurement units [ 2 , 3 ] . If this attack vector fulfill certain conditions, the FDI will pass commonly used residue-based bad data detectors while evades system estimator and misleading it [ 4 , 5 , 6 , 7 , 8 ] . Several studies over the past decade have reviewed FDI attacks from various perspectives. In addition to construction methods, goals, and consequences of FDIAs from the attackers’ perspective, as well as detection and defense strategies reviewed in [ 9 ] , FDI attacks can be analyzed based on their impacts on power system operations [ 10 ] . Depending on various factors in designing an FDI attack, such as locations, numbers, sequence of injecting false data, or values of the compromised devices, the impact of FDI attacks may range from vandalizing critical infrastructure to gaining specific economic advantages or benefits [ 1 ] . Generally, after conducting an FDI attack, the state estimator generates a wrong set of inputs for various control algorithms, such as optimal power flows, contingency analysis, economic dispatch, stabilizer units, or other controllers in the power system. Subsequently, these incorrectly generated control actions might initiate the system destabilization process, possibly leading to a collapse [ 11 ] . Power flow algorithms are essential for the reliable operation of power systems [ 12 , 13 , 14 , 15 , 16 , 17 ] . Attackers can mislead operators by adjusting some power flow measurements, making them appear as real measurements. Based on this incorrect analysis, the controlling algorithm may trigger the relay protection system to open certain breakers, isolating branches and interrupting the normal operation of the system, potentially leading to a power outage [ 10 ] . Numerous studies have investigated conducting FDI attacks on power systems. For example, in [ 10 ] , attackers designed an attack strategy based on AC power flow equations by selecting the target power transmission line. In [ 18 ] and [ 19 ] , it has been shown that FDI attacks can disconnect multiple power transmission lines within the attack zone or cause significant changes in the power flow of the grid. Suspicious changes in power flow variations in power transmission lines due to FDI attacks, based on the Power Transfer Distribution Factor (PTDF), have been analyzed in [ 20 ] . The impacts of FDI attacks on the security, operation, and economics of power systems have been analyzed using the optimal power flow in [ 21 ] . It has been shown that if metering devices contain massively corrupted measurements, existing FDI attacks can be detected in the system [ 22 ] , but these studies have not shown how FDI attacks can cause large variations in transmission line power flow. In all of these studies, the impacts of an FDI attack on transmission line power flow have not been empirically analyzed. A mathematical method based on matrix analysis and graph theory is presented in [ 23 ] to quantify how attacking a predetermined set of power transmission lines with a DC-based FDI attack can affect power flow changes. Although [ 23 ] presented a mathematical analysis for investigating the impacts of an FDI attack on the transmission lines’ power flow, their approach is based on the DC power flow, making their FDI attack easily detectable by BDD algorithms. To address this, we proposed an approach for designing an AC-based FDI attack in the power system. The impact of various FDI attacks differs on the power system; we recently designed an optimal AC FDI attack scheme to design FDI attacks with minimum changes in state variables [ 2 ] . Designing an optimal FDI attack results in a lower residual estimation vector compared to the residuals of estimation with arbitrary attack vectors. Thus, the optimal FDI attacks have a higher chance of dodging the BDD algorithm. Although slight changes in state variables lead to lower residuals, the impact of the designed FDI attack on the power system is lesser. In this connection, the attacker must trade-off between having residuals and FDI attack impact. This paper analyzes the impacts of different AC FDI attacks on the transmission lines’ power flow. We used PowerWorld software to demonstrate the impact of FDI attacks on the power flows in power transmission lines. The rest of this paper is organized as follows: Section II briefly describes the approach for designing AC FDI attacks and how the designed attacks impact power systems. Section III , presents the simulation results of the IEEE 39-bus test system. Section IV concludes the paper. II AC FDI attack Impact on Power Systems Analyzing the impacts of AC False Data Injection (FDI) attacks on power systems involves a systematic process to understand how such attacks affect system operation. The first step in this process is to understand the mechanism of designing an AC FDI attack, identifying the components and corresponding variables that need to be manipulated for a successful attack. In the second step, based on the injected attack vector to the attacked measurements, the values of these measurements and the corresponding estimation residuals of

Read the complete text